• 제목/요약/키워드: expansion performance

검색결과 1,724건 처리시간 0.034초

병렬팽창 냉동시스템의 성능실험에 관한 실험적 연구 (An Experimental Study on the Performance Testing of Parallel Expansion Refrigeration System)

  • 구창대
    • 한국산업융합학회 논문집
    • /
    • 제14권2호
    • /
    • pp.79-85
    • /
    • 2011
  • This study has been experimented about refrigeration capacity difference. It has been used 3 method, Manual expansion valve, thermostatic expansion valve and capillary expansion valve, and tested under the same condition by using the performance testing of parallel expansion. In temperature change of the temperature room, thermostatic expansion valve method displayed the most lower temperature, $-18^{\circ}C$. In addition, the temperature, just before the expansion, also displayed the best result which was $4^{\circ}C$ lower than other expansion valve. In these results, it can be used for performance testing of parallel expansion refrigeration system.

인버터형 냉동시스템의 팽창장치 변경에 따른 성능특성 (Performance of an inverter refrigeration system with a change of expansion devices)

  • 이용택;김용찬;박윤철;김민수
    • 설비공학논문집
    • /
    • 제11권6호
    • /
    • pp.928-936
    • /
    • 1999
  • An experimental study was performed to investigate characteristics of an inverter driven water-to-water refrigeration system with a variation of compressor frequencies and expansion devices. The frequency of a compressor varied from 30Hz to 75Hz, and performance of the systems applying three different expansion devices such as capillary tube, thermostatic expansion valve(TXV), and electronic expansion valve(EEV) were measured. The load conditions were altered by varying the temperature of the secondary fluid entering condenser and evaporator with a constant flow rate. When the test conditions were deviated from the standard value(rated value), TXV and EEV showed better performance than capillary tube due to optimum control of mass flow rate and superheat. In the present study, it was observed that the variable area expansion device had better performance than constant area expansion device in an inverter refrigeration system due to active control of flow area with a change of compressor frequency and load conditions.

  • PDF

지하구조물용 신축이음장치의 방수성능에 관한 실험연구 (An Experimental Study on the Waterproofing Performance of Expansion Equipment for Underground Structures)

  • 이영호
    • 한국산학기술학회논문지
    • /
    • 제13권9호
    • /
    • pp.4302-4309
    • /
    • 2012
  • 지하구조물에 적절한 신축이음을 두지 않게 되면, 신축량에 대응하지 못해 구조물에 구조적 균열과 누수로 인한 콘크리트의 백태 등이 발생할 수 있다. 본 연구에서는 방수성능과 내구성이 우수한 새로운 지하구조물용 신축이음 장치에 대한 성능을 검증하였다. 유한요소해석을 통하여 지하구조물 신축이음장치의 간격을 설정하고 개발된 신축이음장치의 적정 신축량을 확인하였다. 또한, 검증실험결과 개발된 신축이음장치의 수축 신장에 따른 피로 기준을 만족하였으며 방수성능이 우수한 것으로 나타났다.

공조.냉동장치의 제어시스템 개발을 위한 팽창밸브 특성 (Expansion Valves Characteristics for Development of Control System on Air Conditioning and Refrigeration Systems)

  • 김재돌;장재은;윤정인
    • 동력기계공학회지
    • /
    • 제2권3호
    • /
    • pp.34-40
    • /
    • 1998
  • Performance characteristics of a refrigeration systems with various expansion valves and superheat changes were investigated experimentally. Experimental data have been taken utilizing three different devices; a thermostatic expansion valve, a linear type electronic expansion valve and a solenoid type electronic expansion valve. The data taken from tile three types of expansion valves were discussed with the temperature distribution of each zone in the evaporator and the superheat changes of the evaporator outlet In each zone temperature distribution fluctuated larger with the thermostatic expansion valve than with the electronic expansion valves. The optimum superheat ranged from $5^{\circ}C\;to\;15^{\circ}C$, and the superheat with the thermostatic expansion valve showed hunting phenomenon, which affected the evaporating and condensing temperature.

  • PDF

국내 해외진출 기업의 시장지향성과 최고경영자역량 및 해외시장 환경특성이 해외진출성과에 미치는 영향 (The effects of market orientation, CEO capacity and environmental characteristics of companies expanding to overseas markets on their performance)

  • 김민주;오진호;박근식
    • 무역학회지
    • /
    • 제45권5호
    • /
    • pp.303-324
    • /
    • 2020
  • The objective of this study is to verify the effect of the market orientation, CEO capacity, and environmental characteristics of overseas markets on the performance of overseas expansion among the success factors of domestic overseas expansion companies. For this purpose, employees of domestic overseas companies based in the Seoul metropolitan area were surveyed, and the hypothesis test was conducted. As a result of the verification, among the contributors to overseas advancement of domestic overseas companies, the factors of CEO capacity, overseas business_education ability, market environment and market size have a significant positive effect on the financial performance of overseas expansion. However, market-oriented factors were found to have no significant effect on the financial performance of overseas expansion. Among the contributors to overseas advancement of domestic overseas companies, the market-oriented factor, the customer-oriented factor, has a significant positive effect on the non-financial performance of overseas expansion. However, factors in CEO competency and environmental characteristics in overseas markets do not have a significant positive effect on the non-financial performance of overseas expansion.

