• Title/Summary/Keyword: Underground valve station

Search Result 3, Processing Time 0.017 seconds

Investigation of Ventilation Efficiency for the Natural Gas High Pressure Release in an Underground Valve Station (지하 공급관리소내 천연가스 고압분출시 환기효율성 검증)

  • Ha J. M.;Lee J. H.;Sung W. M.
    • Journal of the Korean Institute of Gas
    • /
    • v.6 no.1 s.17
    • /
    • pp.74-80
    • /
    • 2002
  • This study was carried out for the purpose of safety evaluation about the ventilation system (according to the structure of confined room, the position and size of vent window, the amount of blowing air, e.t.c.), which is equipped in one of KOGAS underground valve stations. Particularly, the effect of the fans placed in the upper region was focused in detail. Numerical simulation was conducted in order to predict the features of flow pattern and the diffusion of natural gas concentration. This work examined the ventilation system and resulted in proposing an optimal design of ventilation system.

  • PDF

A Study on the Reliability Analysis and Risk Assessment of Liquefied Natural Gas Supply Utilities (천연가스 공급설비에 대한 기기신뢰도 분석 및 위험성 평가)

  • Ko, Jae-Sun;Kim, Hyo
    • Fire Science and Engineering
    • /
    • v.17 no.1
    • /
    • pp.8-20
    • /
    • 2003
  • Natural gas has been supplied through underground pipelines and valve stations as a new city gas in Seoul. In contrast to its handiness the natural gas has very substantial hazards due to fires and explosions occurring from careless treatments or malfunctions of the transporting system. The main objectives of this study are to identify major hazards and to perform risk assessments after assessing reliabilities of the composing units in dealing with typical pipeline networks. there-fore two method, fault tree analysis ;1nd event tree analysis, are used here. Random valve stations are selected and considered its situation in location. The value of small leakage, large rupture, and no supply of liquefied natural gas is estimated as that of top event. By this calculation the values of small leakage are 3.29 in I)C valve station, 1.41 in DS valve station, those of large rup-lure are $1.90Times10_{-2}$ in DC valve station, $2.32$\times$10^{-2}$ in DS valve station, and those of no supply of LNG to civil gas company are $2.33$\times$10 ^{-2}$ , $2.89$\times$10^{-2}$ in each valve station. And through minimal cut set we can find the parts that is important and should be more important in overall system. In DC valve station one line must be added between basic event 26,27 because the potential hazard of these parts is the highest value. If it is added the failure rate of no supply of LNG is reduced to one fourth. In DS valve station the failure rate of basic event 4 is 92eye of no supply of LNG. Therefore if the portion of this part is reduced (one line added) the total failure rate can be decreased to one tenth. This analytical study on the risk assessment is very useful to prepare emergency actions or procedures in case of gas accidents around underground pipeline networks and to establish a resolute gas safety management system for loss prevention in Seoul metropolitan area.

Analysis of A Gas Explosion-Related State Compensation Case (가스폭발 사고와 관련된 국가배상 사례의 분석)

  • Lee, Euipyeong
    • Journal of the Society of Disaster Information
    • /
    • v.16 no.1
    • /
    • pp.44-59
    • /
    • 2020
  • This study analyzed a gas explosion accident. A gas smell from a underground coffee shop in the two-story building was reported to 119. A fire brigade was turned out, turned off the main valve of LPG gas cylinder on the roof, and checked the turning off of middle valve in the coffee shop. The fire brigade required a gas supplier and gas installer who arrived at the spot to take safety actions. Gas explosion occurred seven minutes after the fire brigade was withdrawn and two people died and 21 people were injured. A court decided that because the causes for gas explosion were not found, compensation responsibility could not be charged with the gas supplier, the gas installer, or Korea Gas Safety Corporation. In this reason, the court judged that only the fire brigade who was withdrawn without taking safety actions shall compensate victims or bereaved families. Therefore, fire brigades who turn out after a 119 report of a gas leak should take safety actions such as escaping people or preventing people's access and ventilating and be withdrawn when there is no possibility of fire or explosion.