• 제목/요약/키워드: Tower effectiveness

검색결과 74건 처리시간 0.031초

A Model-Based Fault Detection and Diagnosis Methodology for Cooling Tower

  • Ahn, Byung-Cheon
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제9권3호
    • /
    • pp.63-71
    • /
    • 2001
  • This paper presents a model-based method for detecting and diagnosing some faults in the cooling tower of healing, ventilating, and air-conditioning systems. A simple model for the cooling tower is employed. Faults in cooling tower operation are detected through the deviations in the values of system characteristic parameters such as the heat transfer coefficient-area product, the tower approach, the tower effectiveness, and fan power. Three distinct faults are considered: cooling tower inlet water temperature sensor fault, cooling tower pump fault, and cooling tower fan fault. As a result, most values of the system characteristics parameter variations due to a fault are much higher or lower than the values without faults. This allows the faults in a cooling tower to be detected easily using above methods. The diagnostic rules for the faults were also developed through investigating the changes in the different parameter due to each faults.

  • PDF

백연 방지를 위한 NWD냉각탑의 성능해석에 관한 수치해석적 연구 (A Numerical Study on the Performance Analysis of the Plume Abatement NWD Cooling Tower)

  • 최창혁;최영기;소헌영
    • 설비공학논문집
    • /
    • 제13권11호
    • /
    • pp.1049-1058
    • /
    • 2001
  • The performance and design analysis for a NWD cooling tower using a combined wet and dry type fill are numerically investigated and compared with the experimental results. The Stoecker's method is applied to the wet section and LMTD or NTU-Effectiveness method to the wet and dry sections. The efficiency ratio of the NWD cooling tower to a wet type crossflow cooling tower is 59.34%. The predicted result shows a good agreement with the experimental data within 1.4% error. Plume abatement is far better with a NWD cooling tower than a counterflow cooling tower. It costs less than a conventional wet/dry tower because the finned exchanger is eliminated. This method also leaves out complexity in structure and Intricacy in operation.

  • PDF

건식 열교환기를 이용한 백연방지 냉각탑 성능의 수치해석적 연구 (A Numerical Study on the Performance Analysis of Plume Abatement Cooling Tower with Dry Type Heat Exchanger)

  • 김병조;최영기
    • 설비공학논문집
    • /
    • 제15권12호
    • /
    • pp.1018-1027
    • /
    • 2003
  • This study treats the analysis of the performance and the design of plume abatement wet/dry cooling tower with dry type heat exchanger using a numerical method. A two-dimensional analysis is performed using the finite volume method for mechanical draft counterflow and crossflow tower. For a coupling problem between water and air system, a turbulent two phase flow is considered. Effectiveness-NTU method is used for modeling of the dry type heat exchanger. The parameter change simulations of the outer wall shape, the relative flowrate of air, and attachment of an air mixer are performed to examine the effect on plume abatement. It is found that if the relative air flowrate ratio and the adequate air mixer type are chosen well in addition to the ratio of water to air flowrate, the loss of the cooling capacity and the additional cost are reduced and the plume is abated.

Numerical Study on the Performance Analysis of Plume Abatement Cooling Tower with Dry Type Heat Exchanger

  • Kim, Byung-Jo;Choi, Young-Ki
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제13권2호
    • /
    • pp.61-70
    • /
    • 2005
  • This study treats the numerical analysis of performance and design for plume abatement wet/dry cooling tower with a dry type heat exchanger. A two-dimensional analysis is performed using the finite volume method for mechanical draft counterflow and crossflow tower. For a coupling problem between water and air system, a turbulent two phase flow is considered. The Effectiveness-NTU method is used for modeling of the dry type heat exchanger. The parametric simulations such as the relative flowrate of air and attachment length of an air mixer are performed to examine the effect on plume abatement. It is found that if the relative air flowrate ratio and the adequate air mixer type are chosen well in addition to the ratio of water to air flowrate, the loss of cooling capacity and the additional cost are reduced and the plume is abated.

풍력발전용 하이브리드 타워 하중영향 및 경제성 분석 (Analysis of Load on the Hybrid Tower and Cost Effectiveness of the Wind Turbine)

  • 이승민;권대용;김용천;;박현철;정진화
    • 신재생에너지
    • /
    • 제6권4호
    • /
    • pp.50-60
    • /
    • 2010
  • With the development of wind industry, rated power of the wind turbine also increases gradually. Accordingly, size of the wind turbine tower is becoming larger. Tower base diameter of the 2MW wind turbine is about 4m. Larger tower is expected for 4MW or 5MW turbines. Due to limitation of transportation, new type of tower with smooth transportation and effective cost is needed. In this work, a hybrid tower consisting of steel and concrete is designed and analyzed. The optimum ratio of steel and concrete of the hybrid tower is calculated as well as the thickness of the concrete part. Different FE analysis including modal analysis, buckling analysis and static analysis are performed to check the design of hybrid tower comparing with the steel tower. Redesign is also expected after various analyses.

