• 제목/요약/키워드: Vapor compressor

검색결과 92건 처리시간 0.022초

증기분사를 적용한 고온수용 지열 히트펌프의 성능특성 (Performance of the Geothermal Heat Pump using Vapor Injection for Hot Water)

  • 박용정;박병덕
    • 한국수소및신에너지학회논문집
    • /
    • 제25권3호
    • /
    • pp.297-304
    • /
    • 2014
  • The purpose of this study is to evaluate the experimental performance characteristics of a water-to-water geothermal heat pump featuring a vapor refrigerant injection for the production of hot water. The performance of geothermal heat pump with a vapor injection was evaluated by comparing with that of a conventional geothermal heat pump without a vapor injection. For heating operation, the geothermal heat pump with a vapor injection is superior in COP and heating capacity. The vapor injection was more effective for supplying hot water while overloading. The vapor injection was effective for the improvement of the cooling capacity. However, the vapor injection was not effective for the increasing of COP according to the increased input of a compressor. The advantage of vapor injection in water-to-water geothermal heat pump become disappeared while cooling operation with lower part loading.

곡물냉각기의 성능해석을 위한 시뮬레이션 (Simulation for Performance Analysis of a Grain Cooler)

  • 박진호;정종훈
    • Journal of Biosystems Engineering
    • /
    • 제26권5호
    • /
    • pp.449-460
    • /
    • 2001
  • This study was carried out to develop a simulation model with EES(Engineering equation solver) for analyzing the performance of a grain cooler. In order to validate the developed simulation model, several main factors which have affected on the performance of the gain cooler were investigated through experiments. A simulation model was developed in the standard vapor compression cycle, and then this model was modified considering irreversibe factors so that the developed alternate model could predict the actual cycle of a grain cooler. The compressor efficiency in vapor compression cycle considering irreversibility much affected on the coefficient of performance(COP). The COP in the standard vapor compression cycle model was greatly as high as about 6.50, but the COP in an alternative model considering irreversibility was as low as about 3.27. As a result of comparison between the actual cycle and the vapor compression cycle considering irreversibility, the difference of pressure at compressor outlet(inlet) was a little by about 48kPa (8.8kPa), the temperatures of refrigerant at main parts of the grain cooler were similar. and the temperature of chilled air was about 8$\^{C}$ in both. The model considering irreversibility could predict performance of the grain cooler. The theoretical period required to chill grain of 1,383kg from the initial temperature 24$\^{C}$ to below 11$\^{C}$ was about 55 hours 30 minutes, and the actual period required in a grain bin was about 58 hours. The difference between the predicted and an actual period was about 2 hours 30 minutes. The cooling performance predicted by the developed model could well estimate the cooling period required to chill the grain.

  • PDF

열압축기를 채용한 다중효용 담수설비의 운전특성에 관한 연구(1보) (A Study on the MED-TVC Operating Performance Characteristics of using the Thermo-Compressor)

  • 최두열;김창복;송영호;최순호;정한식;김필환
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제32권8호
    • /
    • pp.1185-1191
    • /
    • 2008
  • The core design technology for the multi-effect desalination plant using the thermo compressor (MED-TVC) was investigated by the performance test of multi effect desalination plant in this paper. The final G.O.R (gain of output ratio) of MED-TVC type desalination plant is strongly affected by the performance of thermo-vapor compressor. The present experiments for the desalinating capacity and G.O.R were obtained for the range of the motive steam pressure, 266.0, 250.0, 230.0 and 200.0 kPa. And as a practical problem, to investigate the influence of the sea water temperature to the G.O.R, the inlet steam temperature of the suction water vapor was changed in the range of $311.2{\sim}324.2$ K in the present experiment. Through the experiments, the maximum value of G.O.R was 8.5 at the condition of the motive steam pressure, 136.0 kPa and the minimum value of G.O.R was 8.1 at the condition of the motive steam pressure, 266.0 kPa. And it was confirmed that the range of desalination capacity was $355.2{\sim}264.0$ ton/day in the normal operation condition.

