• Title/Summary/Keyword: alternative refrigerant

Search Result 201, Processing Time 0.025 seconds

External Condensation Heat Transfer Coefficients of R22 Alternative Refrigerants and R134a According to the Saturated Vapor Temperature Change on an Enhanced Tube (열전달 촉진관에서 R22 대체냉매 및 R134a의 포화증기 온도변화에 따른 외부 응축 열전달계수에 관한 연구)

  • Yoo Gil-Sang;Hwang Ji-Hwan;Park Ki-Jung;Jung Dongsoo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.11
    • /
    • pp.981-989
    • /
    • 2005
  • In this study, external condensation heat transfer coefficients (HTCs) are measured on a low fin tube and Turbo-C tubes at the saturated vapor temperature of $30^{\circ}C$, $39^{\circ}C$, and $50^{\circ}C$ for R22, R410A, R407C and R134a with the wall subcooled at $3{\~}8^{\circ}C$. The HTCs of all refrigerants decreased as increasing the saturation temperature from $30^{\circ}C$ to $50^{\circ}C$. This trend is due to better thermodynamic properties of the liquid phase at low temperature Beatty and Katz's prediction yielded a $20.0\%$ deviation for the low fin tube data. The heat transfer enhancement factors for the 26 fpi low fin tube and Turbo-C tubes are 4.0${\~}$5.5 and 3.0${\~}$8.1 respectively for the refrigerants tested. Finally the performance of Turbo-C tube is better than that of the low fin tube.

Performance of R290 and R1270 as Alternative Refrigerants of R22 According to Temperature Variations of Evaporator and Condenser (증발기와 응축기 온도변화에 따른 R22 대체냉매 R290 및 R1270의 성능평가)

  • Baek In-Cheol;Park Ki-Jung;Shim Yun-Bo;Jung Dong-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.10
    • /
    • pp.761-767
    • /
    • 2006
  • In this study, performance of 2 pure hydrocarbons R290 and R1270 was measured in an attempt to substitute R22 under 3 different temperature conditions. They were tested in a refrigerating bench tester with a hermetic rotary compressor. The test bench provided about 3.5 kW capacity and water and water/glycol mixture were employed as the secondary heat transfer fluids. All tests were conducted under the same external conditions resulting in the average saturation temperatures of $7/45^{\circ}C$ and $-7/41^{\circ}C$ and $-21/28^{\circ}C$ in the evaporator and condenser, respectively. Test results show that the coefficient of performance (COP) of these refrigerants is up to 11.54% higher than that of R22 in all temperature conditions. Compressor discharge temperatures were reduced by $14{\sim}31^{\circ}C$ with these fluids. There was no problem with mineral oil since the mixtures were mainly composed of hydrocarbons. The amount of charge was reduced up to 58% as compared to R22. Overall, these fluids provide good performance with reasonable energy savings without any environmental problem and thus can be used as long term alternatives for residential air-conditioning and heat pumping application.

Performance Evaluation of R22 Alternative Refrigerants According to Temperature Variations of Evaporator and Condenser (증발기와 응축기 온도변화에 따른 R22 대체냉매의 성능평가)

  • Baek, In-Cheol;Shim, Yun-Bo;Jung, Dong-Soo
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.58-63
    • /
    • 2006
  • In this study, performance of 2 pure hydrocarbons and 3 mixtures was measured in an attempt to substitute R22 under 3 different temperature conditions. The mixtures were composed of R1270(propylene), R290(propane) and R152a. They were tested in a refrigerating bench tester with a hermetic rotary compressor The test bench provided about 3.5 kW capacity and water and water/glycol mixture were employed as the secondary heat transfer fluids. All tests were conducted under the same external conditions resulting in the average saturation temperatures of $7^{\circ}C/45^{\circ}C$ and $-7^{\circ}C/41^{\circ}C$ and $-21^{\circ}C/28^{\circ}C$ in the evaporator and condenser, respectively. Test results show that the coefficient of performance (COP) of these refrigerants is up to 11.54% higher than that of R22 in all temperature conditions. Compressor discharge temperatures were reduced by $14{\sim}31^{\circ}C$ with these fluids. There was no problem with mineral oil since the mixtures were mainly composed of hydrocarbons. The amount of charge was reduced up to 58% as compared to R22. Overall, these fluids provide good performance with reasonable energy savings without any environmental problem and thus can be used as long term alternatives for residential air-conditioning and heat pumping application.

