• Title/Summary/Keyword: arrester

Search Result 303, Processing Time 0.021 seconds

Aging Characteristics of ZnO Surge Arresters (ZnO 피뢰기의 경년변화 특성분석)

  • 김주용;김찬영;송일근;이병성;한용희
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.383-386
    • /
    • 1999
  • Surge arrestor is used for protection of facilities and lines. Recently lots of arresters fatted prematurely In the distribution lines. It is important to know that what the cause of the failures is. This paper presents characteristics of the aged and new 18kV surge arrester. In order to analyse characteristics, we measured leakage current using specialty made leakage current measurement system and also investigated Tan $\delta$ of the arrester and microstructure of the elements. Through the investigation we found that the characteristics among the ZnO elements in an arrester were a little different, It means that the surge arreste can have non-uniform electric field due to the characteristic difference of The each element. Owing to this concentration of the electric field, the localized aging might be proceeded.

  • PDF

A STUDY ON EFFECTIVE APPLICATION OF SURGE ARRESTER BETWEEN THE SWITCHYARD AND MAIN TRANSFORMER IN POWER PLANT (발전소내 스위치야드 및 주변압기간 연결선로의 적정 피뢰기 위치 선정)

  • Lee, Heung-Chan;Ham, Young-Soo;Jung, Gi-Soo
    • Proceedings of the KIEE Conference
    • /
    • 1995.07b
    • /
    • pp.503-505
    • /
    • 1995
  • The surge arrester plays a vital role in the protection of substation against transient overvoltages resulting from lightning surges and system switching operations. The proper selection and application of the surge arrester is an integral part of the process of substation equipment insulation level selection. The paper outlines the basic consideration in modeling the lightning stroke, the surge arrester, and the system to be protected. The paper discusses the results of various cases simulated using the alternative transient computer program to evaluate the separation effects.

  • PDF

A Study on the Deterioration Progress of Railway Arresters (철도용 피뢰기의 열화진전에 관한 연구)

  • 길경석;한주섭;한문섭
    • Journal of the Korean Society for Railway
    • /
    • v.7 no.4
    • /
    • pp.307-311
    • /
    • 2004
  • Arresters are the best protective device on electrical power systems against transient overvoltages generated by lightning and/or switching operation. Nonetheless, arresters are deteriorated by absorption of moisture in the environments of its use, repetition in the protective operation to overvoltages, and some defects at manufacturing. It is therefore important to estimate the electrical characteristic changes of ZnO blocks. In this paper, an accelerated ageing test by a standard lightning impulse current was carried out to extract parameters needed for arrester diagnosis, and leakage current components were measured. Total energy applied to the ZnO blocks at each time is about 1,050[J] in 8/20[${\mu}\textrm{s}$] impulse current. From the experimental results, we proposed electrical parameters and leakage current level to diagnose arrester soundness.

Temperature dependent characteristics of leakage currents of ZnO blocks (온도에 따른 ZnO 피뢰기 소자의 누설전류의 온도의존성)

  • Lee, Bok-Hee;Lee, Su-Bong;Li, Feng;Kim, Dong-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1572-1573
    • /
    • 2006
  • This paper presents electrical properties of Zinc Oxide(ZnO) surge arrester blocks under the power frequency AC voltages and various temperatures. The leakage current, $I_{R}-V$ curios and power dissipation for the fine and aged ZnO surge arrester blocks were measured as a function of the temperatures and applied voltages. When the temperature is increased from $50\;[^{\circ}C]$ to $150\;[^{\circ}C]$, the total leakage current significantly increased at the sane applied voltage level. Also, the resistive leakage currents and power dissipation were increased with increasing temperature. The leakage current and power dissipation of the aged ZnO arrester blocks were higher than the fine ZnO arrester blocks.

  • PDF

Sealing Technology For Polymer Arrester Housed Development (폴리머 피뢰기 애관 개발에서의 기밀기술)

  • Hwang, Myung-Keun;Kim, Kwang-Ho;Park, Nam-Shik;Kim, In-Sung;Cho, Han-Ku
    • Proceedings of the KIEE Conference
    • /
    • 1996.07b
    • /
    • pp.754-756
    • /
    • 1996
  • In this paper, polymer housing arrester has very good characteristics in design versatility as well as excellent resistance to moist ingress and pollution performance. For the presented of the characteristics evaluation and technology of disk spring and knuckle structure of FRP to filament winding seems to protect the arrester elements from moisture absorption. The achievement in the research and technology will contribute to the showed very good characteristic in adhesion of terminal cap and FRP cylinder for outdoor arresters and domestic products of high voltage power distribution arrester.

  • PDF

Influence of System Voltage Harmonics on Arrester Deterioration Diagnostic Techniques by Leakage Current Measurement (누설전류측정에 의한 피뢰기 열화진단기술에 있어 전원고조파의 영향)

  • Kil, Gyung-Suk;Han, Joo-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.08a
    • /
    • pp.142-145
    • /
    • 2002
  • This paper describes an influence of system voltage harmonics on arrester deterioration diagnostic techniques based on leakage current measurement because the resistive current is composed of two components caused by nonlinear characteristics of arrester and by system voltage harmonics. Resistive leakage currents of arresters, which can be evaluated by the third harmonic component of total leakage currents, increase with its deterioration progress. In this paper, we developed a PSpice model for ZnO arrester to simulate the harmonics' effect described above. In simulation, pure sinusoidal voltage and the $3^{rd}$ harmonic voltage are applied to the model, and the leakage current changes are compared. The simulation results showed that the magnitudes of resistive leakage current depend not only on the phase of system voltage harmonics but also on the magnitude of it.

