Failure analysis of a transmission tower during a microburst

  • Shehata, A.Y.;El Damatty, A.A.
    • Wind and Structures
    • /
    • 제11권3호
    • /
    • pp.193-208
    • /
    • 2008
  • This paper focuses on assessing the failure of one of the transmission towers that collapsed in Winnipeg, Canada, as a result of a microburst event. The study is conducted using a fluid-structure numerical model that was developed in-house. A major challenge in microburst-related problems is that the forces acting on a structure vary with the microburst parameters including the descending jet velocity, the diameter of the event and the relative location between the structure and the jet. The numerical model, which combines wind field data for microbursts together with a non-linear finite element formulation, is capable of predicting the progressive failure of a tower that initiates after one of its member reaches its capacity. The model is employed first to determine the microburst parameters that are likely to initiate failure of a number of critical members of the tower. Progressive failure analysis of the tower is then conducted by applying the loads associated with those critical configurations. The analysis predicts a collapse of the conductors cross-arm under a microburst reference velocity that is almost equal to the corresponding value for normal wind load that was used in the design of the structure. A similarity between the predicted modes of failure and the post event field observations was shown.

절연암 적용 컴팩트 철탑 개발 (Development of Compact Towers with Insulation Arm in Korea)

  • Lee, Won-kyo;Yun, Cheol-Hee
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제4권2호
    • /
    • pp.63-66
    • /
    • 2018
  • Lattice towers and tubular steel poles have been commonly used for electrical power transmission in Korea as well as the other countries. They are durable, structurally stable, simple and can easily be constructed in limited spaces. However, residents are opposed to construct transmission lattice towers in their areas because they are not visually attractive, and electrical field occur at the transmission lines. Underground transmissions have been used instead of the traditional towers to resolve these problems, however they are not cost effective to construct and run. Therefore, we have developed compact towers that are more attractive, well blend into the surrounding environment and much more economical than underground transmissions. This paper shows the design of a compact towers with insulation arm, in order to reduce the height of tower and the separation between phases. The compact tower can be installed in a narrow right-of-way. Insulation arms are easily applied to lattice and steel tubular towers instead of steel arms. Compact towers with insulation arm are also considered as a solution to have public acceptance or to create a familiar atmosphere among towers and people. Compact tower compared with a conventional tower, insulation arms reduces the width and height of the tower by 20% and 15% respectively.

송전철탑의 내풍안전성 평가를 위한 1/2축소부분구조 실험 (Half-Scaled Substructure Test for the Performance Evaluation of a Transmission Tower subjected to Wind Load)

  • 문병욱;민경원
    • 한국전산구조공학회논문집
    • /
    • 제20권5호
    • /
    • pp.641-652
    • /
    • 2007
  • 본 논문에서는 풍하중에 대한 기존 송전철탑의 좌굴 및 구조적 안전성을 평가하기 위해서 축소부분구조 실험을 수행하였다. 원 송전철탑에 작용하는 중력 및 풍하중을 재현하기 위해서 1/2크기의 상사법칙을 적용한 축소모델의 상부에 설치된 삼각형태의 지그를 이용하여 가력하는 방법을 고안하였다. 설계하중에 대한 실험체의 안정성을 평가하기 위해서 예비수치 해석을 수행한 결과, 계산된 주주재의 축력은 허용좌굴하중의 $80{\sim}90%$사이에 분포하고 있음을 확인하였다. 최대허용좌굴 하중의 270%까지 가력한 결과, 주주재의 면외거동을 구속하는데 취약한 절점에서 발생한 국부좌굴로 인하여 송전철탑이 파괴되었다. 하중-변위 곡선, 변위, 부재별 변형률을 검토한 결과, 이러한 국부좌굴의 발생은 동일한 단면내에서도 휨모멘트로 인해 항복응력에 도달하는 시간이 위치별로 다르기 때문에 변형의 불균형에 의해서 발생한 부가적인 편심에 기인한 것으로 판단된다.

