• Title/Summary/Keyword: electric power plant equipments

Search Result 25, Processing Time 0.027 seconds

A Study for the Shaft Vibration of the Vertical Type Hydro Electric Power Generator (수축형 수차발전기 축진동에 관한 연구(I))

  • 이승원
    • 전기의세계
    • /
    • v.13 no.3
    • /
    • pp.28-37
    • /
    • 1964
  • It is the intention of this thesis to discriminate and investigate the cause of the shaft vibration of the vertical type hydroelectric power generator with respect to electrical, mechanical and hydraulic aspects, and to analyze the vibration which will occure by the each cause investigated above. In order to test the shaft vibration of No.1 generator in Hwachon, Korea new measurement method and measuring equipments were designed. In practice the shaft vibration of the generator was measured by above equipments and analyzed by the discriminative method. Detailed explanation for the designed measurement method and instruments is presented, and the results which I had tested three times for the generator No.1 in Hwachon power plant are added. As a appendix the mechanism and causes of the thrust bearing's wear and remarks for the runner are written.

  • PDF

Desulfurization Characteristics for Anthracite Coal Power Plant by Increasing Bituminous Coal Fuel (국내 무연탄 발전소 역청탄 사용시 탈황 특성 연구)

  • Kim, Jeong-You;Moon, Seung-Jae;Lee, Jae-Heon
    • Plant Journal
    • /
    • v.4 no.4
    • /
    • pp.71-77
    • /
    • 2008
  • The sulfur oxides is one of important materials to come about air pollution at thermal plant consuming fossil fuel. The several flue gas desulfurization equipments are installed and operated to decrease sulfur oxides. The flue gas desulfurization of our thermal plant is designed for optimizing flue gas desulfurization technical development and research by Korea Electric Power Research Institute. We operate this desulfurization equipment. Now, our country imports nearly 97 percentage of the energy source and competes with the world for the energy because of the sudden rise of raw materials cost. The fuel cost decrease of power plants is the most important factor of the operation. The fuel used in the experiment is the domestic anthracite from Kangwon Taeback and the bituminous coal from Taldinsky Mine in Russia. This Study is experimental investigations of desulfurization characteristics for domestic anthracite power plant by increasing bituminous coal. We surveyed possible parameters and conducted the performance about desulfurization equipment in Yong Dong thermal power plant.

  • PDF

A Study on the safety measures for the protection of hydrogen cooling system of generator (수소를 냉각매체로 하는 발전기 안전대책에 관한 연구)

  • Lee Choon-Ha;Yuk Hyun-Dai
    • Journal of the Korean Institute of Gas
    • /
    • v.8 no.4 s.25
    • /
    • pp.55-61
    • /
    • 2004
  • This paper provided a counter measures against the troubles and accidents that are likely to take place in the power plant using hydrogen gas as a coolant for the cooling system of the generator. Because of the extremely wide flammability limits of hydrogen in comparison to the other flammable gases, the safety measures against the hydrogen accidents is very important to ensure the normal operation of electric-power facility. This study's purpose was a presentation of standard model of safety management of hydrogen equipments in the coal firing power plant such as following items: 1) providing the technical prevention manual of the hydrogen explosions and hydrogen fires occurring in the cooling system of power generator; 2) the selection of explosion-proof equipments in terms of the risk level of operating environment; 3) the establishment of regulations and counter measures, such as the incorporation of gas leakage alarm device, for preventing the accidents from arising, 4) the establishment of safety management system to ensure the normal operation of the power plant.

  • PDF

A Development of Technology for Low- and Intermediate-Level Radioactive Waste Treatment utilizing Induction heater and Plasma torch (플라즈마 및 전기유도가열을 이용한 중.저준위 방사물 처리기술 개발)

  • Moon, Young-Pyo;Cho, Chun-Hyung;Song, Myung-Jae;Han, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 1997.11a
    • /
    • pp.357-360
    • /
    • 1997
  • Currently, there is a need for the development of an advanced new technology for Low-and Intermediate-Level Radioactive Waste (LILW) treatment from nuclear power plants. The vitrification and melting technology by the use of the electrical equipments such as induction heater and plasma torch based furnace, along with off-gas treatment are considered as the most promising one of the LILW treatment technology since they can produce a very stable waste forms as well as considerably large volume reduction, which is a world-wide trend to apply for radioactive waste treatment. Korea Electric Power Research Institute(KEPRI) has already completed a feasibility study on LILW treatment and conceptual system design of a demonstration plant to be constructed. For this research, KEPRI selected a cold crucible melter(CCM) for the vitrification of combustible waste, and plasma torch based furnace(PT) for the melting of noncombustible waste, along with off-gas treatment for the volatile radioisotopes such as cesium.

