• 제목/요약/키워드: dynamic safety system (DSS)

검색결과 2건 처리시간 0.015초

A Study on Design of the Trip Computer for ECC System Based on Dynamic Safety System

  • Kim, Seog-Nam;Seong, Poong-Hyun
    • Nuclear Engineering and Technology
    • /
    • 제32권4호
    • /
    • pp.316-327
    • /
    • 2000
  • The Emergency Core Cooling System in current nuclear power plants typically has a considerable number of complex functions and largely cumbersome operator interfaces. Functions for initiation, switch-over between various phases of operation, interlocks, monitoring, and alarming are usually performed by relays and analog comparator logic which are difficult to maintain and test. To improve problems of an analog based ECC (Emergency Core Cooling) System, the trip computer for ECCS based on Dynamic Safety System (DSS) is implemented. The DSS is a computer based reactor protection system that has fail-safe nature and performs a dynamic self-testing. The most important feature of the DSS is the introduction of test signal that send the system into a tripped state. The test signals are interleaved with the plant signals to produce an output which switches between a tripped and health state. The dynamic operation is a key feature of the failsafe design of the system. In this work, a possible implementation of the DSS using PLC is presented for a CANDU Reactor. ECC System of the CANDU Reactor is selected as the reference system.

  • PDF

A Study on Implementation of Dynamic Safety System in Programmable Logic Controller for Pressurized Water Reactor

  • Kim, Ung-Soo;Seong, Poong-Hyun
    • 한국원자력학회:학술대회논문집
    • /
    • 한국원자력학회 1996년도 추계학술발표회논문집(1)
    • /
    • pp.91-96
    • /
    • 1996
  • The Dynamic Safety System (DSS) is a compute. based reactor protection system that has fail-safe nature and perform dynamic self-testing. In this paper, the implementation of DSS in PLC is presented for PWR. In order to choose adequate PLC implementation model of DSS, the reliability analysis is performed. The KO-RI unit 2 Nuclear power plant is selected as the reference plant, and the verification is carried out using the KO-RI unit 2 simulator FISA-2.

  • PDF