점토지반에서 하중특성 및 연결보조건에 따른 송전철탑용 연결형 말뚝기초의 특성 분석 (Analysis of Characteristics of Connected-pile Foundations for Transmission Tower according to Changes of Load and Connection Beam Conditions in Clay)

  • 경두현;이준환;백규호;김영준;김대홍
    • 한국지반공학회논문집
    • /
    • 제29권10호
    • /
    • pp.5-18
    • /
    • 2013
  • 부등침하는 연약지반에 시공되는 철탑기초에 있어서 주요한 손상을 야기한다. 송전철탑용 연결형 말뚝기초는 연약지반에서의 송전철탑기초의 부등침하를 방지하기 위한 구조물로서, 주기초체와 주기초체 사이에 위치하여 기초를 연결하는 연결보로 구성된다. 본 연구에서는 송전용 철탑기초에 작용하는 연결보의 영향을 조사하기 위하여, 전라북도에 위치한 건설현장에서 24회의 모형재하시험을 수행하였다. 시험에서는 다양한 하중조건과 연결보 조건이 고려되었으며, 시험결과 수평하중에 의한 연결형 말뚝기초의 발생변위가 철탑에 작용하는 수평하중의 각도에 따라 달라지는 것으로 나타났다. 연결형 기초의 침하는 연결보의 강성이 증가할수록 감소하였으며, 수평지지력은 수평하중이 재하되는 철탑의 높이가 낮을수록 증가하였고, 파괴시점에서의 하중의 크기는 대부분의 경우 하중재하방향에 상관없이 유사한 것으로 나타났다.

점토지반에 근입된 송전철탑 연결형 말뚝기초의 저항력증가계수 (Resistance Increasing Factor of Connected-pile Foundation for Transmission Tower in Clay)

  • 경두현;이준환;백규호;김대홍
    • 한국지반공학회논문집
    • /
    • 제28권8호
    • /
    • pp.31-41
    • /
    • 2012
  • 연약지반에 건설되는 송전철탑 말뚝기초는 부등침하로 인한 철탑구조체의 손상을 유발 할 수 있다. 이에 따라 일본과 미국에서는 철탑을 지지하는 각 기초부를 연결보로 연결한 연결형기초의 사용을 추천하고 있다(TEPCO 1988, IEEE 2001). 연결형 말뚝기초의 저항력증가계수는 연결체의 영향으로 인하여 증가되는 연결형 말뚝기초의 저항력의 증가량을 나타낸다. 본 연구에서는 점토지반에 근입된 송전철탑 연결형말뚝 기초의 모형수평재하시험을 수행하여 연결형 말뚝기초의 저항력증가계수를 도출하였다. 본 시험은 실트질 점토지반에서 수행되었으며, 수평하중의 재하높이와 재하각도, 말뚝기초를 연결하는 연결체의 강성을 변화시켜 다양한 조건상에서의 저항력 증가계수를 도출하였다. 본 연구에서 도출된 저항력 증가계수는 송전철탑의 하중작용높이와 기초를 연결하는 연결체의 강성에 대한 함수로 나타났으며, 도출된 증가계수를 통하여 연결형 말뚝기초의 저항력을 산정한 결과 측정결과와 비교적 일치하는 것으로 나타났다.

송전철탑의 내풍성능 향상을 위한 마찰형 보강기구 실험 (Experiment of Friction-type Reinforcing Members for Upgrading Wind-Resistant Performance of Transmission Towers)

  • 박지훈;문병욱;민경원
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2006년도 추계학술대회논문집
    • /
    • pp.884-892
    • /
    • 2006
  • A friction-type reinforcing member(FRM) is proposed for the purpose of upgrading wind resistant performance of a transmission tower and verified through cyclic loading tests. First, suitable install scheme of the FRM is investigated through numerical analysis. Main-post-reinforcing type and X-brace type installation schemes are examined, and numerical analysis shows that the former is more effective due to the vertical cantilever type behavior of the transmission tower. Based on this result, two types of the FRM's, dissipating energy in slotted belted connections, are proposed. The one utilizes the relative displacement between the FRM and the main post, and the other utilizes that between the separated angles consisting of the FRM as a slip deformation of the slotted bolted connection. Proposed FRM's are installed on each main post of the 1/2 scale substructure models of an actual transmission tower body. From cyclic loading tests, the latter type of the proposed FRM's dissipates energy more effectively and its slip load is controlled by applied torque well, and shares considerable amount of the axial force in the main post.

