• 제목/요약/키워드: enhanced harmonic extraction

검색결과 1건 처리시간 0.013초

향상된 고조파 검출 능력을 갖는 계통연계 인버터의 하이브리드 단독운전 방지기법 (A Hybrid Anti-islanding Detection Scheme for Utility Interactive Inverter with Enhanced Harmonic Extraction Capability)

  • 강성욱;김경화
    • 전력전자학회논문지
    • /
    • 제19권4호
    • /
    • pp.312-319
    • /
    • 2014
  • When distributed generation such as a wind power system is connected to the grid, it should meet grid requirements like IEEE Std. 1547, which regulates the anti-islanding method. Since the islanding may cause damage on electrical equipments or safety hazards for utility line worker, a distributed generation should detect it as soon as possible. This paper proposes a hybrid anti-islanding method coupled with the active and passive detection methods. To enhance the harmonic extraction capability for an active harmonic injection method, cascaded second-order band-pass filter and signal processing scheme are employed. Simulation and experiments are carried out under the islanding test condition specified in IEEE Std. 1547. Passive over/under voltage and over/under frequency methods are combined with the active method to improve the detection speed under certain condition. The simulation and experimental results are presented to verify that the proposed hybrid anti-islanding method can effectively detect the islanding.