• 제목/요약/키워드: Surge relief valve

검색결과 8건 처리시간 0.018초

펌프제어밸브를 사용한 취수펌프장에서의 수격현상 (Waterhammer for the Intake Pumping Station with the Pump Control Valve)

  • 김경엽;오상현
    • 한국유체기계학회 논문집
    • /
    • 제4권4호
    • /
    • pp.16-21
    • /
    • 2001
  • The field tests on the waterhammer were carried out for PalDang intake pumping station of the metropolitan water supply 5th stage project. The pumping station was equipped with the pump control valve as the main surge suppression device and the surge relief valve as auxiliary. However, the pump control valve had not been early controlled in the planned closing mode, and the slamming occurred to the valve which abruptly closed during the large reverse flow. Because the pressure wave caused by the pump failure was superposed on the slam surge, the upsurge increased so extremely that the shaft of the valve was damaged. It was desirable that the surge relief valve was installed in the pumping station or near the pump exit for the delay of response. After reforming the oil dashpot of the pump control valve, the sliming disappeared and the measured pressure was in fairly good agreement with the results of simulation. In case of three pumps for ${\phi}2,600$ pipeline being simultaneously tripped, the pressure head in the pumping station increased to 95.6 m, and the upsurge caused by the emergency stop of four pumps for ${\phi}2,800$ pipeline was 89.6m. We concluded that the pumping station acquired the safety and reliability for the pressure surge.

  • PDF

가압펌프장의 수격완화설비에 대한 보수·보강 사례 (Case Study of Repair Works on Surge Suppression Device for Booster Pumping Station)

  • 김상균;이동근;이계복;김경엽
    • 한국유체기계학회 논문집
    • /
    • 제8권4호
    • /
    • pp.20-26
    • /
    • 2005
  • When the pumps are started or stopped for the operation or tripped due to the power failure, the hydraulic transients occur as a result of the sudden change in velocity. The field tests on the waterhammer were carried out for Pangyo booster pumping station in which had six booster pumps and two in-line pumps with the motor of output 1,700 kW, respectively. The booster pumping station was equipped with the pump control valve as the main surge suppression device, and the surge relief valve as auxiliary one. But the pump control valve had not early controlled in the planned closing mode, the slamming occurred to the valve of which abruptly closed during the large reverse flow. Because the positive pressure wave caused by the pump failure was superposed on the slam surge, the upsurge increased so extremely that the pump control valve was damaged. After the air chambers were additionally installed in the booster pumping station, it was preyed that the water supply system acquire the safety and reliability on the pressure surge.

다목적 유전자 알고리즘을 이용한 상수관망에서 스프링 서지 완화 밸브의 최적화 (Optimum design of direct spring loaded pressure relief valve in water distribution system using multi-objective genetic algorithm)

  • 김현준;백다원;김상현
    • 상하수도학회지
    • /
    • 제32권2호
    • /
    • pp.115-122
    • /
    • 2018
  • Direct spring loaded pressure relief valve(DSLPRV) is a safety valve to relax surge pressure of the pipeline system. DSLPRV is one of widely used safety valves for its simplicity and efficiency. However, instability of the DSLPRV can caused by various reasons such as insufficient valve volume, natural vibration of the spring, etc. In order to improve reliability of DSLPRV, proper selection of design factors of DSLPRV is important. In this study, methodology for selecting design factors for DSLPRV was proposed. Dynamics of the DSLPRV disk was integrated into conventional 1D surge pressure analysis. Multi-objective genetic algorithm was also used to search optimum design factors for DSLPRV.

상수관망에서 서지 릴리프밸브의 최적 설계 방법론 (Methodology for optimum design of surge relief valve in water distribution system)

  • 김현준;허지성;김건지;백다원;김상현
    • 상하수도학회지
    • /
    • 제31권1호
    • /
    • pp.1-6
    • /
    • 2017
  • Surge pressure is created by rapid change of flow rate due to operation of hydraulic component or accident of pipeline. Proper control of surge pressure in distribution system is important because it can damage pipeline and may have the potential to degrade water quality by pipe leakage due to surge pressure. Surge relief valve(SRV) is one of the most widely used devices and it is important to determine proper parameters for SRV's installation and operation. In this research, determining optimum parameters affecting performance of the SRV were investigated. We proposed the methodology for finding combination of parameters for best performance of the SRV. Therefore, the objective function for evaluate fitness of candidate parameters and surge pressure simulation software was developed to validate proposed parameters for SRV. The developed software was integrated into genetic algorithm(GA) to find best combination of parameters.