  • PDF

송전철탑의 기초침하에 대한 안정성 평가 (Stability evaluation of foundation settlement of power transmission tower)

  • 이대수;조화경;김대홍;함방욱
    • 한국지반공학회:학술대회논문집
    • /
    • 한국지반공학회 2005년도 춘계 학술발표회 논문집
    • /
    • pp.687-696
    • /
    • 2005
  • Safety diagnosis was conducted to evaluate the long-term stability evaluation of power transmission tower of which deformation of the upper structural elements occurred. To assess the cause of the structural deformation, field investigation including BIPS, down-hole test, concrete pile coring and finite element analysis were carried out. From these studies, the major cause of deformation was found due to the heavily fractured layer and weathered soil topography at the pile tip area. The cement-milk grouting method was proposed to reinforce these weak zone around the pile tip area. Also, the increase of cross-section and stiffness for steel members of upper tower structures was suggested. Instrumental monitoring was proposed as well to verify reinforcing effect.

  • PDF

송전선로 철탑기초의 접지저항 해석 (Analysis of the Earth Resistance for the Tower Footing of T/L)

  • 이현구;하태현;배정효;김대경
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.344-346
    • /
    • 2001
  • The sharing of common corridors by electric power transmission lines and pipelines is becoming more common place. However, such corridor sharing can result in undesired coupling of electromagnetic energy from the power lines to the near facilities. During a fault on any of the transmission lines, energization of the earth by supporting structures near the fault can result in large voltages appearing locally between the earth and the steel wall of any nearby pipeline. This paper presents the outline of the tower footings for the transmission lines having been used in KEPCO and analyzes the earth resistance for operation method of the tower footing, that is contact presence for the anchor and reinforcing rob of the tower and foundation presence of the underground wiring.

  • PDF

보조접지선 시공에 의한 송전선로의 내뢰성 향상효과 모의 (A Simulation of Lightning Faults Reducing Effects on the 154 kV Transmission Tower by Auxiliary Grounding)

  • 곽주식;심정운;심응보;최종기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1843-1846
    • /
    • 1997
  • This paper describes the fault reducing effects of the 154 kV transmission tower by auxiliary grounding from the top of the tower to ground. The grounding surge impedance of the auxiliary grounding system is calculated by CDEGS(:Current Distribution Electromagnetic Interference Grounding and Soil Structure Analysis), and the critical lightning back flashover current and arcing horn dynamic characteristics are simulated by EMTP/TACS(:Electromagnetic Transient Program/Transient Analysis of Control Systems). The calculated results of total LFOR(Lightning Flashover Rate) shows that the LFOR can be reduced from 5.2(count/100km. year) to 3.4 by auxiliary grounding on the 154 kV transmission tower with one ground wire shielding system.

  • PDF

Study on the influence of structural and ground motion uncertainties on the failure mechanism of transmission towers

  • Zhaoyang Fu;Li Tian;Xianchao Luo;Haiyang Pan;Juncai Liu;Chuncheng Liu
    • Earthquakes and Structures
    • /
    • 제26권4호
    • /
    • pp.311-326
    • /
    • 2024
  • Transmission tower structures are particularly susceptible to damage and even collapse under strong seismic ground motions. Conventional seismic analyses of transmission towers are usually performed by considering only ground motion uncertainty while ignoring structural uncertainty; consequently, the performance evaluation and failure prediction may be inaccurate. In this context, the present study numerically investigates the seismic responses and failure mechanism of transmission towers by considering multiple sources of uncertainty. To this end, an existing transmission tower is chosen, and the corresponding three-dimensional finite element model is created in ABAQUS software. Sensitivity analysis is carried out to identify the relative importance of the uncertain parameters in the seismic responses of transmission towers. The numerical results indicate that the impacts of the structural damping ratio, elastic modulus and yield strength on the seismic responses of the transmission tower are relatively large. Subsequently, a set of 20 uncertainty models are established based on random samples of various parameter combinations generated by the Latin hypercube sampling (LHS) method. An uncertainty analysis is performed for these uncertainty models to clarify the impacts of uncertain structural factors on the seismic responses and failure mechanism (ultimate bearing capacity and failure path). The numerical results show that structural uncertainty has a significant influence on the seismic responses and failure mechanism of transmission towers; different possible failure paths exist for the uncertainty models, whereas only one exists for the deterministic model, and the ultimate bearing capacity of transmission towers is more sensitive to the variation in material parameters than that in geometrical parameters. This research is expected to provide an in-depth understanding of the influence of structural uncertainty on the seismic demand assessment of transmission towers.