• Title/Summary/Keyword: ZnO Arrester

Search Result 100, Processing Time 0.028 seconds

A Study of Lightning Impulse Operating Duty and Temperature Dependence of Series Gap Type Arrester (Series Gap Type 피뢰기의 뇌임펄스 동작책무 및 온도의존성에 관한 연구)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.8
    • /
    • pp.659-664
    • /
    • 2009
  • This paper describes lightning impulse operating duty performance and temperature dependence of series gap type for transmission line arresters. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by lightning impulse current. In the discharge withstand test, total energy applied to the ZnO arrester each time is 4/10 ${\mu}s$, 30 kA. and in the operating duty test, the arrester has passed the test if thermal stability is achieved, if the residual voltage measured before and after the test is not changed by more than 5 %, and after the test reveals no evidence of puncture, flashover or cracking of the ZnO block. As a results, the residual voltage was in the range of 17.2${\sim}$20.3 kV and ZnO block bear up against at 2 shot of series impulse current of 30 kA. Also it was so excellent that the mechanical destruction does not occur at the 2 groups of 5 impulses current of 2/20 ${\mu}s$ 10 kA. According to the tests, it is thought that the ZnO arrester shows good stability with impulse current test. and it was found that the ambient temperature is increased resistive leakage current was increased in the range 47.3${\sim}$167.4 ${\mu}A$.

Characteristic Changes of ZnO Arrester Blocks by Multiple-lightning Impuse Currents (다중 뇌충격전류에 의한 산화아연형 피뢰기 소자의 특성 변화)

  • Gil, Gyeong-Seok;Han, Ju-Seop
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.49 no.12
    • /
    • pp.685-690
    • /
    • 2000
  • Multiple-lightning impulse currents are a general feature of the lightning ground f=flash. It is therefore necessary for lightning arresters used in power systems to be estimated by applying not only a single-lightning impulse current but also a multiple-lightning impulse currents. This paper presents the effects of multiple-lightning impulse currents on deterioration of ZnO arrester blocks. The multiple-lightning impulse generator which can produce quadruple 8/20$[\mus]$ 5[kA] with separation time of 30~120[ms] is designed and fabricated. The total energy applied to the arrester block at each impulse is about 1,200[J]. In experiment, various parameters such as leakage current component, reference voltage, and temperature are measured with the number of applied impulse current. Also, micro-structure changes of the ZnO blocks after applying the single and the multiple-lightning impulse currents of 200 times are compared. The experimental results indicate that the types of arrester blocks are more vulnerable to deterioration or damage by multiple-lightning impulse currents.

  • PDF

The characteristic of leakage current of ZnO block varistor according to fault conditions of three-phase four-wire distribution system (3상 배전계통의 고장조건에 따른 산화아연 피뢰기 소자의 누설전류 특성)

  • Lee, B.H.;Choi, H.S.;Kang, S.M.;Park, K.Y.;Lee, S.B.;Oh, S.K.
    • Proceedings of the KIEE Conference
    • /
    • 2003.11a
    • /
    • pp.174-177
    • /
    • 2003
  • Kinds of most frequent faults happened on overhead distribution system are the single line-to-ground fault, the line-to-line fault and the two line-to-ground fault. Occasionally, the three line-to-ground fault and the disconnection of a wire are happened in severe conditions. In this study, the single line-to-ground fault, the line-to-line fault, two line-to-ground fault on three-phase four-wire overhead distribution system were experimentally simulated and characteristics of total leakage current of distribution arrester caused by these faults were investigated. Also, the changing aspect of total leakage current of distribution arrester caused by voltage variation was investigated. In a consequence, abnormal voltages caused by voltage variation, the line-to-line fault, the two line-to-ground fault have a little effect on total leakage current of ZnO arrester. But abnormal voltages caused by the single line-to-ground fault have an important effect on total leakage current of ZnO arrester.

  • PDF

A Study on the Deterioration Progress of Railway Arresters (철도용 피뢰기의 열화진전에 관한 연구)

  • 길경석;한주섭;한문섭
    • Journal of the Korean Society for Railway
    • /
    • v.7 no.4
    • /
    • pp.307-311
    • /
    • 2004
  • Arresters are the best protective device on electrical power systems against transient overvoltages generated by lightning and/or switching operation. Nonetheless, arresters are deteriorated by absorption of moisture in the environments of its use, repetition in the protective operation to overvoltages, and some defects at manufacturing. It is therefore important to estimate the electrical characteristic changes of ZnO blocks. In this paper, an accelerated ageing test by a standard lightning impulse current was carried out to extract parameters needed for arrester diagnosis, and leakage current components were measured. Total energy applied to the ZnO blocks at each time is about 1,050[J] in 8/20[${\mu}\textrm{s}$] impulse current. From the experimental results, we proposed electrical parameters and leakage current level to diagnose arrester soundness.

Study on Surge Absorption Capability for Power Arrester with MOV Micro-milling Characteristics (전력용 피뢰기의 MOV 미립화와 에너지 내량 특성 연구)

  • Han, Se-Won;Cho, Han-Goo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.120-124
    • /
    • 2004
  • The protection performance and energy absorption capability are important for both MOAs for distribution lines and MOAs for high voltage systems, therefore the manufacturing technique of ZnO varistor elements with high ability against surge impacts is great important for high voltage systems. But until now ZnO varistors for low voltage class have been developed in Korea, ZnO varistors with the rate discharge current of 5, 10kA class for high voltage systems depend on an import from advanced countries, such as Japan or U.S.A, which have developed its in the late 1980s. So in the aspect of taking independent technique the development of ZnO varistors with the rate discharge current of 5, 10kA class for high voltage systems is important. In this research project ZnO varistor elements with diameters of 35mm and 70mm for the rate discharge current of 5, 10kA class for high voltage systems are manufactured, then various chemical composition and processing variables affected the electrical and the physical characteristics of these ZnO varistors are investigated.

