• 제목/요약/키워드: The Electrical Fires

검색결과 186건 처리시간 0.027초

전기적 신호와 열적특성 분석에 의한 접촉불량 예측 (Prediction of Poor Contact by Analysis of Electrical Signal and Thermal Characteristics)

  • 이흥수;김두현;김성철;김윤복
    • 한국안전학회지
    • /
    • 제27권3호
    • /
    • pp.36-41
    • /
    • 2012
  • Electrical Connections often cause fires due to poor contact. Occurrence rate of these fires tends to increase annually. The reason why poor contacts occur is often because it is the low mechanical pressure at the contact points. A typical connection method using mechanical pressure is a screw terminal type. This study reviewed these poor contact cases in the screw terminals. In order to get reproduction of such cases, two types of experiments were conducted. the first one was conducted under the normal contact condition, and the other one was conducted under the poor contact condition that screw terminal of breaker was loosen and did not meet the requirements of toque value. In both types of experiments, compulsory vibration was adopted as a variable to aggravate poor contacts. Each of various current values(4.5A, 9.0A, 13.5A) is input. In these experiments, relationships of a contact, electrical signal such as current and electric pulse by ZCT and thermal characteristics according to vibration effect are analyzed. The suggested data and results in this study provide the useful resources helping to investigate fires due to poor contact, and they develop the detector for poor contact and finally reduce the electrical fire occurrence rate.

기호음료에 노출된 전기부품의 절연파괴 및 화재 위험성에 관한 연구 (Experimental Study on the Dielectric Breakdown and Fire Risk Assessment of Electric Parts Exposed to Various Beverages)

  • 오택현;김응식
    • 한국화재소방학회논문지
    • /
    • 제33권1호
    • /
    • pp.15-22
    • /
    • 2019
  • 최근 상가에서 사용되는 온장고에서 저장된 기호음료들의 유출로 인한 절연파괴로 화재가 발생한 사례가 자주 보고되고 있다. 하지만 기호음료의 전기적 특성과 음료 유출로 인한 화재 발생 원인에 대한 연구는 미비한 상태이다. 이에 본 연구에서는 이에 대한 인과 관계를 밝히고자 기호음료 32종을 선별하여 전도도 및 총 용존 고형물질(TDS)의 농도를 측정하였다. 그리고 이를 바탕으로 음료를 선별하여 전극 간 절연파괴 시험과 회로에 소자와 음료를 같이 배치한 후 모의실험을 실시하였다. 그 결과 화재 발생 가능성은 전도도가 높은 음료는 물론 낮은 음료라도 발화 가능성이 있다는 사실을 실험적으로 확인하였다. 또한, 기호 음료의 유출로 회로상에서 불꽃 방전을 일으키는 여러 조건을 발견할 수 있었다.

옥내 배선계통에서 직렬 아크의 검출과 판별 (Detection and Identification of the Series Arc in an Indoor Wiring System)

  • 김우현;왕국명;길경석;지홍근
    • 한국전기전자재료학회논문지
    • /
    • 제31권6호
    • /
    • pp.412-416
    • /
    • 2018
  • Most series arcs lead to electrical fires that cannot be interrupted by circuit breakers, because the arc's current is outside the breaker's operating range. In this paper, experiments were conducted on the detection and identification of series arcs to prevent electrical fires. Plugs and outlets specified in KS C 8305 were deteriorated to replicate arc faults commonly found in fields. The characteristics of series arcs resulting from various types of loose connections were determined by analyzing the frequency spectra and phase distributions of detected arc pulses. The results showed that the simulated arc defects used in this study were more similar to actual arc phenomena than the existing arc generator specified in UL 1699. In addition, loose connections, such as wire-wire, terminal-wire, and outlet-plug, can be identified by phases of $0^{\circ}$, $180^{\circ}$ and $360^{\circ}$, respectively. These phases can be detected by a band pass filter with a frequency range of 5~10 MHz, which can be used as the trip signal for circuit breakers.

Study on Fire Simulation in College Dormitories Based on Pyrosim

  • Zechen Zhang;Hasung Kong
    • International journal of advanced smart convergence
    • /
    • 제13권3호
    • /
    • pp.321-327
    • /
    • 2024
  • In recent years, the frequency of fires in college dormitories has been increasing, primarily due to outdated electrical wiring and improper use of electrical appliances. Given the high population density in such buildings, fires can cause significant damage to life and property. To better understand the dynamics of dormitory fires, this study uses Pyrosim fire simulation software to model fire scenarios in a six-story male dormitory. The study focuses on analyzing key factors such as heat release rates, smoke spread, temperature changes, and carbon monoxide concentrations during a fire. Simulation results indicate that smoke spreads rapidly after a fire breaks out, significantly reducing visibility and hindering evacuation efforts. Simultaneously, temperatures near the fire source rise quickly, exceeding safe levels, and carbon monoxide concentrations reach dangerous thresholds in a short time, greatly increasing the risk of poisoning. Based on these findings, the study proposes several recommendations to improve fire prevention in dormitories, including installing smoke barriers, improving evacuation routes, adding mechanical smoke extraction systems, and enhancing students' fire safety awareness and skills through regular training. These measures are crucial for reducing fire risks and enhancing fire safety in college dormitories.

