• Title/Summary/Keyword: System multi-air conditioner

Search Result 32, Processing Time 0.026 seconds

Experimental studies of energy savings and economic effects by direct removal of carbon dioxide in the multi-use facility ($CO_2$ 직접 제거를 통한 다중이용시설의 에너지 절감 및 경제적 효과에 대한 실험적 연구)

  • Kim, Yo Seop;Lee, Ju-Yeol;Choi, Jin Sik;Shin, Jae Ran;Lim, Yun Hui;Park, Byung Hyun;Kim, Yoon-Shin
    • Journal of the Korean Applied Science and Technology
    • /
    • v.31 no.3
    • /
    • pp.466-471
    • /
    • 2014
  • It is important to develop the smart ventilation system in order to minimize a building energy consumption using ventilation. In this study, We evaluated the efficiency of the smart ventilation system being developed at the nursery. To evaluate the energy savings and carbon dioxide removal efficiency, two kinds of experimental conditions were compared. First, air conditioner and Smart HVAC system were operated. Second, air conditioner was operating and external air was put into the inside by rate of air circulation. It was more effective when working with air conditioning and ventilation system at the same time. If the Smart HVAC system is applied in a multi-use facility, indoor air quality will be comfortable and the social cost will be reduced.

Partial Fault Detection of Air-conditioning System by Neural Network Algorithm using Data Preprocessing Method (데이터 전처리기법을 적용한 신경망 알고리즘의 냉방기 부분고장 검출)

  • 한도영;이한홍;윤태훈
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.7
    • /
    • pp.560-566
    • /
    • 2002
  • The fault detection and diagnosis technology may be applied in order to decrease the energy consumption and the maintenance cost of the air-conditioning system. In this study, two different types of faults in the air-conditioning system, such as the condenser fouling and the evaporator fan slowdown, were considered. The neural network algorithm combined with data preprocessor was developed and applied to detect the faults of the real system. Test results show that this method is very effective to detect the faults in the air-conditioning system. Therefore, this developed method can be used for the development of the air-conditioner fault detection system.

Evaluation of Apartment Cooling System by Multi-Criteria Decision Making Analysis (다기준 의사결정 분석에 의한 공동주택의 냉방시스템 평가)

  • Kang, Byoung-Min;Cho, Jin-Hwan;Kim, Young-Il;Chung, Kwang-Seop
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.8
    • /
    • pp.580-586
    • /
    • 2011
  • In this study, 3 cooling systems of apartment which are air-cooled air conditioner with indoor unit, water-cooled air conditioner with indoor unit and small capacity absorption chiller-heater with FCU have been evaluated by Multi-Criteria Decision Making Analysis. Weights of 7 selected factors which are economics, space, billing, constructability, human comfort, visibility and reliability are determined by expert group of 30 system designers and 30 construction engineers. Final weights were derived for 101 and 166 $m^2$ apartments. Analysis shows that small capacity absorption chiller-heater with FCU is the most favorable system for apartment cooling system.

The Variation of Multi Air Conditioner Operation Characteristics with the Arrangements of Connection Pipe Lengths (멀티에어컨의 연결 배관길이의 변화에 따른 운전특성 변화)

  • Park, B.D.;Ha, D.Y.;Jeong, B.Y.;Koh, J.Y.;Yim, C.S.
    • Solar Energy
    • /
    • v.20 no.4
    • /
    • pp.45-52
    • /
    • 2000
  • Multi A/C is consisted of one outdoor unit and several indoor units. When the Multi Air conditioner is installed, we have to be cautious of the length of pipe arrangements. When the pipe arrangement is installed with unbalance or too long, there can be cooling capacity losses and low EER. An experimental study was carried out about the operation characteristic of Multi Air conditioner varying the length of pipe arrangements. If the pipe arrangement of the system is 15m, the cooling capacity and EER were decreased 0.8% and 1.3% respectively compared to the case when pipe arrangement is 5m. In case of 25m, the cooling capacity and EER were decreased 10.7% and 12.2% respectively compared to the case of 5m. When the length of pipe is not same each other, it is profitable to make the pipe length of highest capacity indoor unit shortest.