직결식 펌프의 수격현상 (Waterhammer For In-line Booster Pump)

  • 김상균;이계복;김경엽
    • 유체기계공업학회:학술대회논문집
    • /
    • 유체기계공업학회 2004년도 유체기계 연구개발 발표회 논문집
    • /
    • pp.208-216
    • /
    • 2004
  • The waterhammer occured when the pumps are started or stopped for the operation or tripped due to the power failure, the hydraulic transients occur as a result of the sudden change in velocity. The field tests of the waterhammer were carried out for PanGyo booster pumping station. The PanGyo pumuing station was installed booster pump of 6 sets and in-line pump of 2 sets. The main surge suppression device was equipped with the pump control valve and the surge relief valve as auxiliary. However, the pump control valve had not early controlled in the planned closing mode, and the slamming occurred to the valve of which abruptly closed during the large reverse flow. Because the pressure wave caused by the pump failure was superposed on the slam surge, the upsurge increased so extremely that the shaft of the valve was damaged. After the addition surge suppression device was equipped with air chamber. Further more in-line pump is needed surge suppression device that the pumping station acquired the safety and reliability for the pressure surge.

  • PDF

고수두 1,000 MW 석탄화력발전소 냉각수계통 수격방지장치의 성능특성 (The Performance Characteristics of Anti-Surge Devices for High Head Cooling Water Systems in 1,000 MW Thermal Power plants)

  • 김근필;유호선
    • 플랜트 저널
    • /
    • 제15권4호
    • /
    • pp.36-42
    • /
    • 2019
  • 최근 환경 규제 정책 강화에 따른 입지 제약발생으로 발전소 부지가 높아지고 냉각수 관로의 길이가 증가되어 냉각수 계통 내 수격현상이 심화된다. 이는 발전소 안정성에 심각한 영향을 주게 된다. 본 연구에서는 수두가 높은 1,000 MW급 대용량 석탄화력발전소 냉각수계통에 대한 안정성을 확보하고자 비정상상태 1차원 해석 상용 소프트웨어인 LIQT 7.2을 사용하여 과도현상을 분석하고, 수격현상을 저감하기 위해 수격방지장치를 개별 및 조합 적용하여 성능특성에 대한 효과를 예측하였다. 수격방지 장치를 설치하지 않고 펌프가 불시 정지되었을 경우 발생하는 냉각수 서지압력은 펌프 출구 측에서 가장 크게 나타났다. 이러한 냉각수계통의 서지압력을 저감시키는 가장 효과적이고 간단한 방법은 펌프 보호를 위해 필수적 장치인 유압구동역류방지밸브에 진공파괴밸브를 조합한 것이다.

유전자 알고리즘을 이용한 서변 가압장 수리구조물의 최적설계 (Optimal Design of Hydraulic Device at the Seobyun Pumping Station using Genetic Algorithm)

  • 정봉석;김주인;김상현;박남식
    • 한국수자원학회논문집
    • /
    • 제33권3호
    • /
    • pp.289-298
    • /
    • 2000
  • 본 연구에서는 대구광역시에 위치하고 있는 서변 펌프가압장에서 발생되는 수격압을 최소화하기 위해 사용되는 감압밸브와 공기밸브의 최적 위치결정과 감압밸브의 최적 열림정도를 도모하였다. 가압장에서 발생하는 펌프의 급정지에 기인한 수격현상은 특성선방법을 이용하여 모의를 하였다. 최적화 방법은 강력한 탐색능력을 가지고 있으며 특히 비선형 문제를 해결하는데 탁월한 성능을 가지고 있는 유전자 알고리즘을 이용하여 실시하였다. 유전자 알고리즘의 계산결과는 감압밸브의 열림시간을 적게 할수록 최고 압력수두의 완화에 효과적이고, 열림시간을 크게 할수록 최대부압의 완화에 효과적임을 알 수 있었다. 본 연구는 특성선방법을 기반으로 하는 관망부속물들의 해석이 유전자 알고리즘과 결합되어 관로내 관로부속물의 최적설계에 도움을 줄 수 있음을 보여준다.

  • PDF

유압 구동계 에너지 재생 브레이크를 적용한 자동차 테일게이트 개폐장치에 대한 동특성 해석 (Dynamic Analysis on the Tail Gate System for Vehicle with the Energy Regenerative Brake of Hydraulic Driven Systems)

  • 최순우;허준영
    • 유공압시스템학회논문집
    • /
    • 제7권2호
    • /
    • pp.19-26
    • /
    • 2010
  • The typical trunk lid system for vehicle is composed of a hinge having 4-bar link and gas lifter. Here, the energy regenerative brake of hydraulic driven systems is applied to the tail gate system for vehicle and removed the gas lifter. The new tail gate system is composed of a hydraulic pump by electric motor, a hydraulic motor, four check valves, an accumulator, a relief valve and a directional control valve. The dynamic characteristics of the hydraulic motor system, such as the surge pressure and response time, are investigated in both brake action and acceleration action. The capacity selection method of accumulator by mathematical model is based upon trial and error approach and computer simulation by AMEsim software is carried out.

  • PDF