Expansion performance and mechanical properties of expansive grout under different curing pressures

  • Yiming Liu;Yicheng Ye;Nan Yao;Changzhao Chen
    • Geomechanics and Engineering
    • /
    • 제33권4호
    • /
    • pp.327-339
    • /
    • 2023
  • The expansion capacity and strength of expansive grout have a significant influence on the stress state of a supported rock mass and the strength of a grout-rock mass structure. The expansion and strength characteristics are vital in grouting preparation and application. To analyze the expansion performance and mechanical properties of expansive grout, uniaxial compressive strength (UCS) tests, expansion ratio tests, XRD, SEM, and microscopic scanning tests (MSTs) of expansive grout under different curing pressure conditions were conducted. The microevolution was analyzed by combining the failure characteristics, XRD patterns, SEM images, and surface morphologies of the specimens. The experimental results show that: (1) The final expansion ratio of the expansive grout was linear with increasing expansion agent content and nonlinear with increasing curing pressure. (2) The strength of the expansive grout was positively correlated with curing pressure and negatively correlated with expansion agent content. (3) The expansion of expansive grout was related mainly to the development of calcium hydroxide (Ca(OH)2) crystals. With an increase in expansion agent content, the final expansion ratio increased, but the expansion rate decreased. With an increase in the curing pressure, the grout expansion effect decreased significantly. (4) The proportion of the concave surfaces at the centre of the specimen cross-section reflected the specimen's porosity to a certain extent, which was linear with increasing expansion agent content and curing pressure.

이산화탄소 사이클에서 팽창장치의 영향에 관한 수치적 연구 (Numerical Study for the Effect of Expansion Device on the Performance of the $CO_2$ Cycle)

  • 김무근;김욱중;김유진
    • 설비공학논문집
    • /
    • 제16권1호
    • /
    • pp.84-90
    • /
    • 2004
  • In order to evaluate the performance of carbon dioxide cycle, a simulation model was developed to predict the steady state performance of $CO_2$ transcritical cycle. The expansion process is treated as an isenthalpic throttling process or isentropic expansion process. The mathematical model is based entirely on the basic energy conservation law and thermodynamic and transport properties of $CO_2$. A Parametric study has been conducted in order to investigate the effect of isentropic efficiency of expansion turbine and various operating conditions on the cycle performance. An optimal heat rejection pressure existed for the given evaporating temperature and outlet temperature of gas cooler.

Airborne Sound Insulation Performance of Window and Indoor Noise Level in the Balcony Expanded Apartments

  • Park, Hyeon Ku
    • KIEAE Journal
    • /
    • 제15권2호
    • /
    • pp.61-67
    • /
    • 2015
  • Purpose: The balcony in the apartment is important space not only as a fire escape but also as a buffer for heat and sound insulation. However, with the legalization of balcony expansion for residential apartments in Korea in 2006, many households have eliminated the balcony space altogether to increase the inner space, often without sufficient consideration for the effects on the indoor environment. This study examined the sound insulation performance of exterior-facing windows in enclosed balconies and the changes in the indoor acoustic environment due to expansion to provide a basis for appropriate balcony expansion. The apartments for the field test were chosen where two balcony types can be compared, and the sound insulation performance for the eighteen balcony windows was measured. The windows installed were typical double window with thickness 16 mm or 22 mm. Measurements of the weighted standard sound pressure level difference showed a decrease of about 3 dB in sound insulation performance due to expansion. For common exterior noise levels of 70-85 dB(A), the indoor noise level can exceed 45 dB(A), the limit level regulated in Korea. However, it was found that the sound insulation performance of the window and the quality of the construction have more influence on indoor noise levels than balcony expansion itself.

열펌프의 성능 최적화에 관한 연구 (Optimization of Heat Pump Systems)

  • 최종민;윤린;김용찬
    • 신재생에너지
    • /
    • 제3권4호
    • /
    • pp.22-30
    • /
    • 2007
  • An expansion device plays an important role in optimizing the heat pumps by controlling refrigerant flow and balancing the system pressures. Conventional expansion devices are being gradually replaced with electronic expansion valves due to increasing focus on comfort, energy conservation, and application of a variable speed compressor. In addition, the amount of refrigerant charge in a heat pump is another primary parameter influencing system performance. In this study, the flow characteristics of the expansion devices are analyzed, and the effects of refrigerant charge amount on the performance of the heat pump and the variation of compressor speed are investigated at various operating conditions. Mass flow rate through capillary tube, short tube orifice, and EEV was strongly dependent on the upstream pressure and subcooling. The heat pump system is very sensitive with a variation of refrigerant charge amount. The performance of it can be optimized by adjusting the flow rate through expansion device to maintain a constant superheat at all test conditions.

  • PDF

열펌프의 성능 최적화에 관한 연구 (Optimization of Heat Pump Systems)

  • 최종민;윤린;김용찬
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2007년도 추계학술대회 논문집
    • /
    • pp.538-541
    • /
    • 2007
  • An expansion device plays an important role in optimizing the heat pumps by controlling refrigerant flow and balancing the system pressures. Conventional expansion devices are being gradually replaced with electronic expansion valves due to increasing focus on comfort, energy conservation, and application of a variable speed compressor. In addition, the amount of refrigerant charge in a heat pump is another primary parameter influencing system performance. In this study, the flow characteristics of the expansion devices are analyzed, and the effects of refrigerant charge amount on the performance of the heat pump are investigated at various operating conditions. Cooling capacity of the heat pump system is strongly dependent on load conditions. The heat pump system is very sensitive with a variation of refrigerant charge amount. But, the performance of it can be optimized by adjusting the flow rate through expansion device to maintain a constant superheat at all test conditions.

  • PDF