  • PDF

Development of Performance Evaluation and Control System of Multi-Air Conditioner (멀티에어컨의 성능평가 및 제어시스템 개발에 대한 연구)

  • Lee H.W.;Ko K.W.;Gwon Yeong-Cheol;Lee J.H.;Lee Y.J.
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2005.06a
    • /
    • pp.1107-1114
    • /
    • 2005
  • The running condition of multi-system air conditioner is prone to vary largely as it is designed for individual conditioning in each space of middle and small sized buildings. This leads to overcooling in case of partial load run, while the lack of capacity happens in case of full load run. Besides these, there exist such problems as instabilities due to the uneven refrigerant distribution caused by fluctuation of load and the change in piping line. Based upon the basic study on the function characteristics found in parts needed for maximized system working design in order to troubleshoot, the system functioning pattern should be identified through the different tests with various operating circumstances and the analysis models should be developed. With this ground, the control logic has to be made to have a control over capacity and make possible the efficient distribution of refrigerant.

  • PDF

Development of the Dynamic Simulation Program for the Multi-Inverter Heat Pump Air-Conditioner (멀티 인버터 히트펌프의 동특성 해석 프로그램의 개발)

  • ;;小山繁
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.11
    • /
    • pp.1079-1088
    • /
    • 2001
  • A dynamic simulation model was developed to analyse the transient characteristics of a multi-inverter heat pump. The programs included a basic air conditioning system such as a evaporator, condenser, compressor, linear electronic expansion valve (LEV) and by-pass circuit. The theoretical model was derived from mass conservation and energy conservation equations to predict the performance of the multi-inverter heat pump at various operating conditions. Calculated results were compared with the values obtained from the experiments at different operation frequencies of compressor, area of the LEV and configuration of indoor units operation. The results of the simulation model showed a good agreement with the experimental ones, so that the model could be used as an efficient tool for thermodynamic design and control factor design of air-conditioners.

  • PDF

A Study on the Evaluation of Air Change Efficiency of Multi-Air-Conditioner Coupled with Ventilation System

  • Kwon, Yong-Il;Han, Hwa-Taik
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.15 no.3
    • /
    • pp.101-107
    • /
    • 2007
  • Indoor air quality becomes of a concern recently in view of human health. This study investigates the air diffusion performance and the air change efficiency of a classroom, when outdoor air is introduced in two different ways in addition to the heating/cooling operation of a ceiling-mounted heat pump. A CFD analysis has been performed to investigate the effect of the discharge angle of the air jets from the heat pump for both parallel and series types of outdoor air system. It is observed that the series type creates more uniform indoor environment compared to the parallel type in general. It can be concluded the discharge angle should not be larger than 40o for the parallel type, in order not to generate thermal stratification in the room.

A Study on the Evaluation of Air Change Efficiency of Multi-Air-Conditioner with Ventilation System for Heating Season (환기시스템이 적용된 히트펌프의 난방시 급기효율 평가에 관한 연구)

  • Kwon Yong-Il;Han Hwataik;Kim Kyung-Hwan;Chung Baik-Young;Lee Gam-Gue
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.1
    • /
    • pp.56-61
    • /
    • 2005
  • Indoor air quality becomes of a concern recently in view of human health. This study investigates the air diffusion performance and the air change efficiency of a classroom, when outdoor air is introduced in addition to the heating/cooling operation of a ceiling-mounted heat pump. A CFD analysis has been performed to investigate the effect of the discharge angle of the air jets from the heat pump for both parallel and series types of outdoor air system. It is observed that the series type creates more uniform indoor environment compared to the parallel type in general. It can be concluded the discharge angle should not be larger than 40o for the parallel type, in order not to generate thermal stratification in the room.