• 제목/요약/키워드: Transmission Line Protection

검색결과 150건 처리시간 0.029초

혼합송전선로에서 고저항 지락사고시 케이블 과도현상 해석 및 전력케이블 시스 접지저항에 따른 CCPU 과도특성 모의 (Modeling and Transient Analysis of Cable in Combined Transmission Line with HIF and Analysis of Transient Characterstic in CCPU of Uderground Cable)

  • 정채균;이종범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 A
    • /
    • pp.446-448
    • /
    • 2000
  • This paper discribes the modeling and transient analysis of cable in combined transmission line under high impedance fault(HIF). And also, transient characterstic analyzed on cable covering protection unit(CCPU) is presented. Modeling of the combined transmission line is established in PSCAD/EMTDC V3. The required data to analyze the transient phenomena is given from the actual system. The results show the HIF modeling in cable, fault current according to the value of fault resistance. And also when the value and method of grounding resistance is changed in CCPU, simulation results are presented.

  • PDF

지중송전계통에서 배전선 불평형전류 유입에 따른 영향 검토 (Analysis of induced voltage of CCPU with unbalanced current from Distribution Line on Underground Transmission Cable System)

  • 강지원;장태인;홍동석;정채균;윤동수;윤종건;김형호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.459-461
    • /
    • 2005
  • This paper analyses the induced voltage characteristic of CCPU with unbalanced current from distribution line on underground transmission power cable systems. In switching surge strokes, in order to obtain the data of induced voltage/current on CCPU, the actual proof test carried out. This paper is expected to contribute the establishment of proper protection methods of CCPU against the unbalanced current from distribution line on underground transmission power cable systems.

  • PDF

키 교환 프로토콜을 이용한 디지털콘텐츠 보호 모듈 설계 (Design of Security Module using Key Exchange Protocol in Digital Contents)

  • 권도윤;이경원;김정호
    • 한국콘텐츠학회논문지
    • /
    • 제3권3호
    • /
    • pp.40-46
    • /
    • 2003
  • 본 논문은 안전하지 못한 DCPS(Digital Contents Protection Systems)와 HOST 사이의 통신채널을 통해 서로 일치하는 암호 키를 생성하기 위한 공개키 적용을 위해 1차적으로 이산대수와 난수를 이용한 Diffie-Hellman 알고리즘을 적용하고, 2차적으로 키 관리 표준인 ANSI X9.17, ISO 8732와 PEM(Privacy-Enhanced Mail) 등에서 채택하고 있는 2개의 서로 다른 암호키를 통해 Triple DES를 적용하여 전송 선로상의 디지털콘텐츠의 안전한 전송을 수행한다. 이에 따라 설계한 정보보호 모듈은 Key Exchange 모듈, Key Derivation 모듈, Copy Protection Processing 모듈로 구성되었으며 사용자 인증 기능과 디지털콘텐츠 암호화 기능을 통해 인가되지 않은 사용자에 의한 디지털콘텐츠의 불법 복제 및 배포를 방지하교 전송선로상의 디지털콘텐츠를 보호할 수 있도록 하였다.

  • PDF

배전선로가 초고속통신망에 미치는 유도장해 요소 분석 (A Review of Methods for Calculation of Induced Voltage to a Communication Line from Distribution Power Line)

  • 임용훈;현덕화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1956-1958
    • /
    • 2002
  • This paper reviews the calculation of induced voltage to a communication line from Power Transmission Line. Power lines, both overhead and underground, often run parallel to weak current lines, such as telecommunication, signal or data transmission systems or protection circuits. The coexistence of both systems in parallel over long lengths is accompanied by the possible induction of significant longitudinal voltage in the weak current line. In order to evaluate a precise induced voltage, this paper indicated problem about coefficient and numerical formula and present some induced voltage production technology standard application.

  • PDF

웨이브렛 변환을 이용한 혼합송전계통에서의 디지털 거리계전 알고리즘에 관한 연구 (A Study on the Digital Distance Relaying Algorithm Using Wavelet Transform in Combined Transmission Line with Underground Power Gables)

  • 정채균;홍동석;이종범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.383-386
    • /
    • 2001
  • Distance relay is tripped by the line impedance calculated at the relay point. Accordingly the accurate operation depends on the precise calculation of line impedance. Impedance can be accurately calculated in case of overhead line. However, in case of power cables or combined transmission lines, impedance can not be accurately calculated because cable systems have the sheath, grounding wires, and cable cover protection units (CCPUs). There are also several grounding systems in cable systems. Therefore, if there is a fault in cable system, these terms will severely be caused much error to calculation of impedance. Accordingly the proper compensation should be developed for the correct operation of the distance relay. This paper presents the distance calculating algorithm in combined transmission line with power cable using wavelet transform. In order to achieve such purpose, judgement method to discriminate the fault section in both sections was proposed using db1 coefficient summation. And also, error compensation factor was proposed for correct calculation of impedance in power cable.

  • PDF

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500kV Substations

  • Ju Hyung-Jun;Lee Heung-Ho
    • KIEE International Transactions on Power Engineering
    • /
    • 제5A권4호
    • /
    • pp.366-370
    • /
    • 2005
  • To meet increasing power demand, 500 kV power systems are under consideration in the regions of some Middle Asian countries. As the power system voltage becomes higher, the cost for the power system insulation increases significantly. 500 kV transmission systems will become the basis of a region's power system and they require much higher system reliability. Consequently, by the methods of limiting overvoltages effectively, a reasonable insulation design and coordination must be accomplished. In particular, the Substations must be constructed to be of outdoor type. In order to determine the various factors for the insulation design, the EMTP (Electro-magnetic transient program) is used for the magnification of transient phenomena of the 500 kV systems in the planned network. In this paper, we will explain the calculation results of lightning overvoltages by the EMTP for lightning protection design for the 500 kV substations. To obtain reliable results, the multi-story tower model and EMTP/TACS model are introduced for the simulation of dynamic arc characteristics.