  • PDF

A study on the characteristics of evaporation heat transfer of carbon dioxide flowing upward in a vertical smooth tube (이산화탄소의 수직원관 내 상향유동 증발열전달 특성에 관한 연구)

  • Kim, Yong-Jin;Cho, Jin-Min;Kim, Min-Soo
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.2217-2221
    • /
    • 2007
  • Because of the ozone layer depletion and global warming, new alternative refrigerants are being developed. In this study, evaporation heat transfer characteristics of carbon dioxide flowing upward in a vertical tube have been investigated by experiment. Before the test section, a pre-heater is installed to adjust the inlet quality of the refrigerant to a desired value. A smooth tube with outer diameter of 5 mm and length of 1.44 m was selected as a test tube. The test was conducted at mass fluxes of 212 to 530 kg/$m^2s$, saturation temperature of -5 to 20$^{\circ}C$, and heat fluxes of 20 to 45 kW/$m^2$. As the vapor quality and mass fluxes increase, the heat transfer coefficients of carbon dioxide are decreased, and the heat transfer coefficients increase when the heat fluxes and saturation temperatures increase.

  • PDF

Dynamic Models and Intelligent Control Algorithms for a $CO_2$ Automotive Air Conditioning System (자동차 $CO_2$ 냉방시스템의 동적모델과 지능제어알고리즘)

  • Han, Do-Young;Jang, Kyung-Chang
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.14 no.4
    • /
    • pp.49-58
    • /
    • 2006
  • In the respect of the environmental protection viewpoint, $CO_2$ may be one of the most attractive alternative refrigerants for an automotive air-conditioning system. For the development of control algorithm of a $CO_2$ automotive air-conditioning system, characteristics of a $CO_2$ refrigerant should be considered. The high-side pressure of a $CO_2$ system should be controlled in order to improve the system efficiency. In this study, dynamic physical models of a $CO_2$ system were developed and dynamic behaviors of the system were predicted by using these models. Control algorithms of a $CO_2$ system were also developed and the effectiveness of these algorithm was verified by using dynamic models.

Computation of Compact Heat Exchanger Performance by the Heat Exchangelet Method : Effect of Tube-to-tube Conduction along the Fin (미소열교환기법에 의한 밀집형 열교환기의 성능 계산 : 핀을 통한 튜브간 전도의 영향)

  • 성시경;송태호;최영철
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.5
    • /
    • pp.494-501
    • /
    • 2000
  • Effectiveness of a 3-pass plate finned-tube heat exchanger is calculated using heat exchangelet method by changing the shape of fin and the arrangement of tubes. The alternative refrigerant R134a is taken in this study. Conduction between neighboring tubes along the fin is taken into account in addition to convection between the fin and the surrounding air. Governing equations are obtained by using energy balance in a small control volume containing a tube and fins. They are numerically solved following the tube. Effect of tube-to-tube conduction is investigated in single-phase and two-phase flows with various fin shapes and arrangements of tubes. Improvement of effectiveness by fin perforation is studied too. The results shows that perforating fins, increasing the number of tubes, and increasing the distance between neighboring tubes at the same fin area enhance the effectiveness.

  • PDF

Condensation Heat Transfer Coefficients of R245fa on a Plain Tube (수평관에서 R245fa의 응축 열전달계수)

  • Shim, Yun-Bo;Park, Ki-Jung;Jung, Dong-Soo;Kim, Jong-Seong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.8
    • /
    • pp.555-562
    • /
    • 2007
  • In this study, condensation heat transfer coefficients (HTCs) of R22, R134a, R245fa and R123 are measured on a horizontal plain tube. All data are taken at the vapor temperature of $39^{\circ}C$ with a wall subcooling temperature $3-8^{\circ}C$. Test results show the HTCs of newly developed alternative low vapor pressure refrigerant, R245fa, on a plain tube are 9.5% higher than those of R123 while they are 3.3% and 5.6% lower than those of R134a and R22 respectively. Nusselt's prediction equation for a plain tube underpredicts the data by 13.7% for all refrigerants while a modified equation yielded 5.9% deviation against all data. From the view point of environmental safety and condensation heat transfer, R245fa is a long term good candidate to replace R123 used in centrifugal chillers.