재열기를 사용한 고성능 VI 사이클 열펌프의 난방 성능 특성에 관한 연구 (A Study on the Characteristics of Heating Performance of High-Performance Heat Pump with VI cycle using Re-Heater)

  • 이진국;최광환
    • 동력기계공학회지
    • /
    • 제19권4호
    • /
    • pp.69-75
    • /
    • 2015
  • In this study, the characteristics of heating performance of a high-performance air-cooled heat pump with vapor-injection(VI) cycle using re-heater was investigated experimentally. Devices used in the experiment is consist of a VI compressor, condenser, oil separator, refrigerant (economizer outlet refrigerant) re-heater, economizer, evaporator. And R410A was used as a working fluid. The experiment was conducted with two cycles(cycles A and B) for investigating heating performance. In case of cycle B, heat exchange was conducted by re-heater between outlet refrigerant of compressor and suction refrigerant of the VI system(Fig.1, re-heater). But the re-heater was not used in case of cycle A. As a result of this experiment, discharge temperature of refrigerator in compressor was shown higher value, when the cycle B was conducted, because of the heat exchange between suction refrigerant of VI cycle and outlet refrigerant of compressor in the re-heater than cycle A that was not use re-heater. it means that liquid hammer and the decrement of heating performance can be decreased by using re-heater. Also, Heating coefficient of performance(COPh) was shown about 2.98 in Cycle B which was 4% higher than Cycle A and from these results, It was confirmed that the improvement of the heating performance of heat pump with VI cycle can be achieved by applying re-heater.

증기재압축용 원심압축기의 성능시험 (Performance test of centrifugal compressor for vapor recompression)

  • 전원표;김동국;김상현;양귀철;성병일;박용환
    • 한국에너지공학회:학술대회논문집
    • /
    • 한국에너지공학회 1999년도 추계 학술발표회 논문집
    • /
    • pp.165-170
    • /
    • 1999
  • 기계적 증기재압축(Mechanical Vapor Recompression) 시스템은 증기를 압축하여 압력을 올리면 온도가 상승하는 원리를 이용한 것으로서 시스템의 최종 증발관에서 발생한 저온의 증발증기를 전량 증기압축기로 압축ㆍ승온하여 자신의 최초 증발관의 가열 열원으로 재사용 하는 방식이다. 따라서 이 사이클에 필요한 보충열원은 가열측과 증발측과의 온도상승분 만큼만 증기의 포화온도를 올리면 되므로 에너지절약 효과가 매우 크다.(중략)

  • PDF

부하변화에 따른 hot-gas 바이패스 방식별 성능 비교 (Performance Comparison of Hot-gas Bypass Types with the Variation of Refrigeration Load)

  • 백승문;윤정인;손창효;허정호
    • 동력기계공학회지
    • /
    • 제18권5호
    • /
    • pp.48-54
    • /
    • 2014
  • In this paper, three refrigeration systems bypassing hot-gas to compressor outlet, compressor and condenser outlet and evaporator inlet are theoretically compared to offer basic design data for performance depending on cooling load using a HYSYS program. The main results are summarized as follows : First, the COP of third system is the highest. Next, the COP of second system is higher than first one. And, the temperature of compressor inlet of third system is constant for all cooling load. Compared to first and second system, the compressor inlet temperature of the first system is higher than second one for all cooling loads. From the above results, third system, which is bypassing hot-gas to evaporator inlet, is more advantageous when considering the precise temperature control and excellent performance of oil and water cooler of industrial machine.

