Weak Feed 전력계통의 블랙스타트와 고조파 공진 사례연구 (A Case Study of Harmonic Resonance & Black Start in Weak Feed Power System)

  • 박영철;이은섭;손효수;이석현
    • 전기학회논문지
    • /
    • 제65권1호
    • /
    • pp.40-50
    • /
    • 2016
  • In order to recover the power system during the wide power outage or power failure in the power plant, black start system should be properly operated without any problem. Especially power for black start in the geographically isolated areas of electric island is supplied from small emergency start-up generator, and loads are aux systems of gas turbines such as SFC(Static frequency converter). This paper introduces the international practices to overcome the voltage drop problem with harmonics of the system having the DC output such as SFC during black start in weak feed system and analyzes the relationship between house load inputs and harmonics. By varying the house load and input of power supply, this paper identified boundaries between weak feed and strong feed power. In order to verify the theory of stable condition in weak feed power system with DC output, house load is simulated using ETAP. Additionally MATLAB was used for harmonic analysis between the load inertia moment and non load inertia moment.

High-Pass-Filter-Based Virtual Impedance Control for LCL-filtered Inverters Under Weak Grid

  • Wang, Jiangfeng;Xing, Yan;Zhang, Li;Hu, Haibing;Yang, Tianyu;Lu, Daorong
    • Journal of Power Electronics
    • /
    • 제18권6호
    • /
    • pp.1780-1790
    • /
    • 2018
  • Voltage feed-forward control (VFFC) is widely used in LCL-type grid-tied inverters due to its advantages in terms of disturbance rejection performance and fast dynamic response. However, VFFC may worsen the stability of inverters under weak grid conditions. It is revealed in this paper that a large phase-lag in the low-frequency range is introduced by VFFC, which reduces the phase margin significantly and leads to instability. To address this problem, a novel virtual-impedance-based control, where a phase-lead is introduced into the low-frequency area to compensate for the phase lag caused by VFFC, is proposed to improve system stability. The proposed control is realized with a high-pass filter, without high-order-derivative components. It features easy implementation and good noise immunity. A detailed design procedure for the virtual impedance control is presented. Both theoretical analysis and experimental results verify the effectiveness of the control proposed.