• 제목/요약/키워드: Thermostatic valves

검색결과 11건 처리시간 0.027초

비례제어식 자동온도조절기의 온도감지방식별 난방제어 특성 비교 (A Comparison of Heating Control Characteristics by Temperature Sensing Methods for Thermostatic Valves with the Proportional Control Mode)

  • 김용기;이태원;강성주
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.161-166
    • /
    • 2007
  • Various thermostatic valves have been used widely in Korea for conservation of heating energy and enhancement of thermal comfort in residential buildings. But heating control performances of thermostatic valves extensively vary with the design and operational conditions of the heating system, climate condition and others. An experimental method was carried out in this study to analyze heating control characteristics by temperature sensing methods of thermostatic valves for various parameters, such as supply temperatures and flow rate of hot water, the position of room thermostats and outdoor air temperatures. As a result, the heat flow rate per day of S-Valve($34^{\circ}C$-Type) of water temperature sensing method was liked that of C-Valve of indoor air temperature sensing method with stage 3.3 of room thermostat in case supply temperature of hot water was $45^{\circ}C$, flow rate was 1.3 L/min and outdoor air temperature was $7.8^{\circ}C$.

  • PDF

공조.냉동장치의 제어시스템 개발을 위한 팽창밸브 특성 (Expansion Valves Characteristics for Development of Control System on Air Conditioning and Refrigeration Systems)

  • 김재돌;장재은;윤정인
    • 동력기계공학회지
    • /
    • 제2권3호
    • /
    • pp.34-40
    • /
    • 1998
  • Performance characteristics of a refrigeration systems with various expansion valves and superheat changes were investigated experimentally. Experimental data have been taken utilizing three different devices; a thermostatic expansion valve, a linear type electronic expansion valve and a solenoid type electronic expansion valve. The data taken from tile three types of expansion valves were discussed with the temperature distribution of each zone in the evaporator and the superheat changes of the evaporator outlet In each zone temperature distribution fluctuated larger with the thermostatic expansion valve than with the electronic expansion valves. The optimum superheat ranged from $5^{\circ}C\;to\;15^{\circ}C$, and the superheat with the thermostatic expansion valve showed hunting phenomenon, which affected the evaporating and condensing temperature.

  • PDF

바닥난방용 자동온도조절기의 난방방식에 따른 에너지성능 해석용 프로그램에 관한 연구 (Energy Performance Analysis Program with Heating methods of Automatic Thermostatic Valves in Floor Radiant Heating System)

  • 안병천;송재엽;이태원;김용기
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 동계학술발표대회 논문집
    • /
    • pp.381-386
    • /
    • 2008
  • In this study, the energy characteristic of automatic thermostatic valves according to each heating method in floor radiant heating system were researched by computer simulation. For the analysis of unsteady heat transfer phenomena in household, the method of using electrical equivalent R-C circuit is applied, and radiation heat transfer between panel, ceiling and walls in household is calculated by enclosure analysis method. The parametric study on heating method, valve's control method, outdoor air condition, supply heating water temperature, supply flow rate are performed to compare energy characteristic, respectively.

  • PDF

공동주택 난방용 자동온도조절기의 성능해석 연구 (A Study on the Performance of Automatic Thermostatic Valves for Hot Water Heating System in Residential Buildings)

  • 안병천;이태원;김용기;송재엽
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.457-462
    • /
    • 2005
  • In this study, the performance of automatic thermostatic valves according to each heating method of a large scale residential building were researched by simulation. The flow characteristics of the entire pipe networks of the hot water radiant heating system is analized by using linear analysis method. For the analysis of unsteady heat transfer phenomena in each household, the method of using electric equivalent R-C circuit is applied.

  • PDF

바닥난방 시스템용 비례식 자동온도조절밸브의 성능해석에 관한 연구 (A Study on the Performance Analysis of Proportional Automatic Thermostatic Valves in Floor Radiant Heating System)

  • 송재엽;안병천;김용기;이태원
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.52-57
    • /
    • 2007
  • The control characteristics for radiant panel heating system with automatic thermostatic valves were researched by computer simulation and experiment. The unsteady energy analysis using equivalent R-C circuit method and radiation heat transfer analysis of enclosure analysis method with simple structured rooms was performed. The results of flow rate changes of the simulation study are good fit with the ones of experimental one.

  • PDF

바닥난방 시스템의 열환경 개선을 위한 제어방안 연구 (A Study on Thermal Heating Control Performance of Automatic Thermostatic Valves in Floor Radiant Heating System)

  • 송재엽;안병천;김경철;장사윤
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.973-978
    • /
    • 2009
  • In this study, the thermal environment characteristics of On-Off control and thermal difference proportional control method in floor radiant heating system were researched by computer simulation. For the analysis of unsteady heat transfer phenomena in household, the method of using electrical equivalent R-C circuit is applied, and radiation heat transfer between panel, ceiling and walls in household is calculated by enclosure analysis method. The parametric study on two control methods, conventional on-off control and temperature error based time control(T.E.B.T.C.) method, are performed to compare thermal heating control performances, respectively.

  • PDF

자동차용 블록식 온도감응 팽창밸브의 모델링 (Modelling of an Automotive Block Type Thermostatic Expansion Valve)

  • 원성필
    • 설비공학논문집
    • /
    • 제23권4호
    • /
    • pp.251-258
    • /
    • 2011
  • The objective of this study is to propose two empirical correlations to predict the mass flow rate through an automotive block type thermostatic expansion valve and then to evaluate the correlations. The first correlation is deduced by modifying the basic equation of the orifice meter for the mass flow rate and the second correlation is deduced by using the Buckingham's ${\pi}$ theorem. The first correlation showed very good agreement on the measured data for R134a, given by Monforte. Average relative deviation and standard deviation of it are 2.5% and 1.6%, respectively. The second correlation agreed on the same measured data with a little greater deviations. The two correlations may apply to common expansion valves which have different geometrical sizes of the same shape.