에어 드라이어 제습성능 최적화 프로그램 개발 (A Study on Optimizing Drying Performance of Air Dryer)

  • 박원기;이희관;양균의;문상돈
    • 한국자동차공학회논문집
    • /
    • 제18권6호
    • /
    • pp.70-75
    • /
    • 2010
  • Compressed air represents an energy source and an force-transmission medium for brake systems on medium-heavy and heavy-duty commercial vehicles. However, one disadvantage is the tendency of air to absorb moisture in the form of water vapor. This water vapor condenses once the air, which is heated during compression, cools back to ambient temperature upon emerging from the air compressor. The resulting condensation assumes the form of moisture in pneumatic lines, air tanks, cylinders and valve assemblies and can have negative consequences for the brake system and vehicle safety. The pneumatic systems on today's vehicles are equipped with air dryers, in which the supplied air is dried according to the adsorption principle. In the systems, the compressed air flows through a granular desiccant with molecular sieves which captures the water molecules.

가변속 증기압축 냉동시스템에서 고장시의 성능변화와 고장 감지 및 진단에 관한 연구 (Studies on the Performance Variation of a Variable Speed Vapor Compression System under Fault and Its Detection and Diagnosis)

  • 김민성;김민수
    • 설비공학논문집
    • /
    • 제17권1호
    • /
    • pp.47-55
    • /
    • 2005
  • An experimental study has been peformed to develop a scheme for fault detection and diagnosis(FDD) in a vapor compression refrigeration system. This study is to analyze fault effect on the system performance and to find efficient diagnosis rules for easy determination of abnormal system operation. The refrigeration system was operated with a variable speed compressor to modulate cooling capacity. The FDD system was designed to consider transient load conditions. Four major faults were considered, and each fault was detected over wide operating load range by separating the system response to the load change. Rule-based method was used to diagnose and classify the system faults. From the experimental results, COP degradation due to the faults in a variable speed system is severer than that in a constant speed system. The method developed in this study can be used in the fault detection of refrigeration systems with a variable speed compressor.

An Experimental Investigation of Thermodynamic Performance of R-22 Alternative Blends

  • Kim, Chang-Nyeon;Park, Young-Moo
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제6권
    • /
    • pp.36-44
    • /
    • 1998
  • R-410a and R-407c which have the best potential among R-22 alternatives were tested as drop-in refrigerants against a set of R-22 baseline tests. The performance evaluations were carried out in a psychometric calorimeter test facility using the residential spilt type air conditioner under the ARI rating conditions. Except the lubricant and hand-operated expansion valve, the other parts of the air conditioner were the same with the commercial system. Performance characteristics were measured; compressor power, capacity, VCR, mass flow rate and COP. The tests showed that R-407c can be directly charged into the current refrigeration system because its vapor pressure and other thermochemical properties are similar to those of R-22. However, it is required to change the volume flow rate of compressor in order to achieve the volumetric capacity of R-22. This results from its relatively small VCR and capacity. Meanwhile, R-410a has vapor pressure values too high to be substituted for the current system and this resulted relatively low COP of R-410a compared to that of R-22.

  • PDF

증기압축식 에어컨의 냉매 충전량에 따른 성능 예측 (A Theoretical Evaluation of the Effect of Refrigerant Charge on the Performance of Vapor-Compression Air-Conditioning System)

  • 이경중;방광현
    • 설비공학논문집
    • /
    • 제12권5호
    • /
    • pp.486-493
    • /
    • 2000
  • A theoretical model for the transient performance of vapor-compression air-conditioning system has been developed to evaluate the influence of the refrigerant charge on the system performance. A set of mass and energy equations for the simulation of the heat exchangers and the capillary tube and a polytropic compression model for the compressor are used. The present model successfully predicts the transient behavior of the vapor-compression air-conditioner from the startup. As the refrigerant charge is increased, both the evaporating and condensing pressures increase gradually, and the cooling rate and the COP show a maximum in the range of 0.75-0.8 kg of refrigerant charge. This amount of refrigerant mass is determined to be the optimum charge of the model system. Also, the effect of outdoor air temperature on the optimum refrigerant charge is discussed.

  • PDF