• 제목/요약/키워드: Ventilating Fan

검색결과 31건 처리시간 0.027초

분배계통에 따른 지하주차장 환기설비 성능의 예측

  • 김경환;이재헌;오명도;김종필
    • 설비공학논문집
    • /
    • 제13권10호
    • /
    • pp.982-992
    • /
    • 2001
  • In this paper, the performance of ventilation equipments in enclosed parking garages were investigated for several air distribution systems by numerical method. Air change effectiveness of the non-mixing system was 0.42. It meant that more supply air as much as the design supply air was needed to maintain good indoor air quality. In the high speed nozzle ventilating system which is most expensive one, air change effectiveness was 0.54. Therefore this system satisfied to ventilation design. In the jet fan ventilating systems, air change effectiveness for jet fan ventilating system-A with 18 jet fans and jet fan ventilating system-B with 6 jet fans in circulation mixing arrangement were 0.565 and 0.42 respectively. Jet fan ventilating system-C with 6 jet fans in transport mixing arrangement was 0.535. Jet fan ventilating system-A and jet fan ventilating system-C met the ventilation design. But velocity in jet fan ventilating system-A was over 2.0m/s which is inappropriate in human comfort. Therefore this system is not proper to ventilation. Jet fan ventilating system-C was the optimum one for enclosed parking garages among 5 systems examined in this paper.

  • PDF

미세 다공판을 이용한 환기팬 시스템의 소음저감 (Noise Reduction of a Ventilating Fan System using Micro-Perforated Panel)

  • 이종석;송화영;이동훈;권혁정;김동윤
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2006년도 춘계학술대회논문집
    • /
    • pp.1209-1211
    • /
    • 2006
  • This paper introduces an experimental study for the noise reduction of a ventilating fan system. For the purpose of noise reduction, conventionally an absorptive duct silencer filled with a glass fiber has been utilized. However, a glass fiber has some disadvantages like hygiene and secondary pollution problems. In order to overcome these problems, in this paper, a perforated duct silencer has been applied to the ventilating fan system. For the designing of a perforated duct silencer, the transmission losses for various perforated panel systems are measured and compared with its noise reduction performance.

  • PDF

환기팬 시스템의 소음특성과 저감에 관한 실험적 연구 (An Experimental Study on the Noise Characteristics and Reduction of a Ventilating Fan System)

  • 김덕한;이동훈;권혁정;김동윤;이종석
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.500-505
    • /
    • 2005
  • This paper introduces an experimental study for the noise characteristics and reduction of a ventilating fan system. For the purpose of noise reduction of it, an absorptive duct silencer filled with a glass fiber has been conventionally utilized. However, a glass fiber has some disadvantages like hygiene and secondary pollution problems. In order to overcome these problems, in this paper, a perforated duct silencer has been applied to the ventilating fan system. For the designing of a perforated duct silencer, the transmission losses for various perforated panel systems are measured and compared with their sound absorption performances.

  • PDF

무 구속·구속 실험에 의한 환풍기 온도 특성 (The Characteristic of Temperature in Ventilating Fans by Festraint or Nonrestraint)

  • 김성삼
    • 조명전기설비학회논문지
    • /
    • 제30권1호
    • /
    • pp.44-48
    • /
    • 2016
  • In this paper, we analyzed the operating characteristics of a ventilating fan due to overload and overheating. The experiment assumed the forcible restraint of the blade due to external objects and the aging process. We analyzed the experimental temperature and operating characteristics of the three places in the interior of the ventilating fan. As a result of the analysis, the temperature distribution was highest to lowest in the following order: the thermal fuse, the motor inside, and the above winding. There was smell of burning enamel in the restraint experiment. Following the thermal fuse operation, the insulation of motor winding was good. In the case of rated voltage and new ventilating fan restrained for about 4hours, and the results of restraint experiments in the presence or absence of the thermal fuse, no risk of deformation or fire due to overheating was identified. Henceforward, ignition hazard experiments will be required for additional factors of aging, pollution, and defective insulation.

지하 수처리시설 유지관리층 환기설비의 성능평가 (Evaluation of the Ventilation Efficiency in an Underground Sewage Disposal Plant)

  • 강한기;이재헌
    • 설비공학논문집
    • /
    • 제19권10호
    • /
    • pp.695-702
    • /
    • 2007
  • In this paper, the ventilation efficiencies of an underground sewage disposal plant were investigated for ventilating system without fan, ventilating system with eleven cross flow fans and ventilating system with sixteen cross flow fans by numerical method. It has been found that the air change effectiveness of the system without fan was predicted 0.44. It means that an additional ventilating equipment is needed to maintain good indoor air quality. For the ventilating system with sixteen cross flow fans, the air change effectiveness was predicted 0.55. The air change effectiveness of the ventilating system with eleven cross flow fans was predicted 0.51. It is known that the air change effectiveness above 0.5 is enough to eliminate pollutant and bad smell in the indoor. Therefore, it is recommended to select the ventilating system with eleven cross flow fans for the underground sewage disposal plant in an economic point of view.

