• Title/Summary/Keyword: Test standars

Search Result 1, Processing Time 0.014 seconds

A Study on Reliability Improvement of Domestic Ground Source Heat Pump Units by Analyzing the Certification System (국내 지열원 히트펌프 유닛의 인증제도 분석을 통한 신뢰성 향상 방안 연구)

  • Chan Woo Yang;Hee Jeong Kang;Sewang Oh;Ubin Do;Kwang Ho Lee;Jong Woong Choi;Yong Cho;Jong Min Choi
    • New & Renewable Energy
    • /
    • v.19 no.4
    • /
    • pp.72-83
    • /
    • 2023
  • Only ground source heat pump units certified according to the regulations in Korea can be adopted in ground source heat pump systems. In this study, domestic and international standards and regulations for ground source heat pump units were investigated. Unlike ISO 13256-1~2, which is the international standard, KS B 8292~8294 for ground source heat pump unit only included rated test conditions. Therefore, it is necessary to supplement various test conditions to the KS B series, because its performance data, which is required to calculate the system's design capacity, is dependent on the change in entering water temperature. The difference between the coefficient of performance of the certified ground source heat pump units and the certified criteria changed significantly according to the operating mode, heat source, and load type, because the criteria increased by about 5% for all. Thus, it is highly suggested that the certification standards be revised while considering the product performance level and various conditions.