TCSC가 적용된 실계통 시스템에서의 TRV와 MOV의 영향에 대한 분석 (Analysis on the Effects of TRV and MOV in Real System with TCSC)

  • 이석주
    • 한국산업정보학회논문지
    • /
    • 제24권2호
    • /
    • pp.41-46
    • /
    • 2019
  • 전력 시스템에서 직렬 보상기의 적용은 회로 차단기 과도 재기 전압 (Transient Recovery Voltage : TRV) 문제와 같은 다른 장치에 영향을 미친다. 본 논문에서는 TCSC (Thyristor-Controlled Series Capacitor)가 있는 경우와 없는 경우의 선로 차단기에 대한 TRV 효과를 시뮬레이션을 통해 분석하고, TCSC 설치로 인한 TRV 증가를 극복하는 효과적인 방법을 제안한다. 또한 금속 산화물 바리스터 (Metal Oxide Varistor : MOV)에 대한 제안된 보호의 영향에 대해서도 설명한다. 시뮬레이션 모델은 국내의 345 kV 송전선로를 사용하였다. 전력 시스템은 PSCAD (Power Systems Computer Aided Design) / EMTDC (Electro Magnetic Transient Direct Current)를 사용하여 모델링하였다. TRV는 송전선로 및 차단기 단자에서 단락 고장을 구현하여 분석하였고, MOV의 에너지는 보호 동작 알고리즘을 적용하여 해석하였다. 제안된 보호 방안을 적용하는 경우 TRV는 표준을 만족시키지만, 지연 시간이 증가함에 따라 MOV 에너지 용량의 증가하여야 한다. 이 결과를 적용하여 실제 전력 시스템에서 예상되는 전송 선로 고장 상태로 인한 TRV 문제를 해결할 수 있다.

통신시스템의 데이터 전송선로에 대한 연구 (A Study on the Data Transmission line of communication system)

  • 김석환;이규정;허창우
    • 한국정보통신학회논문지
    • /
    • 제9권6호
    • /
    • pp.1277-1281
    • /
    • 2005
  • 현재 통신시스템에서는 FPGA를 사용하여 여러 가지 로직을 구현하고 있다. 본 논문에서는 데이터 전달 특성을 분석하고 신호의 노이즈와 데이터 손실을 방지하기 위하여 10층의 PCB(Printed Circuit Board)를 만들었다. FPGA에 클럭과 64bit의 데이터를 동기 시켜 전송선로의 길이의 변화와 입력된 클럭의 주파수 변화에 따른 최대 안정된 데이터 전달속도와 전송선로의 길이를 알아보았다. 제작된 PCB보드에서 FPGA의 출력 핀에서 출력포트 사이의 전송선로 길이는 13cm이며 확장된 테스트용 전송선로 보드의 길이는 30cm, 60cm, 120cm이다. 그러므로 전송선로의 길이를 13cm, 43cm, 73cm, 133cm간격으로 측정하였으며, 데이터 전송특성에 대한 클럭 주파수는 100MHz, 50MHz, 100MHz, 125MHz, 150MHz로 나누어 측정하였다. 데이터 전달 특성에서 125Mbps까지는 불가능 하지만 전송선로의 길이가 30cm일 경우 최대 100Mbps까지 안정하게 데이터를 전달할 수 있었다.

송전선로 보호용 고장기록장치의 설계 및 구현 (Design and Implementation of Fault Recorder for Transmission Line Protection)

  • 최순철;박철원
    • 조명전기설비학회논문지
    • /
    • 제30권3호
    • /
    • pp.46-52
    • /
    • 2016
  • When a fault occurs on a transmission line, it is important to identify the fault location as speedily as possible for improvement of the power supply reliability. Generally, distance to fault location is estimated by off line from the recorded data. Conventional fault recorder uses the fault data at one end. This paper deals with the design of an advanced fault recorder for enhancement accuracy of the fault distance estimation and fast detection a fault occurrence position. The major emphasis of the paper will be on the description of the hardware and software of the fault recorder. The fault locator algorithm utilizes a GPS time-synchronized the fault data at both ends. The fault data is transmitted to the other side substation through communication. The advanced fault locator includes a Power module, MPU(Main Processing Unit) module, ADPU(Analog Digital Processing Unit) module, and SIU(Signal Interface Unit) modules. The MMI firmware and software of an advanced fault recording device was implemented.

UPFC를 포함한 송전성에서의 전류차동 보호 방식의 개선 (Improvement of the Differential Current Relaying Method for Protecting the Transmission Line Equipped with UPFC)

  • 임정욱;권영진
    • 조명전기설비학회논문지
    • /
    • 제19권8호
    • /
    • pp.40-47
    • /
    • 2005
  • 본 논문에서는 대표적인 유연송전기기인 UPFC(Unified Power flow Controller)를 대상으로 UPFC 운전이 송전계통에 미치는 영향을 분석하여 송전선 보호를 위한 전류차동방식을 개선하였다. UPFC가 포함된 송전계통을 대상으로 UPFC의 여러 운전 모드에 대한 동적 해석을 통하여 UPFC 동적 특성이 송전선 보호를 위한 전류차동 계전방식에 미치는 영향을 분석하였다. 이를 바탕으로 UPFC가 운전하고 있을 때의 고장을 효과적으로 판단할 수 있도록 개선된 전류차동 보호방법을 제안하였고, 제안된 방법의 타당성을 시뮬레이션으로 입증하였다.