• 제목/요약/키워드: Transformer bushing

검색결과 22건 처리시간 0.023초

적외선 열화상 장비를 이용한 실시간 변압기 진단 및 평가 (Diagnosis and Evaluation of the Real Time Transformer by the Infrared Thermal Image Equipment)

  • 이철구;백원갑;김승대
    • 한국생산제조학회지
    • /
    • 제21권4호
    • /
    • pp.666-671
    • /
    • 2012
  • It was diagnosed customer transformers and other equipment by using non-contact infrared equipment. Examiners can identify not only abnormalities in real time in the field of the transformer immediately, as well as they were able to safely perform the scan. Thanks to successful transformer diagnosis, we can easily diagnose abnormalities of transformer itself which can be caused by deterioration of the oil used as overlaod or refrigerant and we can also diagnose abnomalities from low voltage bushing which can be result by external environmental factors and physical factors and abnomalities from its connections at the same time we found it is very useful at proactive diagnostics.

온라인 변압기 부분방전 측정기법 적용 (An Application of the On Line Partial Discharge Measurement Method in Transformer)

  • 권동진
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제50권8호
    • /
    • pp.394-400
    • /
    • 2001
  • This paper describes an application of the on line partial discharge measurement method in operating transformer. In the operating transformer, the partial discharge signal may be superimposed by radio intereference voltage(RIV) and pulse shaped noise signals generated by external corona. The partial discharge quantity showed about 3,800pC due to very high sinusoidal interferences at the measuring impedance terminal of the transformer bushing tap. In order to reject these noises, this paper applied RIV filter, band-pass filters and noise gating method. The resulting measuring sensitivity was improved from 3,800pC to 160pC.

  • PDF

온라인 변압기 부분방전 측정기법 (On Line Partial Discharge Measurement Method for Transformer)

  • 권동진;최인혁;송일근;박재준
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.38-42
    • /
    • 2001
  • This paper describes an application of the on line partial discharge measurement method in operating transformer. In the operating transformer, the partial discharge signal may be superimposed by radio intereference voltage(RIV) and pulse shaped noise signals generated by external corona. The partial discharge quantity showed about 3,800pC due to very high sinusoidal interferences at the measuring impedance terminal of the transformer bushing tap. In order to reject these noises, this paper applied RIV filter, band-pass filters and noise gating method. The resulting measuring sensitivity was improved from 3,800pC to 160pC.

  • PDF

변압기 부분방전 상시 감시기법에 관한 연구 (A Study on the on Line Monitoring Techniques of the Partial Discharge for Transformer)

  • 권동진;박재준
    • 한국전기전자재료학회논문지
    • /
    • 제14권12호
    • /
    • pp.1032-1040
    • /
    • 2001
  • In order to apply the partial discharge measuring technique utilizing electrical pulse to the transformer at sites, this paper describes the measuring technique obtaining only the signals due to internal partial discharge in the transformer, but the noises due to external corona which has been a major problem so far. At first, partial discharge and corona noise were simultaneously generated in the model transformer by using needle-plane electrodes and rod-sphere electrodes out of it in a high voltage laboratory, respectively. It was verified that only the partial discharge signals in the transformer could be measured by removing the noise signals from the superposed signals of partial discharges and noises on the grounding wire of the model transformer. By application to a 345kV transformer in service, it was also confirmed that the partial discharge could be on-line monitored by removing the noise signals measured by the inductance sensor on the grounding wire of a 154kV lightning arrester from the superposed signals of internal partial discharge and external corona noise measured by bushing tap coupler of the transformer.

  • PDF

주상변압기 고압권선의 서지응답 특성 (Electrical Characteristics of Insulation Paper for Distribution Transformers)

  • 송일근;정종욱;이병성;이재봉;김상준;오재형
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 일렉트렛트 및 응용기술
    • /
    • pp.156-159
    • /
    • 2002
  • This paper presents an experimental study of the surge response characteristics for the primary winding of a pole transformer and ultimately aims at devising countermeasures against the surge in operating transformer. After applying the impulse voltage to the primary of the 30 kVA pole transformer with single bushing, the voltage waveforms were measured at each tap lead and compared with one another. As a result, the voltage peak of the surge propagating in the primary was decreased in magnitude at a constant rate and somewhat delayed compared to the peak of the applied surge as the tap leads were getting closer to the grounding terminal. The voltage measured at the secondary was not delayed in time, different from that at the primary, and it was about 1/6 according to the turn ratio.

  • PDF

22.9 kV용 변압기 부싱 절연 커버의 실태 조사 및 열화 특성 (The Deterioration Properties and Actual Conditions of Insulation Cover used at 22.9 kV Transformer Bushing)

  • 최충석;김향곤;한운기;이기연
    • 한국화재소방학회논문지
    • /
    • 제20권3호
    • /
    • pp.35-41
    • /
    • 2006
  • 본 논문에서는 22.9 kV용 변압기 부싱 절연 커버의 실태조사를 실시하였다. 절연 커버에 열적 스트레스를 인가하여 열화 패턴, 열 중량 변화, 적외선 특성 등을 해석하여 전기사고 원인 분석을 위한 근거를 제시하고자 한다. 노출된 변압기 단자를 보호하기 위해 설치한 절연 커버의 크기 및 길이가 부적절한 것이 확인되었다. 절연 커버에 $150^{\circ}C$의 열적 스트레스를 인가한 경우 플라스틱 절연 커버(A, B, D, E)는 심한 변형이 일어났으나, 고무 절연 커버 C는 정상이었다. 열 중량 분석 결과 절연 커버 A는 $307.8{\sim}405.9^{\circ}C$에서 33.3%의 감소가 있었으며, 절연 커버 C는 $258.8{\sim}332.9^{\circ}C$에서 53.7%의 감소가 발생하였다. FT-IR 분석에서 플라스틱 절연 커버는 $CH_2,\;CH_3$, C=O, C=C 결합 구조를 갖는 것으로 나타났으며, 고무 절연 커버는 OH, $CH_2,\;CH_3$, C=O, C=N, C=C 등의 결합인 것을 알 수 있었다.

