• 제목/요약/키워드: end winding reactance

검색결과 2건 처리시간 0.015초

개방회로, 단락회로 특성시험 및 부하시험을 이용한 30 kVA 초전도 발전기의 특성해석 (A Study on 30 kVA Super-Conducting Generator Performance using Open Circuit, Short Circuit Characteristics, and Load Tests)

  • 하경덕;황돈하;박도영;김용주;권영길;류강식
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제49권2호
    • /
    • pp.85-92
    • /
    • 2000
  • 30 kVA rotating-field type Super-Conducting Generator is built and tested with intensive FE(Finite Element) analysis. The generator is driven by VVVF inverter-fed induction motor. Open Circuit Characteristic(OCC) and Short Circuit Characteristic(SCC) are presented in this paper. Also, the test result under the light load(up to 3.6 kW) are given. From the design stage, 2-D FE analysis coupled with the external circuit has been performed. The external circuit includes the end winding resistance and reactance as well as two dampers. When compared with the test data, the FE analysis results show a very good agreement.

  • PDF

30 kVA 초전도 발전기의 소용량 부하 인가시 운전특성 해석 (Performance Analysis of 30 kVA Super-Conducting Generator under Light Load)

  • 하경덕;황돈하;박도영;김용주
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 A
    • /
    • pp.271-273
    • /
    • 1999
  • In this paper 30 kVA Super-Conducting Generator's test and analysis results of OCC and SCC are presented. Also the test and FE analysis results of the generator under 1.2, 2.4, and 3.6[kW] load are described. For FE analysis of the generator's performance, the external circuit is coupled with the FE region. The generator's end winding reactance is obtained based on the design data, actual dimension, preliminary FE analysis, and empirical formulas. The comparison of FE analysis coupled with external circuit to the test results shows a good agreement.

  • PDF