• Title/Summary/Keyword: Very fast transient overvoltage

Search Result 6, Processing Time 0.024 seconds

Analysis of Magnitude and Rate-of-rise of VFTO in 550 kV GIS using EMTP-RV

  • Seo, Hun-Chul;Jang, Won-Hyeok;Kim, Chul-Hwan;Chung, Young-Hwan;Lee, Dong-Su;Rhee, Sang-Bong
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.1
    • /
    • pp.11-19
    • /
    • 2013
  • Very Fast Transients (VFT) originate mainly from disconnector switching operations in Gas Insulated Substations (GIS). In order to determine the rate-of-rise of Very Fast Transient Overvoltage (VFTO) in a 550 kV GIS, simulations are carried out using EMTP-RV. Each component of the GIS is modeled by distributed line model and lumped model based on equivalent circuits. The various switching conditions according to closing point-on-wave and trapped charge are simulated, and the results are analyzed. Also, the analysis of travelling wave using a lattice diagram is conducted to verify the simulation results.

Introduction of Insulation Coordination for UHV AC Systems

  • Shim, Eungbo;Zaima, Eiichi
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.1293-1297
    • /
    • 2015
  • This paper introduces the insulation coordination study results for UHV AC systems which was performed by CIGRE working group. The study results will be discussed within IEC technical committee in order to amend the IEC Insulation Coordination 60071-1 Ed. 8 2010 and 60071-2 Ed. 3, 1996. This paper includes the insulation coordination of transformer, gas insulated switchgear, metal oxide arresters and clearances of transmission towers. This article also illustrates the overvoltage specific to UHV systems such as TOV(temporary overvoltage), switching overvoltage, lightning overvoltage and VFTO(very fast transient overvoltage).

Analysis of Transient Overvoltages within a 345kV Korean Thermal Plant

  • Yeo, Sang-Min;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • v.7 no.3
    • /
    • pp.297-303
    • /
    • 2012
  • This paper presents the simulation results for the analysis of a lightning surge, switching transients and very fast transients within a thermal plant. The modeling of gas insulated substations (GIS) makes use of electrical equivalent circuits that are composed of lumped elements and distributed parameter lines. The system model also includes some generators, transformers, and low voltage circuits such as 24V DC rectifiers and control circuits. This paper shows the simulation results, via EMTP (Electro-Magnetic Transients Program), for three overvoltage types, such as transient overvoltages, switching transients, very fast transients and a lightning surge.

Development of Measurement System of Very Fast Transient Overvoltage (과도급준파전압측정계의 개발에 관한 연구)

  • Lee, B.H.;Kil, G.S.;Chung, S.J.;Kim, J.N.;Lee, J,S.;Lee, H.H.;Kim, J.K.;Lee, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1523-1525
    • /
    • 1994
  • This paper describes a proposed very fast transient overvoltages(VFTO) measurement system suited for established gas insulated switchgear(GIS). The detecting system consists of a shield electrode connected to a buffer amplifier, and the transmission of the detected signal to an oscilloscope is made through an optical fiber. The bandwidth of the measurement system is 5 Hz to 30MHz. When determining the voltage dividing ratio by use of the commercial frequency voltage, the error is less than 0.5 %. Also, the data were obtained by the electric field probe and the high voltage probe, and their deviation for voltage dividing ratio were less than 1 %.

  • PDF

Analysis of Rate-of-rise of VFTO Measured in Transformer During the Operation of Disconnector (단로기 조작 시 변압기 단자에서 측정된 VFTO의 상승률 분석)

  • Lee, Ji-Young;Oh, Yun-Sik;Seo, Hun-Chul;Kim, Chul-Hwan
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.45-46
    • /
    • 2011
  • 단로기와 회로 차단기의 스위칭 동작에 의해 발생하는 Very Fast Transient Overvoltage(VFTO)는 변압기, 회로차단기 등 GIS 전력소자에 큰 충격을 주어 잠재적인 위험이 된다. VFTO는 전력기기 소자 및 절연체 손상의 주된 원인이므로 시스템을 설계할 때 반드시 VFTO 최대값을 고려해야 한다. 본 논문에서는 55kV Gas Insulated Substation(GIS)를 분포정수회로기반으로 모델링하여 다양한 투입위상각에 따른 VFTO 상승률을 모의하였다. 이때, EMTP-RV를 이용하여 변압기로 전파된 VFTO를 측정하여 그 경향을 분석하였다.

  • PDF

Dielectric Characteristics of N2 Gas under Impulse Voltage in a Quasi-Uniform Electric Field (준평등전계에서 임펄스전압에 대한 N2가스의 절연파괴특성)

  • Lee, Bok-Hee;Kim, Dong-Kyu;Li, Feng
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.8
    • /
    • pp.126-132
    • /
    • 2010
  • This paper presents dielectric characteristics of $N_2$ gas under impulse voltages in a quasi-uniform electric field gap. The experiments were carried out at the test gap applied by the 1.2/50[${\mu}s$] lightning impulse voltage, 180/2500[${\mu}s$] switching impulse voltage, 500[ns]/1[MHz] very fast transient overvoltage(VFTO). The gap separation of sphere-to-plane electrodes was 14[mm] and the electric field utilization factor was about 71.2[%]. The gas pressure ranges from 0.2 to 0.6[MPa]. As a result, the electrical breakdowns are occurred by streamer discharge. Breakdown voltages are linearly increased with the gas pressure and the highest breakdown voltage is appeared under the VFTOs having fast rising time. Breakdown voltages under the positive impulse voltages were higher than those under the negative ones, and also the time to breakdown in the positive polarity is longer than that in the negative polarity.