• Title/Summary/Keyword: cable joint material

Search Result 34, Processing Time 0.031 seconds

Influence of Partial Discharge Properties due to Void in Cable Joint Parts (케이블 접속재 부분방전 특성에 미치는 보이드의 영향)

  • 신종열;홍진웅
    • Journal of the Korean Society of Safety
    • /
    • v.18 no.3
    • /
    • pp.69-74
    • /
    • 2003
  • To investigate the partial discharge and electric field distribution in cable joint parts, we measured the partial discharge and electric field in specimen. The specimens which cross-linked polyethylene(XLPE) and ethylene propylene diene ethylene(EPDM) are used to insulating material for underground cable md cable jointing parts. The polymers are used to insulating material in switchgear which is a kind of transformer equipment and in ultra-high voltage cable. Its using is increasing gradually, the electrical insulation properties are not only excellent but also mechanical property is excellent. And because it is possible to be made void of several type in insulator while it is produced, which the electrical field distribution is changed by void, it has a critical influence to insulator performance. The underground cable is connecting by the jointing material, insulating breakdown and the electric ageing which are caused by several mixing impurity and the damage of cable insulator layer, which reduced the life of cable while intermediate joint kit is connected. Therefore, the computer simulation is used to estimating insulator performance, XLPE is used to the insulating material of ultra-high voltage cable and EPDM is used to insulator layer in joint material kit, and which are produced as specimen. And it is analyzed the electric field concentrating distribution and partial discharge by modeling of computer simulation in void and cable joint kit.

Characteristics of Joint High Temperature Superconducting tape (High Temperature Superconducting tape(Bi-2223)의 접속시 통전특성)

  • Kim, Hae-Joon;Sim, Ki-Deok;Cho, Jeon-Wook
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.06a
    • /
    • pp.244-245
    • /
    • 2007
  • Specially, High Temperature Superconducting power-transmission cable(HTS cable), 3-phase 100m long, 22.9kV class HTS power transmission cable system have been developed by Korea Electrotechnology Research Institute (KERI) and LS cable Ltd. that is one of 21st century frontier project in Korea. This cable was installed in KEPCO(Go-chang) testing site. In case of manufacturing HTS cable, superconducting joint is very important because they need very long tapes. Therefore, this paper gives some investigation of AC Loss in joined HTS tape by using several joint methods. Finally, this paper was shown background data for the form of HTS cable joint.

  • PDF

Electric Field Distribution Simulation of the Cable Joint Materials (케이블 접속재료의 전계분포 시뮬레이션)

  • Kim, Hyung-Joo;Byun, Doo-Gyoon;Shin, Jong-Yeol;Lee, Duk-Jin;Lee, Chung-Ho;Hong, Jin-Woong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11b
    • /
    • pp.601-604
    • /
    • 2001
  • The insulation materials of cables used for underground power transmission requires a higher insulating capability. and the most popular method to examine the cable is partial discharge test due to applying variation voltage. In the thesis. air void. silicone oil. of which may possibly exist real cables. are simulated by Electra 2D program. Also the relations between calculated field strength and the void defect type in the cable joint materails. In the modeling. electic field inner to the cable joint material composed by XLPE and EPDM is modeling simulated. We obtained the electric field distribution in void due to two conditions.

  • PDF

Electric Field Distribution Simulation of the Cable Joint Materials (케이블 접속재료의 전계분포 시뮬레이션)

  • 김형주;변두균;신종열;이덕진;이충호;홍진웅
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11a
    • /
    • pp.601-604
    • /
    • 2001
  • The insulation materials of cables used for underground power transmission requires a higher insulating capability, and the most popular method to examine the cable is partial discharge test due to applying variation voltage. In the thesis, air void, silicone oil, of which may possibly exist real cables, are simulated by Electro 2D program. Also the relations between calculated field strength and the void defect type in the cable joint materials. In the modeling, eclectic field inner to the cable joint material composed by XLPE and EPDM is modeling simulated. We obtained the electric field distribution in void due to two conditions.

  • PDF

The Application of Al-foil Electrode for Detecting Partial Discharge Signal in Middle Joint Box of EHV Power Cable (초고압 전력케이블용 중간 접속부 내의 부분방전신호 검출을 위한 박전극 응용)

  • Lee, Yong-Sung;Yang, Jong-Kyung;Yang, Jong-Keok;Choi, Yong-Sung;Park, Dae-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.142-144
    • /
    • 2005
  • To detect partial discharge of 154kV joint box, we have made experiment by using the Al-foil electrode sensor. Generally the signals which are detected in partial discharge test of underground power transmission cable are accompanied wi th both noises of high voltage and noises of surrounding power cable. The most noise in near to end part of joint box is corona, beside other noises flowed from surrounding area. Partial discharge test is difficulty due to these noises. First, we had used Al-Foi1 sensor on middle joint box of 154[kV] underground transmission power cable, and then analyzed reliability of calibration signal by using the Al-Foi1 electrode sensor of NJB. From above results, decrement properties measured highly. But incase of injecting calibration signal of 500[pC] after measuring signals in IJB, the S/N ratio had about 25[dB] acquisition.