변압기의 내진성능 향상을 위한 마찰진자 면진장치의 시험 연구 (Experimental Study of Friction Pendulum System to Improve the Seismic Capacity of Transformer)

  • 장정범;김정기;황경민;함경원;박진완;이찬욱
    • 한국지진공학회논문집
    • /
    • 제12권2호
    • /
    • pp.1-8
    • /
    • 2008
  • 본 연구에서는 전력설비 중 그 중요도가 가장 큰 변압기를 대상으로, 지진 발생 시 변압기의 파손을 방지하기 위하여 마찰진자 면진장치를 개발하고, 진동대시험을 통하여 그에 대한 내진성능을 입증하였다. 본 연구에서 개발한 마찰진자 면진장치에 대해 압축재하시험 및 마찰시험을 수행한 결과, 변압기의 면진장치로서 적용 가능한 것으로 나타났으며, 특히 변압기 축소모형을 대상으로 진동시험대에 의한 내진성능시험을 수행한 결과, 기존의 일반 고정기초형식보다 변압기 기초부의 최대 응답가속도는 약30%, 부싱 상단의 최대 응답가속도는 약 59% 감소하였다. 또한, 마찰진자 면진장치 설치 후, 변압기의 고유진동수가 약 82% 감소하며 장주기로 이동함을 확인할 수 있었다. 이와 같이 변압기에 마찰진자 면진장치를 적용하는 경우, 지진으로 인한 변압기의 파손을 효과적으로 방지할 수 있을 것으로 판단된다.

부하가 불규칙하게 분포된 배전선로의 전압추정 방법 (Voltage Estimation Method for Distribution Line with Irregularly Dispersed Load)

  • 박상현;임성일
    • 전기학회논문지
    • /
    • 제67권4호
    • /
    • pp.491-497
    • /
    • 2018
  • Most of the applications for distribution system operation highly rely on the voltage and current managements from the field devices. Voltage from the remote controlled switch contains unacceptably large measurement error due to the nonlinear characteristics of the bushing potential transformer. This paper proposes a new voltage magnitude estimation method by calculating voltage drop using current measurement, line impedance and loads deployment data. Contract demand power and pole transformer capacity managed by NDIS are used as a key element to improve accuracy of the proposed method. Various case studies using Matlab simulation have been performed to verify feasibility of the propose voltage estimation method.

고장수목을 이용한 변전소의 지진취약도 분석 (Seismic Fragility Analysis of Substation Systems by Using the Fault Tree Method)

  • 김민규;전영선;최인길;오금호
    • 한국지진공학회논문집
    • /
    • 제13권2호
    • /
    • pp.47-58
    • /
    • 2009
  • 본 연구에서는 변전소 시스템의 지진취약도 분석을 수행하여 변전소에 대한 지진취약도 함수를 제시하였다. 변전소는 여러 개의 설비와 구조물이 복합적으로 구성되어 있는 시스템이므로 각 설비에 대한 지진취약도 분석을 수행하여 이를 바탕으로 고장수목을 작성하여 변전소 전체의 파괴확률을 산정함으로써 변전소에 대한 지진취약도 평가를 수행하였다. 이를 위하여 국내 변전소의 현황을 파악하여 지진피해추정을 위한 변전소의 분류형식을 결정하였으며, 결정된 대표변전소 형식에 대한 평가대상 기기를 선정하였다. 대표 변전소 형식으로는 765kV, 345kV, 154kV 변전소의 GIS형 변전소로 결정하였다. 각 변전소의 취약도 검토대상 기기로는 변압기와 절연 애자를 선택하였다. 각 변전소의 변압기와 절연애자의 파괴모드와 파괴기준을 설정하여 지진취약도 곡선을 도출하였다. 최종적으로 변전소에 대한 고장수목을 이용하여 각 기기의 지진취약도 곡선으로부터 변전소 전체의 파괴확률을 산정하여 정의된 손상상태별 변전소의 지진취약도 함수를 산정하였다.

저압측 서지에 의한 주상변압기 고압권선 동특성 해석 (Dynamic Behavior Analysis of Pole Transformer Primary by Secondary Surge)

  • 정종욱;송일근;김상준;장덕근;곽희로
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1745-1747
    • /
    • 2002
  • This paper describes the effect of secondary surges entering low voltage side on the primary winding of pole transformers. After having connected the secondary winding by 4 different methods, surge voltages were applied to the low voltage side, and voltage waveforms were measured at a surge applied point and a high voltage bushing terminal. The measured voltages were compared by the waveform, magnitude and damping characteristics with each connection. As a result, the voltage waveforms induced by the secondary surges were different one another with each connection, especially, the conventional connecting method for 2 voltage sources was far different from the present method supplying only 1 voltage source in shape of the voltage waveform.

  • PDF