• 제목/요약/키워드: Underbuilt Ground Wire

검색결과 2건 처리시간 0.026초

Underbuilt Ground Wire와 Guy Wire를 이용한 변전소 기기 보호에 관한 연구 (A Protection of Substation Equipment Applying Underbuilt Ground Wire and Guy Wire)

  • 김재관;이종범;조한구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.610-612
    • /
    • 2004
  • Because the overhead transmission lines are exposed to the outdoor weather, the faults of the transmission lines are due to natural conditions, and among these faults, the outage rate by lightning is about $50\%$. Therefore, the insulation design is important to decrease the damage of the facility and to increase the reliability of electric power system. This paper describes the protective method of substation equipments using the Underbuilt Ground Wire and the Guy Wire. This would not only reduce backflashover possibility but also minimize crest and duration of surges entering the substation. EMTP is used to analyze the efficiency of the proposed methods.

  • PDF

송전계통 및 변전소 뇌서지 보호방안 연구 (A Study on the Lightning Surge Protection Methods on Transmission System and Substation)

  • 김재관;정채균;이종범;조한구;서재호
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권6호
    • /
    • pp.279-285
    • /
    • 2005
  • The lightning causes the damage of power system equipments as well as large power failure. Therefore, the insulation design should be established not only to decrease the damage of the facilities itself but also to increase the reliability of electric power system. This paper describes the useful way applying underbuilt ground wire and guy wire in transmission tower that safely protect the substation equipments. One or more shield wires under the phase conductor will not intercept lightning stroke, but they may improve reduce lightning voltages almost as effectively as if they were above the phase conductors. And the guy wires will mitigate the tower surge response. These would not only reduce backflashover possibility but also minimize crest and duration of surges entering the substation. EMTP is used to analyze the efficiency of the proposed methods.