  • PDF

Comparison on electrical characteristic changes of ZnO Arrester Blocks by Lightning Impulse Current (ZRO 피뢰기 소자의 뇌충격전류에 의한 전기적 특성 변화 비교)

  • Han, Joo-Sup;Park, Young-Ho;Kil, Gyung-Suk;Kim, Chan-Young
    • Proceedings of the KIEE Conference
    • /
    • 1999.11d
    • /
    • pp.1108-1110
    • /
    • 1999
  • This paper describes the comparison results on electrical characteristic changes of ZnO blocks by lightning impulse current. The five types of ZnO blocks used in lightning arrester for distribution lines have been estimated repeatedly till about 400 times by a standard lightning impulse current of 3kA, $8/20{\mu}s$, and changes of the performance characteristics of them to operation times were examined and compared quantitatively every fifty times discharge. It is expected that the result will be useful to diagnose the soundness of ZnO blocks or lightning arresters, and to develope deterioration diagnosis device for them.

  • PDF

A Technique of Deterioration Diagnosis for ZnO Element by Analyzing the 3rd order Harmonics- of Leakage Current (누설전류의 제3고조파 분석에 의한 ZnO소자의 열화진단기술)

  • Lee, Bok-Hee;Kang, Sung-Man
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1740-1742
    • /
    • 1998
  • This paper describes the technique of deterioration diagnosis for ZnO element. Due to the non-linear resistance of ZnO block, the total leakage current contains harmonics when arrester deteriorated. The most significant harmonics is the 3rd order component. So, it can be used as an indicator of the arrester condition. An iron core, which has a very high relative permeability, is used for increasing detection sensitivity and the 3th order harmonics of leakage current was detected by band-pass circuit. And we have verified the reliability and performance of the sensing device through several laboratory tests.

  • PDF

Change of the Microstructure of ZnO Arrester block by Lightning Surge Current and Ageing test (뇌서지전류와 Ageing에 의한 산화아연형 피뢰기 소자의 미세구조변화)

  • Lee, Bok-Hee;Kang, Sung-Man
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1877-1879
    • /
    • 2000
  • This paper deals with the change of the micro-structure of ZnO associated with lightning surge current and ageing test. In this work, a surge current generator which can produce 8/20 [${\mu}s$], 6 [kA] impulse current is designed and fabricated to simulate the lightning impulse current. The residual voltage and leakage current flowing to ZnO blocks are observed. Also a compensation circuit was used in resistive current measurement. The micro-structures of ZnO arrester block were significantly changed by lightning surge current and accelerated temperature ageing test.

  • PDF

Electrical Behaviors of ZnO Elements under Combined Direct and Alternating Voltages

  • Yang, Soon-Man;Lee, Bok-Hee;Paek, Seung-Kwon
    • Journal of Electrical Engineering and Technology
    • /
    • v.4 no.1
    • /
    • pp.111-117
    • /
    • 2009
  • This paper presents the characteristics of leakage currents flowing through zinc oxide (ZnO) surge arrester elements under the combined direct-current (DC) and 60 Hz alternating-current (AC) voltages. The current-voltage characteristic curves (I-V curves) of the commercial ZnO surge arrester elements were obtained as a function of the voltage ratio a. At constant peak value of the combined DC and AC voltage, the resistive leakage current of the ZnO blocks was significantly increased as the voltage ratio $\alpha$ increased. The I-V curves under the combined DC and AC voltages were placed between the pure DC and AC characteristics, and the cross-over phenomenon in both the I-V curves and R-V curves was observed at the low current region. The ZnO power dissipation for DC voltages was less than that for AC voltage in the pre-breakdown region and reversed at higher voltages.

Design and Performance Evaluation of Surge Arrester for Loading in Railway Rolling Stock (전철 탑재용 피뢰기의 설계 및 성능평가)

  • Cho, H.G.;Han, S.W.;Lee, U.Y.;Kim, S.S.;Chang, T.B.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.74-77
    • /
    • 2000
  • The main objective of this paper is to design and test a new type of polymer ZnO surge arrester for AC power system of railroad vehicles. Metal oxide surge arrester for most electric power system applications, electric train and must not have explosive breakage of the housing to minimize damage to other equipment when subjected to internal high short circuit current. When breakdown of ZnO elements in a surge arrester occurs due to flashover, fault short current flows through the arrester and internal pressure of the arrester rises. The pressure rise can usually be limited by fitting a pressure relief diaphragm and transferring the arc from the inside to the outside of the housing. However, there is possibility of porcelain fragmentation caused by the thermal shock. pressure rise, etc. Non-fragmenting of the housing is the most desired way to prevent damage to other equipment. The pressure change which is occurred by flashover become discharge energy. This discharge energy raises to damage arrester housing and arrester housing is dispersed as small fragment. Therefore, the pressure relief design is requested to obstruct housing dispersion. The main research works are focused on the structure design by finite element method, pressure relief of module, and studies of performance of surge arrester for electric railway vehicle.

  • PDF