Structural Work Duration Estimation and Analysis of Tower-Type Residential Construction Project

  • Yun, Seok Heon;Kim, Sang Chul
    • Architectural research
    • /
    • 제14권3호
    • /
    • pp.109-116
    • /
    • 2012
  • In order to shorten construction duration in high-rise project, construction company tried to make various system method toward simplifying construction method and shortening construction duration. Though high-rise tower-type residential project are growing, there are few case study. Then, the data for preliminary schedule planning in high-rise tower-type residential project are rare. This purpose of research shows construction method in structural work in high-rise tower-type residential project, suggests schedule planning in structural work through case studies. The structural work in high-rise tower-type residential project was divided 1) completion of form in lower part and 2) the typical floor under penthouse. The statistical analysis were done in two parts, the data from analysis were used in simulation. Finally, researcher confirmed the difference between real construction duration and the figure from simulation. The results shows that the more construction duration is long, the less ACS's cost is low. It means the effectiveness is increasing in ACS, if the floor number is high.

점탄성감쇠기를 이용한 송전철탑 풍하중의 저감 (Wind Load Mitigation for Transmission Tower using Viscoelastic Damper)

  • 민경원;박지훈;문병욱
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2005년도 추계학술대회논문집
    • /
    • pp.955-958
    • /
    • 2005
  • In this study, the wind load characteristics for a transmission tower is investigated considering the effect of the transmission lines through stochastic analysis. The assemblage of the transmission line and insulator are modeled as a double pendulum system connected to the SDOF model of the tower It is observed that the background component of the overturing moment induced by the wind response of the transmission line has considerable portion in the total overturning moment. Based on this result, a rotational viscoelastic damper (VED) is proposed for the mitigation of the transmission line reactions, which act as wind load transferred to the tower. To verify the effectiveness of the proposed strategy, time history analysis is conducted for different wind velocities and VED damping constants. From the analysis, the proposed VED is proved to be effective for mitigation of the background component rather than the resonance component of the transmission line reaction.

  • PDF

Hybrid nonlinear control of a tall tower with a pendulum absorber

  • Orlando, Diego;Goncalves, Paulo B.
    • Structural Engineering and Mechanics
    • /
    • 제46권2호
    • /
    • pp.153-177
    • /
    • 2013
  • Pendulums can be used as passive vibration control devices in several structures and machines. In the present work, the nonlinear behavior of a pendulum-tower system is studied. The tower is modeled as a bar with variable cross-section with concentrated masses. First, the vibration modes and frequencies of the tower are obtained analytically. The primary structure and absorber together constitute a coupled system which is discretized as a two degrees of freedom nonlinear system, using the normalized eigenfunctions and the Rayleigh-Ritz method. The analysis shows the influence of the geometric nonlinearity of the pendulum absorber on the response of the tower. A parametric analysis also shows that, with an appropriate choice of the absorber parameters, a pendulum can decrease the vibration amplitudes of the tower in the main resonance region. The results also show that the pendulum nonlinearity cannot be neglected in this type of problem, leading to multiplicity of solutions, dynamic jumps and instability. In order to improve the effectiveness of the control during the transient response, a hybrid control system is suggested. The added control force is implemented as a non-linear variable stiffness device based on position and velocity feedback. The obtained results show that this strategy of nonlinear control is attractive, has a good potential and can be used to minimize the response of slender structures under various types of excitation.

최적 제어법에 의한 타워크레인의 자동화에 관한 연구 (Automation of Tower Cranes based on Optimal Control Method)

  • Lee, Jin-Woo;Kim, Sang-Bong
    • 한국안전학회지
    • /
    • 제8권4호
    • /
    • pp.213-222
    • /
    • 1993
  • 본 논문은 하역작업이나 제품의 권상, 권하시 타워크레인의 로바스트 콘트롤을 고려한 타워크레인의 자동화에 관한 것이다. 본 논문을 위한 타워크레인의 모델방정식은 라그랑즈 방정식을 사용하였으며, 동방정식은 평행점 근방에서 선형화 하였다. 본 논문의 제어법으로서는 최적 레규레타법을 적용하였으며, 그 효용성은 설계된 최적 제어법을 위하여 16비트 마이크로컴퓨터를 이용하여 카고로우프의 진동제어와 그레인의 붐 및 트로리의 위치제어를 위한 실험결과로써 입증되었다.

  • PDF

Seismic response control of transmission tower-line system using SMA-based TMD

  • Tian, Li;Zhou, Mengyao;Qiu, Canxing;Pan, Haiyang;Rong, Kunjie
    • Structural Engineering and Mechanics
    • /
    • 제74권1호
    • /
    • pp.129-143
    • /
    • 2020
  • This study proposes a new shape memory alloy-tuned mass damper (SMA-TMD) and investigates the effectiveness of this damper in reducing and controlling the vibrations of a transmission tower-line system under various seismic excitations. Based on a practical transmission line system and considering the geometric nonlinearity of this system, the finite element (FE) software ANSYS is used to create an FE model of the transmission tower-line system and simulate the proposed SMA-TMD. Additionally, the parameters of the SMA springs are optimized. The effectiveness of a conventional TMD and the proposed SMA-TMD in reducing and controlling the vibrations of the transmission tower-line system under seismic excitations is investigated. Moreover, the effects of the ground motion intensity and frequency ratio on the reduction ratio (η) of the SMA-TMD are studied. The vibration reduction effect of the SMA-TMD under various seismic excitations is superior to that of the conventional TMD. Changes in the ground motion intensity and frequency ratio have a significant impact on the η of the SMA-TMD. As the ground motion intensity and frequency ratio increase, the η values of the SMA-TMD first increase and then decrease. Studying the vibration reduction effects of the SMA-TMD can provide a reference for the practical engineering application of this damper.