Development of Ground Impedance Measuring Instrument for Lightning Protection System (뇌보호 설비를 위한 접지임피던스 측정기 개발)

  • Lee, Tae-Hyung;Cha, Sung-Chul;Earn, Ju-Hang
    • Proceedings of the KIEE Conference
    • /
    • 2006.10a
    • /
    • pp.194-195
    • /
    • 2006
  • This study evaluated the impedance characteristics of earth termination system and developed a variable frequency-typed inverter (measuring tool) for the utilization in ground design for lightning protection. The variable-frequency-typed inverter were composed of rectification part, voltage adjuster, IGBT controller and measuring part. Meanwhile, the square wave signal of variable frequency converted its frequency up to lightning surge band by using an IGBT after rectifying an alternating current (AC). It conducted performance evaluation of ground impedance of actual earth termination system by using the developed measuring tool for ground impedance and confirmed that such impedance-oriented performance evaluation was effective in the design of lightning protection.

  • PDF

Log Count Rate Circuits for Checking Electronic Cards in Low Frequency Band Reactor Power Monitoring (저주파수대의 원자로 출력신호 점검을 위한 대수 카운트레이트 회로)

  • Kim, Jong-ho;Che, Gyu-shik
    • Journal of Advanced Navigation Technology
    • /
    • v.24 no.6
    • /
    • pp.557-565
    • /
    • 2020
  • In order for thermal degradationIn, excore nuclear flux monitoring system, as a monitoring and signal processing methodology of reactor power, monitors neutron pulses generated during nuclear fission as frequency status, and converts them into DC voltage, and then log values resultantly. The methods realy applied in the nuclear power plant are to construct combination of counters and flip-flops, or diodes and capacitors up to now. These methodes are reliable for relative high frequencies, while not credible for reasonable low frequencies or extreme low values. Therefore, we developed the circuit that converts frequencies into DC voltages, into and into log DC values in the wide range from low Hz to several hundred high kHz. We proved their validities through testing them using real data used in nuclear power plant and analyzed their results. And, these methods will be used to measure the neutron level of excore nuclear flux monitoring system in nuclear power plant.