  • PDF

Application of FMECA with Stochastic Approach to Reliability-Centered Maintenance of Electric Power Plants in Korean Power Systems (RCM 수립을 위해 발전설비의 고장확률을 고려한 확률론적 FMECA 평가 기법)

  • Joo, Jae-Myung;Lee, Seung-Hyuk;Kim, Jin-O;Lee, Hyo-Sang
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.196-197
    • /
    • 2006
  • Preventive maintenance can avail the generation utilities to reduce cost and gain more profit in a competitive supply-side power market. So, it is necessary to perform reliability analysis on the systems in which reliability is essential. In this paper, RCM (Reliability -Centered Maintenance) analytical method is adopted using real historical failure data in Korean power plants. Therefore, the reliability -based Probability model for predicting the failures of components in the power plant is also established, and application to FMECA(Failure Mode Effects and Critical Analysis) consideration of failure probability, Based on the weighting ranking of generating equipments which status to be probability estimation by FMECA. The FMECA is an engineering analysis and a core activity performed by reliability engineers to review the effects of probable failure modes of generating equipments and assemblies of the power system on system performance. The results of this paper show that application of FMECA with stochastic approach to the preventive maintenance can efficiently avail decreasing the cost on maintenance and hence improve the total benefit.

  • PDF

A Real-time Calculation Method on Performance Impact of Controllable Operation Parameters for Combined Cycle rower Plant (복합화력 제어가능 운전 파라미터의 실시간 영향산출 기법)

  • Joo Yong-Jin;Park Jong-Ho
    • Journal of Energy Engineering
    • /
    • v.15 no.1 s.45
    • /
    • pp.67-73
    • /
    • 2006
  • A calculation method on performance impact of the controllable operations parameter such as GT inlet filter ${\Delta}P$, compressor efficiency, and condenser pressure was devised to achieve best performance of combined cycle power plant with the on-line performance monitoring system. This method calculates the performance impact on the deviation between 'Expected' values and 'Actual' values. Controllable parameter targets are determined based on achievable performance given existing equipments and control conditions.

The Study of FUSE Installing of PT in the trend of Digitalization and Convergence of Power Machinery. (디지탈화 및 복합화된 전력기기 변성기용 퓨즈 설치의 문제점)

  • Ok Yeon Ho;Lee Hyoung Mook;Hong Yeong Jae;Lee Eun Woong
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.357-359
    • /
    • 2004
  • Fuse is the initial equipment of Protective Relay The installation standard of Fuse has been used for long time in Power Facilities. However according to the innovative development of Electric & Electronic element(=semiconductor) Technology, Protective Relay and other Power Equipments are being changed into Digitalization and Multi-Functional Convergence. In contrast with it, the installation standard of Fuse is just the same. There is a need to give careful consideration to it. This study will bear a Part of producing a safe and efficient Power by examining the current installation of primal 8f secondary 1'use in multi-functional PT of Power plant, giving a problem careful consideration and suggesting suitable countermeasures.

  • PDF

Round Robin Test for Performance Demonstration System of Ultrasonic Examination Personnel (초음파검사자 기량검증 체제를 위한 다자비교시험)

  • Yoon, Byung-Sik;Yang, Seung-Han;Kim, Yong-Ho;Kim, Yong-Sik;Yang, Dong-Soon
    • Journal of the Korean Society for Nondestructive Testing
    • /
    • v.24 no.4
    • /
    • pp.378-383
    • /
    • 2004
  • The Korean Performance Demonstration(KPD) System for the ultrasonic testing personnel, equipments and procedures applicable to the Class 1 and 2 piping examination for nuclear power plant in Korea has been established. A round robin test was conducted in order to compare the examination results by the method of Performance Demonstration(PD) with the traditional dB-drop method. The round robin test shows that the reliability of the PD method is better than that of the dB-drop method. As a result, adoption of the PD method to the in-service inspection of the nuclear power plants will improve the reliability of the ultrasonic test results.

Proposal of A Novel Generator Efficiency Test Using The Shaft-Torque Method (축-토크법을 이용한 새로운 발전기 효율시험 방법의 제안)

  • Kim, Hyun-Han;Ok, Yeon-Ho;Kim, Kwang-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.4
    • /
    • pp.461-468
    • /
    • 2014
  • An efficiency test for generators is generally required in case of construction of a new power plant or replacement of an existing generator. Generally, the efficiency of generator is measured by the input-output ratio under any given condition. Therefore, the best way is to directly measure the value of input and output power of a generator and calculate the efficiency values. However, it is difficult to measure a generator's input values accurately, especially for large systems. So, we are usually measuring the losses of the generator. But for measuring these values, there are several constraints for test such as preparing additional power generator and releasing the protection relay for manual operation of auxiliary equipments. Therefore, this study suggests that a novel generator efficient test method using the shaft-torque method which can be carried out while the generator is normally operating. The reliability of the result value was verified by comparing with the efficiency test results of the conventional retardation method on IEEE Std 115-1995.

The Analysis about Trouble of GOVERNOR (속도 및 제어시스템의 부조화에 따른 조속기 에러 원인 분석)

  • Ok, Yeon-Ho;Oh, Sueg-Young;Kim, Ki-Won;Byun, Ill-Hwan;Go, Young-Hwan;Im, Seung-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.252-253
    • /
    • 2011
  • Many errors are broken out when hydro power plants are operating connected to electric power system. To minimize ripple effects of accidents, a hydro power plant is separated by a circuit breaker consisting of each protection equipments. In this paper, I will analyze a cause of abnormal events of emergency stop and therefore I take measures and suggest solutions for similar cases.

  • PDF