Characteristics of Evaporative Heat Transfer and Pressure Drop of Carbon Dioxide and Correlation Development near the Critical Point (임계점 부근에서 이산화탄소의 증발열전달 및 압력강하 특성 연구와 상관식 개발)

  • 윤석호;조은석;김민수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.6
    • /
    • pp.530-537
    • /
    • 2004
  • In recent years, carbon dioxide among natural refrigerants has gained consider-able attention as an alternative refrigerant due to its excellent thermophysical properties. However, few investigations have been performed to develop useful correlations of heat trans-fer coefficients and pressure drop during evaporation of carbon dioxide. This study is aiming at providing the characteristics of heat transfer and pressure drop during the evaporation process of carbon dioxide. Heat is provided by a direct heating method to the test section, which was made of a seamless stainless steel tube with an inner diameter of 7.53 mm, and a length of 5.0 m. Experiments were conducted at saturation temperatures of -4 to 2$0^{\circ}C$, heat fluxes of 12 to 20 ㎾/$m^2$ and mass fluxes of 200 to 530 kg/$m^2$s. A comparison of different heat transfer correlations applicable to evaporation of carbon dioxide has been made. Based on the experiments for evaporation heat transfer and pressure drop, new correlations were developed. The newly developed empirical correlations for the heat transfer and pressure drop show average absolute deviations of 15.3% and 16.2%, respectively.

Decomposition of HFCs using Steam Plasma (스팀 플라즈마를 이용한 HFCs 분해특성)

  • Kim, Kwan-Tae;Kang, Hee Seok;Lee, Dae Hoon;Lee, Sung Jin
    • Journal of Korean Society for Atmospheric Environment
    • /
    • v.29 no.1
    • /
    • pp.27-37
    • /
    • 2013
  • CFCs (Chlorofluorocarbons) and HCFCs (Hydrochlorofluorocarbons) that are chemically stable were proven to be a greenhouse gases that can destroy ozone layer. On the other hand, HFCs (Hydrofluorocarbons) was developed as an alternative refrigerant for them, but HFCs still have a relatively higher radiative forcing, resulting in a large Global Warming Potential (GWP) of 1,300. Current regulations prohibit production and use of these chemicals. In addition, obligatory removal of existing material is in progress. Methods for the decomposition of these material can be listed as thermal cracking, catalytic decomposition and plasma process. This study reports the development of low cost and high efficiency plasma scrubber. Stability of steam plasma generation and effect of plasma parameters such as frequency of power supply and reactor geometry have been investigated in the course of the development. Method for effective removal of by-product also has been investigated. In this study, elongated rotating arc was proven to be efficient in decomposition of HFCs above 99% and to be able to generate stable steam plasma with steam contents of about 20%.

Performance of Refrigerator Using R134a, R152a and R22/142b (R134a, R152a, R22/142b를 이용한 냉동기의 성능실험)

  • Chang, Y.S.;Shin, J.Y.;Ro, S.T.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.6 no.1
    • /
    • pp.39-46
    • /
    • 1994
  • Experiments on the performance of refrigeration system using alternatives to R12 are carried out. The condenser and the evaporator are concentric-tube heat exchangers of counter-flow type and the compressor is driven by a variable speed motor. In this study, R134a, R152a, R22/142b(50 : 50 by mass) are adopted as alternatives to R12. Tests are performed by varying the inlet and outlet temperatures of secondary fluids of evaporator and condenser under the condition of constant compressor speed, degree of superheating and degree of subcooling. Results show that R134a has refrigeration capacity close to that of R12 and requires the greatest compressor power compared with that of others. And the system using R152a shows the best performance from the viewpoint of refrigeration capacity, compressor power and coefficient of performance. R22/142b is superior to R12 in the above points.

  • PDF