A study on Cause of Errors of Dissolved Gases Analysis in Transformer (변압기 유중 가스 진단 오차 원인에 대한 연구)

  • Cho, Sung-Min;Lee, Yang-Jin;Kim, Young-Sung;Kim, Jae-Chul;Kweon, Dong-Jin
    • Proceedings of the KIEE Conference
    • /
    • 2006.11a
    • /
    • pp.141-143
    • /
    • 2006
  • Dissolved gas analysis (DGA) is widely used to detect incipient faults in oil-filled electrical equipment. KEPCO make a rule of DGA in 1985. They have been diagnosing power transformer using their DGA criteria. In this paper, we analysis the result of DGA data about transformer in the substation. We try to find out what is cause of an error in DGA diagnosis considering accuracy in extracting gases from mineral oil in transformer. The carbon-monoxide was primary reason of warning in DGA data. We specially consider that aging is a cause of generating of carbon-monoxide in power transformer.

  • PDF

Research of Flow Electrification Phenomena of the used Environment-Friendly Vegetable Insulating Oils (친환경 식물성절연유의 유동대전현상 연구)

  • Choi, Sun-Ho;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.4
    • /
    • pp.580-584
    • /
    • 2012
  • The insulating oils perform a cooling and insulation action in electric power transformer. The mineral oil has immanent fire dangerousness and environmental contamination problem. Vegetable insulating oil has higher ignition point, flash point and more excellent biodegradability than conventional mineral oil. In a real oil-filled transformers, some of the power is dissipated in the form of heat. And transformer require the heat to be removed from the winding and insulator by forced convection of the insulating oil. The flow electrification occurs when insulating oil was forced to be circulated. In this paper, influence of temperature, velocity of flow, and insulating pipe and diameter on streaming electrification of vegetable insulating oil was investigated using forced circulation apparatus. Temperature effects were most significant, and it showed a peak in the temperature $30^{\circ}C$ to $35^{\circ}C$ at insulating and copper pipe. The change of flow electrification according to area variety could be checked by change of diameter.

A Study on the Streaming Electrification Phenomena of the Transformer Oil (변압기유의 유동대전 현상에 관한 연구)

  • 강성화;임기조;주상범;김명녕;강도열;김봉협
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.39 no.6
    • /
    • pp.568-576
    • /
    • 1990
  • Recently, streaming electrification in forced oil cooled power transformer has been taken up as a serious problem. In this paper, the charging tendency of various insulation oils, such as mineral oil, polybutene and silicone oil has been measured by means of an injection type charging tendency measuring apparatus under various condition. The experimental data of the dependence of the leakage current on flow velocity and temperature of oil can be explained by considering the flow state such as laminar and turbulent flow. The effect of additives on the charging tendency of mineral oil has been investigated. BTA is regarded as the most effective retardant to electrification of oil among the additives chose for this investigation.

  • PDF

Dielectric Characteristic Analysis of Thermally Aged Insulating Oil for Transformers (열적열화된 변압기용 절연유의 유전특성 분석)

  • Jung, J.W.;Lee, B.S.;Song, I.K.;Park, J.S.;Kwak, H.R.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1594-1596
    • /
    • 2001
  • The purpose of this paper is to provide the fundamental data which can be used for the design of pole transformers. For the purpose, electrical characteristics of aged mineral oil and silicone oil were analyzed by comparing with the results of virgin ones. For the experiment, an oil bath which can keep constant temperature was constructed to thermally deteriorate the specimens. And transformer materials were put together in the bath according to the their ratio in weight in the pole transformer. And the parameters such as relative permittivety, tan$\delta$ and specific resistance were measured. As a results, the permittivity of silicone oil was higher than that of mineral oil, and its decreasing rate with temperature was also higher. In addition, it was found that tan$\delta$ and specific resistance of virgin and aged oil began to differ at similar temperature.

  • PDF

Study on the Damage Pattern Analysis of a 3 Phase 22.9/3.3kV Oil Immersed Transformer and Judgment of the Cause of Its Ignition (3상 22.9/3.3kV 유입변압기의 소손패턴 해석 및 발화원인 판정에 관한 연구)

  • Choi, Chung-Seog
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.6
    • /
    • pp.1274-1279
    • /
    • 2011
  • The purpose of this paper is to present the manufacturing defect and damage pattern of a 3 phase 22.9/3.3kV oil immersed transformer, as well as to present an objective basis for the prevention of a similar accident and to secure data for the settlement of PL related disputes. It was found that in order to prevent the occurrence of accidents to transformers, insulating oil analysis, thermal image measurement, and corona discharge diagnosis, etc., were performed by establishing relevant regulation. The result of analysis performed on the external appearance of a transformer to which an accident occurred, the internal insulation resistance and protection system, etc., showed that most of the analysis items were judged to be acceptable. However, it was found that the insulation characteristics between the primary winding and the enclosure, those between the ground and the secondary winding, and those between the primary and secondary windings were inappropriate due to an insulating oil leak caused by damage to the pressure relief valve. From the analysis of the acidity values measured over the past 5 years, it is thought that an increase in carbon dioxide (CO2) caused an increase in the temperature inside the transformer and the increase in the ethylene gas increased the possibility of ignition. Even though 17 years have passed since the transformer was installed, it was found that the system's design, manufacture, maintenance and management have been performed well and the insulating paper was in good condition, and that there was no trace of public access or vandalism. However, in the case of transformers to which accidents have occurred, a melted area between the upper and the intermediate bobbins of the W-phase secondary winding as well as between its intermediate and lower bobbins. It can be seen that a V-pattern was formed at the carbonized area of the transformer and that the depth of the carbonization is deeper at the upper side than the lower side. In addition, it was found that physical bending and deformation occurred inside the secondary winding due to non-uniform pressure while performing transformer winding work. Therefore, since it is obvious that the accident occurred due to a manufacturing defect (winding work defect), it is thought that the manufacturer of the transformer is responsible for the accident and that it is lawful for the manufacture to investigate and prove the concrete cause of the accident according to the Product Liability Law (PLL).

