  • The minimum airflow of VAV terminal boxes is a key factor for comfort, indoor air quality(IAQ) and energy cost. If the minimum airflow is not reasonable, it would waste energy and make IAQ problems. There are two types of VAV terminal box control logic. One is the single maximum, another is the dual maximum control logic. Dual maximum control logic is more efficiency way to reduce the energy consumption. It has a minimum airflow set point and a heating maximum set point. It allows the minimum airflow set point to be much lower than single maximum control logic. A building simulation was conducted to evaluate the energy consumption and the IAQ according to the control logic of the V AV terminal box. In the simulation, dual maximum control logic can save the energy up to 6.5% compared to the single maximum control logic.