• 제목/요약/키워드: Unbalance and nonlinear load

검색결과 34건 처리시간 0.022초

선형 및 비선형 부하 사용시 전류 및 부하불평형률에 대한 연구 (A Study on the Current & Load Unbalance Factor in using Linear & Nonlinear Load)

  • 김종겸;김지명
    • 전기학회논문지
    • /
    • 제66권8호
    • /
    • pp.1291-1296
    • /
    • 2017
  • Single-phase and three-phase load can be used together in 3-phase 4-wire system. Single-phase and three-phase loads can be classified as linear loads without harmonics and nonlinear with harmonics. Single-phase linear loads are linear loads such as lamps and heat, and single-phase nonlinear loads are power converters such as rectifiers. It is recommended that the distribution of loads in the 3-phase, 4-wire distribution lines be evenly distributed within a certain range. However, harmonic currents generated in a nonlinear load flow on the neutral line and affect the phase current magnitude. The difference in the magnitude of the individual phase current due to the influence of the harmonic current present in the neutral line can produce a difference in current and load unbalance. In this study, current unbalance ratio and load unbalance ratio which can occur when a combination of linear and nonlinear loads are applied to 3-phase 4-wire distribution line are calculated.

비선형 부하의 증감에 따른 고조파 특성 분석 (Analysis on the Harmonics Characteristics Due to Increase & Decrease of Nonlinear Load)

  • 김종겸;이은웅
    • 전기학회논문지P
    • /
    • 제52권3호
    • /
    • pp.100-106
    • /
    • 2003
  • The increasing application of power electronic equipment in industrial field has led to a growing concern for harmonic distortion and the resulting impacts on system equipment and operations. Harmonic currents are generated by the operation of nonlinear loads and equipment on the power system. These are more increased by unbalance voltage of electrical distribution power systems. This paper describes harmonics characteristics generated by varying of nonlinear load at the PCC under the voltage unbalance.

불평형 전압으로 운전시 비선형 부하에 나타나는 현상 (The Phenomena Giving Rise of Nonlinear Load Operated by Unbalance Voltage)

  • 김종겸;이은웅
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제51권6호
    • /
    • pp.285-291
    • /
    • 2002
  • In general, utility voltage is maintained at a relatively low level of Phase unbalance since a low level of unbalance can cause a significant power supply ripple and heating effects on the power system equipment. Voltage unbalance more commonly emerges in individual customer loads due to phase load unbalanced, especially where single phase power loads are used. Under unbalanced input voltages large lower order harmonics appears at the input and output ports of Power conversion devices. As the application of adjustable -speed drives (ASDs) and their integration with complex industrial processes increase, so does the need to understand how ASDs perform during voltage This paper describes a real load test to investigate the performance of 3-HP adjustable speed drives by an unbalanced voltage at the low-voltage system.

3상 4선식 저압 배전선로에서 선형 및 비선형 부하의 사용시 전압 불평형률 비교 분석 (Comparative Analysis of Voltage Unbalance Factor on the use of Linear and Non-linear loads in Three-phase Four-wire Low Voltage Distribution Line)

  • 김종겸;김지명
    • 전기학회논문지
    • /
    • 제66권3호
    • /
    • pp.587-592
    • /
    • 2017
  • In the three-phase four-wire low-voltage power distribution equipment, single-phase and three-phase load have been used mainly mixed. Also linear and nonlinear loads have been used together in the same conditions. In a three-phase four-wire distribution line, the current distribution of three-phase linear load is almost constant in each phase during driving or stopping, but the single-phase load is different from each other for each phase in accordance with the operation and stop. So that the voltage unbalance is caused by the current difference of each phase. In the three-phase four-wire distribution system, non-linear load is used with linear load. The presence of single-phase nonlinear loads can produce an increase in harmonic currents in three-phase and neutral line. It can also cause voltage unbalance. In the present study, we analyzed for the voltage unbalance fluctuations by the operation pattern of the single and three-phase linear and non-linear load in three-phase four-wire low voltage distribution system.

불평형 전압으로 운전하는 비선형 부하의 고조파 특성 분석 (Analysis on the Harmonic Characteristics of Nonlinear Load Operated by Unbalance Voltage)

  • 김종겸;이은웅;이동주
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제52권10호
    • /
    • pp.491-500
    • /
    • 2003
  • Most of the loads in industrial power distribution systems are balanced and connected to three wires power systems. However, in the user power distribution systems, most of the loads are single & three phase and unbalanced, generating a large amount of non-characteristic harmonics. With the advent of power electronics and proliferation of non-linear loads in industrial power applications, power harmonics and their effects on power quality are a topic of concern. Harmonics by the unbalance voltage and non-linear loads, cause the increase of machine loss and heating. In order to allow current harmonic compensation, a filter must be installed. This paper describes the performance of passive filter under the voltage unbalance and non-linear load.

High-Performance Control of Three-Phase Four-Wire DVR Systems using Feedback Linearization

  • Jeong, Seon-Yeong;Nguyen, Thanh Hai;Le, Quoc Anh;Lee, Dong-Choon
    • Journal of Power Electronics
    • /
    • 제16권1호
    • /
    • pp.351-361
    • /
    • 2016
  • Power quality is a critical issue in distribution systems, where a dynamic voltage restorer (DVR) is commonly used to mitigate the voltage disturbances for loads. This paper deals with a nonlinear control for the three-phase four-wire (3P-4W) DVR under a grid voltage unbalance and nonlinear loads in the distribution system, where a novel control scheme based on the feedback linearization technique is proposed. Through feedback linearization, a nonlinear model of a DVR with a PWM voltage-source inverter (VSI) and LC filters is linearized. Then, the controller design of the linearized model is performed by applying the linear control theory, where the load voltages are kept constant by controlling the d-q-0 axis components of the DVR output voltages. To keep the load voltage unchanged, an in-phase compensation strategy is employed, where the load voltages are recovered to be the same as the previous voltage without a change in the magnitude. With this strategy, the performance of the DVR becomes faster and more stable even under unbalanced source voltages and nonlinear loads. The validity of the proposed control strategy has been verified by simulation and experimental results.