A Study on the Cooling Characteristic of a 154kV Less-Flammable Power Transformer (154kV 방재형 난연 변압기 냉각특성에 관한 연구)

  • Park, J.H.;Oh, W.K.;Ha, Y.S.
    • Proceedings of the KIEE Conference
    • /
    • 2001.10a
    • /
    • pp.61-64
    • /
    • 2001
  • Demand for development of 154kV Less-Flammable Power transformer is now increasing greatly instead of a oil-immersed transformer for preventing disasters and Less-flammability of substations. The most important point in developing Less-flammable transformer is cooling system. This paper describes the study on cooling characteristic of Less-flammable transformer.

  • PDF

The Effect of Antioxidant in the Electrical Properties of Homemade Insulating Oil (국산절연유의 전기적 특성에 미치는 산화방지제의 효과)

  • 성영권;김은배;김호윤;이덕출
    • 전기의세계
    • /
    • v.22 no.4
    • /
    • pp.30-34
    • /
    • 1973
  • The main purporse of this paper is to study on the influence of temperature effect on electrical-properties, i.e., dielectric breakdown voltage, dielectric constant and resitivity of homemade insulating oil containing antioxidant. Transformer oil manufactured in Korea is taken for a sample, and this sample is classified into seven samples in which antioxidant is contained and not contained, and antioxidant is divided into three kinds of amount: 0.3%, 0.5%, 0.8%. Changing the tempe5rature of the samples by oil bath, the electric properties measured from the samples are as follows: (1) the variation of either the dielectric breakdown voltage or the resistivity are considerably large, but the dielectric constants are almost unchanging. (2) In view of electrical characteristic, the deterioration rate of the samples containing antioxidant is somewhat lower than that of other samples. (3) Nearly the same value is shown in the dielectric-breakdown voltage of the samples, in which contained the different amount of antioxidant: 0.3%, 0.5%, 0.8%, but the decrease rate of resitivity is lowest, 0.3%, of all. As the result of the experiment, This study can suggest that 0.3% be the optimum amount of antioxidant which will be added transformer oil manufactured in Korea and is useful for the understanding about the electrical properties of transformer oil containing antioxidant.

  • PDF

Safety Analysis and Safety Measures of 22900/1200V Oil Immersed Transformer at Power Supply System (전철 급전시스템의 22900/1200V 유입변압기 안전성 분석)

  • Lee, Jong-Su;Lee, Jongwoo
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.9
    • /
    • pp.1335-1342
    • /
    • 2013
  • Subway is electrified railway system nowadays, in which liquid dielectric transformers have been widely used, though mold type transformers are replacing it. The transformers supplies large electric power and have innate hazards causing accidents under operation. A number of researcher have carried out on failures of it and have oriented to identify transformer's failure causes and how to maintain it healthy state. The transformer failures can cause serious accidents which can provoke economic loss and leads persons to kill. In this paper, we carried out a safety activity to reveal hazards and to estimate risk of subway liquid dielectric transformers using FMEA, HAZOP and What-if methods. In case of installing safety devices in oil immersed transformer, we tried to evaluate an effect on a subsystem's failure rate. We proposed how to design subsystem failure rate and safety device failure rates.

Analysis on the Electric Characteristics of Natural Ester after Accelerated Thermal Aging (식물성 절연유의 열 열화에 따른 전기적 특성 연구)

  • Shim, Meoung-Seop;An, Jung-Sik;Choi, Sun-Ho;Jung, Joong-Il;Kim, Nam-Ryul;Huh, Chang-Su
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.81-81
    • /
    • 2010
  • This paper presents results of experimental investigations on natural ester regarding the breakdown strength. Aging of insulating material in a pole transformer has been studied by performing accelerated thermal aging test. Sealed aging test vessels containing copper, laminated core, Krapt paper and insulating oil(Natural oil and Mineral oil) were aged at $140^{\circ}C$ for 30days. Compared to the conventional transformer oil, electric property of the natural ester fluid is excellent.

  • PDF

Dissolved Gas Analysis of Environment-Friendly Vegetable Insulating Oils (친환경 식물성 절연유의 유중가스 분석)

  • Choi, Sun-Ho;Kim, Kwan-Sik;Huh, Chang-Su
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.28 no.4
    • /
    • pp.238-243
    • /
    • 2015
  • The vegetable insulating oils are substitute for the mineral oil in power transformer. Vegetable insulating oils has higher flash/fire point and biodegradability than conventional mineral oils. In this paper, we investigated the dissolved gas analysis of vegetable oils. In the experiment, I had to accelerated aging under the same conditions mineral oil and vegetable oils. Accelerated aging proceeded to about 100% of the life of oil-filled transformer. In addition, we performed gas analysis of insulating oil of accelerated aging progress. The experiment results of the five gases was measured with the exception of Hydrogen and Acetylene. The mineral oil and vegetable oils gas is generated in a similar tendency depending on the accelerated aging. As a result, vegetable oils, can be dissolved gas analysis by method such as mineral oil.