• Title/Summary/Keyword: Vestibule of smokeproof stairway

Search Result 2, Processing Time 0.016 seconds

Experimental Study on Features of Air Egress Velocity in Vestibule Pressurization System (특별피난계단 부속실 제연설비의 방연풍속 기류특성에 관한 실험적 연구)

  • Ryu, Sung-Ho;Lee, Su-Kyung;Hong, Dae-Hwa;Yoon, Myong-O;Choi, Keum-Ran;Park, Jae-Hyun
    • Fire Science and Engineering
    • /
    • v.24 no.5
    • /
    • pp.79-86
    • /
    • 2010
  • In this study, we confirmed the fact that air egress velocity of pressure differential system which is installed in vestibule of smokeproof stairway in domestic high-rise building becomes back-flow into the vestibule not into the livingroom when the doors open to escape in case of fire by actual measurement. It concerned that fire smoke inflow into the vestibule of smokeproof stairway. so, reflux symptoms were developing the condition does not occur by creating an area of $2m^2$ and a model. if it‘s area is less, airflow in upper area was severely reflux. in the case upward 45 gradient of supply damper’s angle of blade, The results that reflux symptoms include upper door but bottom has some reflux. also vestibule of smokeproof stairway‘s area of $4m^2$ in the living room door in the direction of the flow distributon was normal. if a vestibule of smokeproof stairway is smaller, it designed to be performance-based design should be.

Characteristics of Air Egress Velocity in Vestibule Pressurization System Using the Fire Dynamics Simulator (FDS를 이용한 특별피난계단 부속실 제연설비의 방연풍속 기류특성)

  • Ryu, Sung-Ho;Lee, Su-Kyung;Hong, Dae-Hwa;Choi, Keum-Ran
    • Fire Science and Engineering
    • /
    • v.24 no.6
    • /
    • pp.153-159
    • /
    • 2010
  • In this study, we confirmed the fact that air egress velocity of pressure differential system installed at vestibule of smokeproof stairway in domestic high-rise building becomes back-flow to stair-lobby at upper vestibule. Rather it do not back-flow to the livingroom. when fire occur and the door opens to escape from fire zone. so we carry out actual and computational fluid dynamics measurement. In the case upward 45 gradient of supply damper's blade, The simulation results that air flow of upper vestible is steady but back-flow phenomenon occurred at the bottom. However, in the case of $4m^2$, direction of the flow was ideal to living room. If a vestibule’s area is smaller, it must be designed and built according to performance-based design.