  • PDF

Effect oh Heat Treatment on Breakdown Properties in the Joint Interface of Power Cables (전력케이블 절연접속계면의 절연파괴 특성에 미치는 열처리 효과)

  • 이창종;김진수;박강식;한상옥
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.11 no.7
    • /
    • pp.502-507
    • /
    • 1998
  • The purpose of this study is to investigate the breakdown properties in joint interface of power cables with heat treatment. The specimens have the structure of XLPE/EPDM interface like the joint of distribution power cable. The breakdown characteristics of the SLPE/EPDM joint were studied with crosslinking by=products. AC breakdown voltages were measured with heat treatment time and interfacial materials and crosslinking by-products as testing factors. This study has shown that crosslinking by-product gases play an important role at the insulation properties of cable joints by heating. The dielectric strength shows the lowest values at 4 hours heat treatment. The AC breakdown strength in the untreated sample was increased with heat treatment time.

  • PDF

Development of Friction Welded Al to Cn Bimetallic Sleeve for 220kV XLPE Cable Termination & Joint (220kV XLPE CABLE 접속함용 Al-Cu 이종접속슬리브 개발)

  • Kim, Hyun-Ju;Park, Jeong-Ki;Park, Sung-Min
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.93-93
    • /
    • 2010
  • We developed friction welded bimetallic sleeve for 220kV aluminum conductor XLPE cable. Not only friction welded bimetallic sleeve for Termination(EB-A, EB-G) but also friction welded sleeve for Joint of Al to Cu conductor was developed regardless of this project. Generally, friction welded sleeve used to connect Al conductor cable to Cu conductor cable and used for improvement of mechanical property of terminal by offer the copper side of friction welded bimetallic sleeve at the Termination. Connection method for Al-Cu conductor has mainly used friction welding at the solid state, because it is difficult to connect by using conventional welding method. this investigation introduces development of friction welded bimetallic sleeve by friction welding and test result of 220kV Al conductor XLPE cable and accessories using friction welded sleeve.

  • PDF

DC Performance of $Nb_3$Sn Cable Joints with multi-interfaces (다수의 접합경계를 갖는 $Nb_3$Sn 케이블 접합부의 직류 저항 특성)

  • 이호진;김기백;연제욱;홍계원;김기만
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.13 no.2
    • /
    • pp.170-176
    • /
    • 2000
  • The joints with multi-interfaces was expected to have low DC resistance compared with those with single interface. The small size joint specimens joined with Nb3Sn sub-cables were fabricated to investi-gate the DC performance in the range of 0 to 600A transport current without external magnetic field. The joints with multi-interfaces have a few n-Ohm resistance, which is much lower than that of single lap joint. Because the interfaces between sub-cables of multi-interfaced joint are more complicated than those of single-interfaced joint, the soldering condition between sub-cables is very effective on the joint DC resistance.

  • PDF

Design and Implementation of the Cable Rod Hydraulic Actuator for Robotic Revolute Joints (로봇의 회전관절을 위한 케이블 로드를 갖는 유압 구동기 설계 및 구현)

  • Kim, Jungyeong;Park, Sangdeok;Cho, Jungsan
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.33 no.9
    • /
    • pp.723-730
    • /
    • 2016
  • This paper presents a cable-driven hydraulic actuator named Cable Rod Hydraulic Actuator (CRHA). The cable actuating system is attractive for designing a compact joint in robotic applications since it can be installed remotely from the joint. Recently, cable rods have been used in pneumatic area for inertia reduction. However, designing cable rods in hydraulics is challenging because it is difficult to achieve flexibility and endurance simultaneously under high pressure conditions. In this paper, the cable rod, which consists of a cable and jacket, is proposed to meet both requirements. To design the CRHA, we determined the design parameters, such as cylinder size, and selected the cable rod's material by friction and leakage test. Finally, comparisons experiments about step and frequency responses with conventional hydraulic actuators were performed to assess feasibility for robotic joints, and the results show that the proposed system has good bandwidth and fast response as robotic joints.

Partial Discharge Characteristics of the XLPE/EPDM Interface in Power Cable Joint (전력케이블 접속재 XLPE/EPDM 계면의 부분방전 특성)

  • Cho, Kyung-Soon;Hong, Jin-Woong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.9
    • /
    • pp.780-786
    • /
    • 2007
  • This paper describes the influence on partial discharge characteristics of defects at the model XLPE/EPDM interfaces of power cable joints. The defects of void and copper which could inadvertently be present at the joint interface. We measured ${\Phi}-n,\;{\Phi}-q$ patterns by a computer-aided partial discharge measuring system. Several parameters i, e, maximum discharge $q_{max}$ [pC], average discharge q [pC/cycle], and average angle of discharge ${\Theta}g$ [deg] were found to depend upon the defect type varying applied voltage. As the result of time evaluation, partial discharges are small different at copper defects, but is decreasing obviously about 20 minutes at void defect. It considered that difference of magnitude of total positive discharge of Q+ [pC] and total negative discharge of Q- [pC] is SPMD(swarming pulsive micro discharges).