  • PDF

A Detection Method of Resistive Leakage Current Flowing through ZnO Arrester Blocks (산화아연 피뢰기소자에 흐르는 저항분 누설전류의 검출기법)

  • 이복희;강성만
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.15 no.3
    • /
    • pp.67-73
    • /
    • 2001
  • This paper resents a developed measuring device of resistive leakage current and a fundamental discussion of deterioration diagnosis for Zinc Oxide(ZnO) arrester blocks. We have developed the leakage current detection device for ageing test and durability evaluation for ZnO arrester blocks. The resistive leakage current can be used as an indicator to discriminate whether the ZnO arrester blocks is in good state or in bad. The resistive leakage current measuring system with the compensation circuit was designed and fabricated. The sauce tests for ZnO arrester blocks were investigated by observing the resistive leakage current together with fast Fourier transform analysis. The proposed monitoring systems for the resistive leakage current can effectively be used to investigate the electrophysical properties of ZnO arrester blocks in laboratory and to develop the techniques of forecasting the deterioration of ZnO arresters in electric power systems.

  • PDF

Characteristic Changes of ZnO Arrester Blocks by Multiple-lightning Impuse Currents (다중 뇌충격전류에 의한 산화아연형 피뢰기 소자의 특성 변화)

  • Gil, Gyeong-Seok;Han, Ju-Seop
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.49 no.12
    • /
    • pp.685-690
    • /
    • 2000
  • Multiple-lightning impulse currents are a general feature of the lightning ground f=flash. It is therefore necessary for lightning arresters used in power systems to be estimated by applying not only a single-lightning impulse current but also a multiple-lightning impulse currents. This paper presents the effects of multiple-lightning impulse currents on deterioration of ZnO arrester blocks. The multiple-lightning impulse generator which can produce quadruple 8/20$[\mus]$ 5[kA] with separation time of 30~120[ms] is designed and fabricated. The total energy applied to the arrester block at each impulse is about 1,200[J]. In experiment, various parameters such as leakage current component, reference voltage, and temperature are measured with the number of applied impulse current. Also, micro-structure changes of the ZnO blocks after applying the single and the multiple-lightning impulse currents of 200 times are compared. The experimental results indicate that the types of arrester blocks are more vulnerable to deterioration or damage by multiple-lightning impulse currents.

  • PDF

Characteristics of ZnO Arrester Blocks Leakage Currents under Mixed Direct and 60 Hz Alternating Voltages (직류와 60 Hz 교류가 중첩된 전압에 대한 산화아연 피뢰기 소자의 누설전류 특성)

  • Lee Bok-Hee;Kang Sung-Man;Pak Keon-Young
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.1
    • /
    • pp.23-29
    • /
    • 2005
  • This paper presents the characteristics of leakage currents flowing through ZinC Oxide(ZnO) surge arrester blocks under mixed direct and 60 Hz alternating voltages. A mixed voltage, in which an alternating voltage is superimposed upon a direct voltage, appears on the HVDC system network. The mixed direct and alternating voltage generator with a peak open-circuit of 10 kV was designed and fabricated. The leakage currents and V-I curves for the fine and used ZnO surge arrester blocks were measured as a function of the voltage ratio k, where the voltage ratio k is defined as the ratio of the peak of alternating voltage to the peak of the mixed voltages. The resistive component in the leakage current in the low conduction region is significantly increased with increasing the voltage ratio k. The V-I characteristic curves for the mixed voltages lies between the direct and alternating characteristics, and the cross-over phenomenon in the high conduction region was appeared.

Temperature and Leakage Current Characteristics of Polymeric Surge Arrester with Housing (폴리머 피뢰기의 구조에 따른 온도와 누설전류 특성)

  • Cho, Han-Goo;You, Dae-Hoon;Lee, Un-Yong;Kim, Ha-Na
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.3
    • /
    • pp.273-280
    • /
    • 2007
  • In this paper, the ZnO surge arrester performance of power distribution class has been studied under different manufacturing conditions such as housing materials(polymeric, porcelain), interface sealants and one-body molding type. In the recent years, the polymeric ZnO surge arresters have been developed and put into operations based on their excellent characteristics. For polymeric surge arresters, the inner gas volume is extremely small, especially in solid insulation polymeric arresters there are not any gas volume inside arresters in the structure due to polymeric materials are filled into the internal gas volume. The sealing integrity is related to safe operation of surge arrester, the prime failure reason of porcelain housed arresters is moisture ingress. In this paper, the sealing integrity of polymeric surge arresters is investigated with moisture multi-aging test and ingress test. The evaluation techniques are used to inspect the sealing integrity of polymeric arresters, including leakage current, surface temperature, reference voltage and dissipation factor.