화재예방을 위한 실시간 모니터링 시스템의 알고리즘 개발 (Development of a Novel Real-Time Monitoring System Algorithm for Fire Prevention)

  • 김병조;김재호
    • 한국안전학회지
    • /
    • 제29권5호
    • /
    • pp.47-53
    • /
    • 2014
  • Despite the automatic fire alarm system, according to the national fire data system of national emergency management agency, the fires account for 40,932 incidents, 2,184 injuries and about 430 billion won in property losses in 2013. Since the conventional automatic fire alarm system has several weaknesses related to electrical signal such as noise, surge, lighting, etc. Most fires are mainly caused by electrical faults, mechanical problem, chemical, carelessness and natural. The electrical faults such as line to ground fault, line to line fault, electrical leakage and arc are one of the major problems in fire. This paper describes the development of a novel real-time fire monitoring system algorithm including fault detection function which puts the existing optic smoke and heat detectors for fire detection with current and voltage sensors in order to utility fault monitoring using high accuracy DAQ measurement system with LabVIEW program. The fire detection and electrical fault monitoring with a proposed a new detection algorithm are implemented under several test. The fire detection and monitoring system operates according to the proposed algorithm well.

국내 원자력발전소의 공기 압축기실에서 윤활유 화재의 위험성 분석을 위한 FDS의 활용 (Application of FDS for the Hazard Analysis of Lubricating Oil Fires in the Air Compressor Room of Domestic Nuclear Power Plant)

  • 한호식;황철홍;백경록;이상규
    • 한국안전학회지
    • /
    • 제31권2호
    • /
    • pp.1-9
    • /
    • 2016
  • The standard procedure of fire modeling was reviewed to minimize the user dependence, based on the NUREG-1934 and 1824 reports. The hazard analysis of lubricating oil fires in the air compressor room of domestic nuclear power plant (NPP) was also performed using a representative fire model, FDS (Fire Dynamics Simulator). The area ($A_f$) and location of fire source were considered as major parameters for the realistic fire scenarios. As a result, the maximum probability to exceed the thermal damage criteria of IEEE-383 unqualified electrical cables was predicted as approximately 70% with $A_f=1m^2$. It was also found that for qualified electrical cables, the maximum probabilities of exceeding the criteria were 2% and 90% with $A_f=2$ and $4m^2$, respectively. It was concluded that all electrical cables should be replaced with IEEE-383 qualified cables and the dike to restrict as $A_f{\leq}2m^2$ should be installed at the same time, in order to assure the thermal stability of electrical cables for lubricating oil fires in the air compressor room of domestic NPP.

스타트모터 B단자 절연파괴 화재사례에 대한 실험적 연구 (A experimental Study on Insulation Breaking Fire Case of Starter Motor B Terminal)

  • 우승우;박정만;현병수;남정우;박우식;김진표;조영진;고재모;박남규
    • 한국안전학회지
    • /
    • 제34권5호
    • /
    • pp.55-62
    • /
    • 2019
  • In this paper, we introduce a case of a fire accident during parking of a large truck that is repeatedly occurring. The shape and location of the combustion and electrical singularity commonly found in other vehicle fire accidents could limit the starter motor as the ignition section. In addition, it was possible to confirm the electrical melting singularity that could act as a cause of ignition between the start motor B terminal and the start motor enclosure. By combining the above investigations and investigations, it was possible to estimate the electric fire expressed from insulation breaking of the starter motor B terminal, and by using the renewable starter motor comparison product mounted on the fire vehicle, an experiment was performed to reproduce the ignition process from the starter motor under specific conditions. So. It is hoped that this will raise awareness about vehicle fires, which can lead to large fires or casualties, share the risks of using starter motors for regeneration, and help in the rapid and accurate investigation of similar vehicle fires in the future.

계측된 전력정보를 이용한 전기화재 경보 퍼지 시스템 (Electrical Fire Warning Fuzzy System for Measured Power Informations)

  • 조도현
    • 전자공학회논문지
    • /
    • 제50권9호
    • /
    • pp.189-193
    • /
    • 2013
  • 이본 논문은 전력시스템에서 발생하는 전기화재를 예측하고 예방하기 위하여, 전력정보를 계측하고, 이 정보를 활용하여 전기화재를 예측하는 시스템을 제안하였다. 이를 위하여 과전류, 과부하와 과열에 대한 상관관계를 분석하였다. 이러한 상태들은 지락전류와 누설전류에 의하여 발생하고, 전기화재의 주요 원인이기 때문이다. 이 관계를 이용하여 퍼지규칙을 위한 소속도함수를 도출하였다. 또한 설계된 알고리즘에 수배전반의 실측된 전력정보를 활용하여 시뮬레이션 하였다.

옥내배선, 콘센트 및 플러그 개선을 통한 전기화재 예방대책 (Electrical and Fire Prevention Measures through Improvement of Indoor Wiring, Outlets and Plugs)

  • 정성효;안희석;이용수;김창은
    • 한국건설안전학회 논문집
    • /
    • 제1권1호
    • /
    • pp.31-39
    • /
    • 2018
  • 국내에서 발생하는 화재사고 중 약 20%가 전기설비에서 기인한 화재로 확인되고 있다. 복잡하고 대형화되어있는 건축물에서 전기화재는 재산 피해와 인명 피해가 증가하면서 대형화하는 양상으로 발생하고 있다. 여러 가지 전기화재의 원인 중 누전에 의한 발화가 약 71.5%를 차지하고 있고, 전기설비별 분류에서는 배선 및 배선기구에서 발생하는 화재가 약 38.3%를 차지하고 있다. 본 연구의 목적은 현재 사용되고 있는 옥내배선 형태를 개선하여 누전으로 인한 전기화재를 예방하는 방법을 제시하고, 배선기구에서 범용 되고 있는 콘센트와 플러그를 개선하여 배선기구에서 발생하는 화재를 예방하는 근원적 방안을 찾고자 한다. 본 연구를 통해서 제시되는 전기화재 예방대책은 전기화재의 근원적 원인을 제거하여 많은 인명과 재산을 보호하는 대책으로 활용될 수 있을 것으로 기대된다.