다수의 열원을 가지는 공간에서의 환기 조건에 따른 열환경 해석 (Thermal Environment Analysis of a Room in Accordance with Ventilation Condition with Multi-Heat Sources)

  • 김재중;손영갑;장석원;유동수
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2000년도 추계학술대회논문집B
    • /
    • pp.199-204
    • /
    • 2000
  • This paper reports a thermal environmental analysis of a room in accommodated with multi-heat sources according to ventilation condition. Two case modification have been investigated to obtain the lower temperature distribution in the room. The temperature distribution of the original room were found about $25{\sim}35^{\circ}C$. As a result, the use of, three ventilating fans and two electric fans are useful for room ventilation respectively, and using two electric fan is more recommendable in side of economical efficiency.

  • PDF

지하주거의 실내공기환경 실태조사와 CO2 조절기 및 타이머에 의한 환기팬 자동운전에 관한 연구 (A Study on the Actual Conditions of Indoor Air Quality of Underground Dwellings and the Automatic Ventilating Fan Operated by CO2 Controller and Timer)

  • 권영철;박진철
    • KIEAE Journal
    • /
    • 제8권4호
    • /
    • pp.3-9
    • /
    • 2008
  • The rapid urbanization after 1970s caused the shortage of dwellings in urban areas. As the result, the underground dwellings were developed to compensate for the insufficient dwelling spaces. While the underground dwellings have some advantage in the respect of thermal and acoustic environment, they usually have the basic problems in the indoor air quality because of the lack of natural ventilation through small window areas. The purpose of this study is to investigate and to improve the indoor air quality of underground dwellings. Thirty Units in Seoul and Gyung-Gi Province were investigated into the indoor environmental conditions. For the purpose of the improvement of their indoor air quality, Automatically-operated ventilating fan was installed in a sample unit which has worst indoor environmental condition. Then the indoor air quality was monitored when it was operated by $CO_2$ control system and timer. Finally economic feasibility study was made considering the effect of the improvement of indoor air quality. The extra cost for installing timer could be paid back only in 10 months, so timer-installed automatic fan is recommended to improve the indoor air quality of underground dwellings.

환기용 축류팬의 가이드핀 블레이드 형상변화에 따른 유동특성에 관한 연구 (Effects of a Guide Fin Blade on the Flow Characteristics in a Ventilating Axial Fan)

  • 박홍광;이지근;노병준
    • 설비공학논문집
    • /
    • 제19권12호
    • /
    • pp.874-882
    • /
    • 2007
  • The effects of a guide fin blade on the flow characteristics in a ventilating axial fan were investigated experimentally. The guide fins were setup onto the pressure surface of the blade, and their effects on the flowrate were evaluated. Two types of the guide fin blade were designed. One is the stem fin blade, and the other is the radial fin blade. The stem fin is designed normal to the circumference of a circle, and the radial fin is designed along the circumference of a circle. The results from the guide fin blade fans are compared with that of the blade without guide fins. The position and the geometry of the radial fin setting up on the blade have an effect on the increase of flowrate with the minor sacrifice of rotational speed of the blades. The radial fin positioning at 0.84 times blade diameter shows highest performance in the flowrate. The increase of the blade weight resulting from applying the guide fins shows minor effect on the variation of rotational speed of the blades.

제트 홴 방식 환기시스템을 사용하는 터널의 환기량에 영향을 주는 인자에 대한 수치해석 검토 (A Numerical Analysis on the Effect of Parameters for the Flow Rate through the Tunnel with Jet Fan Ventilating System)

  • 김사량;김기정;허남건;김영일
    • 설비공학논문집
    • /
    • 제14권7호
    • /
    • pp.567-574
    • /
    • 2002
  • In the present study, ventilation flow rates and pressure rises through a road tunnel are simulated numerically using CFD with the various conditions such as roughness height, swirl angle of jet fan, entrance and exit effect and hub to tip ratio. By using a modified wall function, friction factor can be predicted under 10% of error with respect to the Moody chart for the circular pipe flow and 15%, for the present tunnel. For more precise design, the effects of the swirl angle and hub to tip ratio of jet fan, which is not included in the theoretical equation of pressure rise by jet fan are necessary to be considered.

도로터널 환기/제연 시스템 시뮬레이션 (A NUMERICAL STUDY OF THE VENTILATION AND FIRE SIMULATION IN A ROAD TUNNEL)

  • 박종택;원찬식;허남건;차철현
    • 한국전산유체공학회지
    • /
    • 제11권4호
    • /
    • pp.20-25
    • /
    • 2006
  • In the present study, flow characteristics inside a road tunnel are simulated for the ventilation flows due to jet fan system and flows induces by the traffic. Traffic ventilation is numerically simulated by multiple reference frame. From the results of steady state simulation of tunnel ventilation, it is found that the proper ventilation is achieved by the designed jet fan system along with ventilating flow induced by the traffic. A transient simulation is also performed for the case of vehicle fire in the tunnel reversing the direction of rotation of some fans. The results suggest that the heat and smoke can be controlled by the proper changing of fan operation mode. The present results can be used to design proper ventilation system and effective smoke control system as well.