선형 및 비선형 부하에 적용 가능한 3상 전압변동 발생기의 스위칭 특성해석 (Switching Characteristics Analysis of a 3-phase Voltage Disturbance Generator Applicable to Linear and Nonlinear Loads)

  • 노의철;박성대;김인동
    • 전력전자학회논문지
    • /
    • 제13권3호
    • /
    • pp.163-170
    • /
    • 2008
  • 본 논문에서는 DVR 등의 전력품질 개선장치들의 성능시험에 용이하게 사용하기 위하여 제안한 3상 전압변동 발생기에 대하여 선형뿐만 아니라 비선형 부하에서도 동작이 가능함을 보이는 스위칭 특성해석을 하였다. 선형 부하의 경우는 전류가 연속이므로 전압변동 발생기를 구성하는 SCR 사이리스터의 자연전류(natural commutation)가 용이하게 발생하지만, 비선형 부하의 경우는 전류 불연속 모드 동작이 발생하여 SCR 사이리스터의 원활한 스위칭이 이루어질 수 없는 경우도 있다. 따라서 비선형 부하 시 전류 불연속 구간에서의 SCR 사이리스터의 스위칭 패턴을 분석하여 전압 새그(sag), 스웰(swell), 순간정전(outage), 전압불평형(voltage unbalance) 동작이 선형에서와 동일하게 발생되는 조건을 파악하였다. 각각의 기능을 발생시키는 원리와 동작 특성을 해석하였으며 시뮬레이션과 실험을 통하여 성능을 확인하였다. 본 논문에서 다룬 전압변동 발생기는 전원 외란 발생을 낮은 비용으로 구현해 낼 수 있고 구조와 제어가 간단하여 전력품질 개선과 관련된 연구를 하는데 용이하게 활용될 것으로 기대한다.

전압 불평형에서 콘덴서와 리액터의 직렬 연결시의 콘덴서의 특성 분석 (A Study on Condenser Characteristics at the Series Connection of Condenser and Reactor Under Voltage Unbalance)

  • 김일중;김종겸;박영진;김성헌
    • 전기학회논문지P
    • /
    • 제59권3호
    • /
    • pp.325-329
    • /
    • 2010
  • Capacitor has been used principally for the power factor compensation long ago. However now it does as passive filter to reduce harmonics of nonlinear load with reactor. Most of the customer's low-voltage feeder has been designed with approximately balanced and connected at the 3 phase four wire system. But voltage and current unbalance is appeared by the mixing operation of single or three phase load etc. The addition of reactor at the condenser may rise its terminal voltage. Voltage and current values above rating can act on electrical stress on the condenser. In this paper, we calculated and measured that voltage, current and capacity of condenser are changed under the voltage balance. We conclude that magnitude and deviation of phase voltage act on major point of electrical stress.

불평형 전압 공급시 비선형 부하의 고조파 특성 해석 (Analysis on the Harmonic Characteristics of Nonlinear Load operated by Unbalance Voltage)

  • 김종겸;이은웅;이동주;이화수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 B
    • /
    • pp.696-698
    • /
    • 2003
  • Most of the loads in industrial power distribution systems are balanced and connected to three wires power systems. However, in the user power distribution systems, most of the loads are single & three phase and unbalanced, generating a large amount of non-characteristic harmonics. With the advent of power electronics and proliferation of non-linear loads in industrial power applications, power harmonics and their effects on power quality are a topic of concern. Harmonics by the unbalance voltage and non-linear loads, cause the increase of machine loss and heating. In order to allow current harmonic compensation, a filter must be installed. This paper describes the performance of passive filter under the voltage unbalance and non-linear load.

  • PDF

마찰을 고려한 포일저널베어링의 동특성해석: 회전불균형 응답 (The Dynamic Performance Analysis of Foil Journal Bearings Considering Coulomb Friction: Rotating Unbalance Response)

  • 김경웅;이동현;김영철
    • Tribology and Lubricants
    • /
    • 제23권5호
    • /
    • pp.219-227
    • /
    • 2007
  • The dynamic performance of air foil bearings relies on a coupling between a thin air film and an elastic foil structure. A number of successful analytical techniques to predict dynamic performance have been developed. However, the evaluation of its dynamic characteristic is still not enough because of the mechanical complexity of the foil structure and strong nonlinear behavior of friction force. This work presents a nonlinear transient analysis method to predict dynamic performance of foil bearings. In this method, time dependent Reynolds equation is used to calculate pressure distribution and a finite element method is used to model the bump foil structure. The analysis is treated with a direct implicit integration technique that can handle nonlinear problems and the stick-slip algorithm is used to consider friction force. Using this method the response to the mass unbalance excitation is investigated for various design parameters and operating conditions. The results of analysis show that foil bearing is very effective on the restriction of vibration at the resonance frequency compared to the rigid surface bearings and the effectiveness depends on the operating conditions, static load and a amount of mass unbalance. In addition, there exist optimum values of friction coefficient, bump foil stiffness and number of circumferential slit with regards to minimizing dynamic response at the resonance frequency. These optimum values are system dependent.