• Title/Summary/Keyword: Subway fire

Search Result 220, Processing Time 0.022 seconds

THE STUDY ON THE CHARACTERISTICS OF FIRE DRIVEN SMOKE-FLOW FOR DIFFERENT FIRE-LOCATION IN DEEPLY UNDERGROUND SUBWAY STATION (대심도 지하역사에서 화원 위치에 따른 연기거동 특징 연구)

  • Kim, H.B.;Jang, Y.J.;Lee, C.H.;Jung, W.S.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2009.04a
    • /
    • pp.202-207
    • /
    • 2009
  • In this study, Numerical simulations were performed to analyze the characteristics of fire driven smoke flow for different location of fire source in the deeply underground subway station with using FDS code. The fire driven smoke-flow which was simulated by using Parallel Computational Method for fast calculation and LES for turbulence model. In this research, the fire location to obstruct a suitable egress from the fire disaster were discussed.

  • PDF

Fire Test of Old Type Interiors of Subway Vehicle in ISO 9705 Room (ISO 9708 룸 설비를 이용한 구형 지하철 내장재 화재시험)

  • Lee, Duck-Hee;Park, Won-Hee;Jung, Woo-Sung;Hwang, Jung-Ho
    • Journal of the Korean Society for Railway
    • /
    • v.13 no.5
    • /
    • pp.481-487
    • /
    • 2010
  • A room scale fire test was done for interior materials from a subway vehicle installed within an ISO 9705 fire test room. The interior materials are the old ones which were made before the new fire safety guideline of subway vehicles. The output of ignition burner was increased in controlled steps to CEN/TS 45545-1. The objectives of this interior fire test are to assess the fire performance in terms of ignition and flame spread on interior lining materials and to provide data on an enclosure fires involving subway vehicle interior materials that grow to flashover. Temperatures, heat flux and heat release rate variations verse time of the test are measured. Heat release rate is compared with that of calculated by modified flaming area based summation method. These test results will be used for verification of CFD fire simulation of full subway vehicle.

Time-Temperature Curve for Fire Safety Assessment of Metropolitan Transit Tunnels (도시철도 터널구조체의 내화안정성 평가를 위한 표준시간-온도곡선 적용)

  • Won, Jong-Pil;Choi, Min-Jung;Lee, Su-Jin;Lee, Sang-Woo
    • Journal of the Korea institute for structural maintenance and inspection
    • /
    • v.14 no.3
    • /
    • pp.118-122
    • /
    • 2010
  • The study presents a standard time-temperature curve to evaluate the fire performance of subway tunnel structures. The central subway section is 135km long in Korea, the fourth longest in the world. The number of subway tunnels has been increasing rapidly and fire risk is proportional to the tunnel length. However, an adequate time-temperature curve for subway tunnel fires does not exist. Therefore, we studied a proposed foreign fire design model for which the heat rate is based on the traffic, and we present an appropriate time-temperature curve for Korean subway tunnels. The ISO 834 curve was used as a fire design model and the temperature distribution in the tunnel was estimated using numerical analysis. This led to a proposal for effective measures against subway tunnel fires.

PERFORMANCE EVALUATION OF PASSENGERS' EVACUATION FOR SMOKE-CONTROL MODES IN A SUBWAY STATION (지하역사 제연모드 승객피난 성능평가)

  • Park, Won-Hee;Chang, Hee-Chul;Jung, Woo-Sung;Lee, Han-Su
    • Journal of computational fluids engineering
    • /
    • v.13 no.4
    • /
    • pp.8-12
    • /
    • 2008
  • Heat/smoke detectors are installed in most subway platforms in Korea to detect fire. Subway platform is divided by smoke-control zones for efficient smoke-control. Once the detectors detect heat or smoke, the smoke-control ventilation system in the platform and concourse is activated according to the smoke-control ventilation mode. Smoke-control mode during fires in Korean subway platforms is that the smoke zones operate by exhausting smoke while other zones in the platform and in the concourse which is the upper floor of the platform operate by supplying air or stopping any ventilation. This study is conducted to evaluate performance of passengers' evacuation for various smoke control modes in the subway station. Distribution of smoke and heat due to fire on the platform is analyzed by using Fire Dynamics Simulator(FDS V 4.06) of NIST. Various smoke-control ventilation modes and locations of fire are considered. Evacuation and movement of passengers within the platform is simulated by building EXODUS V.4.0.

A Study on the Design of Evacuation Route at Subway Station Using Simulation Analysis (Simulation 분석을 통한 지하철 역사 피난동선 설계 방안에 관한 연구)

  • Ham, Eun-Gu;Roh, Sam-Kew
    • Journal of the Korean Society of Hazard Mitigation
    • /
    • v.10 no.5
    • /
    • pp.1-7
    • /
    • 2010
  • Since subway fire disaster at Daegu, Korea smoke control system and passengers evacuation distance has been focused to reform. Existing smoke control facilities need to expand volume of ventilation capacity however, the complicate subway station structure can hardly react dispersion of smokes from massive subway cabin fire. Smoke flow at platform level move upward thought vertical stairway and passengers evacuation goes with same direction. The victims of evacuees from subway station fire mainly due to exposure of heat radiation and smoke. The study demonstration the effect of downward evacuates stairway system by separating evacuation route to smoke movement pass way including saving times of evacuation.

Performance Evaluation of Passengers' Evacuation for Smoke-Control Modes in a Subway Station Based on CFD Results (전산열유체 해석결과를 이용한 지하역사 제연모드 승객피난 성능평가)

  • Park, Won-Hee;Jang, Yong-Jun;Lee, Han-Su;Chang, Hee-Chul;Lee, Duck-Hee
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2008.03b
    • /
    • pp.276-279
    • /
    • 2008
  • Heat/smoke detectors are installed in most subway platforms in Korea to detect fire. Subway platform is divided by smoke-control zones for efficient smoke-control. Once the detectors detect heat or smoke, the smoke-control ventilation system in the platform and concourse is activated according to the smoke-control ventilation mode. Smoke-control mode during fires in Korean subway platforms is that the smoke zones operate by exhausting smoke while other zones in the platform and in the concourse which is the upper floor of the platform operate by supplying air or stopping any ventilation. This study is conducted to evaluate performance of passengers' evacuation for various smoke control modes in the subway station. Distribution of smoke and heat due to fire on the platform is analyzed by using Fire Dynamics Simulator(FDS V 4.06) of NIST. Various smoke-control ventilation modes and locations of fire are considered. Evacuation and movement of passengers within the platform is simulated by buildingEXODUS V 4.0.

  • PDF

A Study for a Effectiveness of Smoke Control Operation Mode for a Subway with Separate Platform (지하철 상대식 승강장의 제연운전모드 실효성에 관한 연구)

  • Rie Dong-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.20 no.1 s.69
    • /
    • pp.24-29
    • /
    • 2005
  • This study aim to derive the operation method of a comprehensive ventilation system which is capable of providing passengers with safe exit paths from platforms in onboard The situations. The airflow distributions in subway platforms under 13 types of tunnel vent system for a double track stop condition was calculated and having analyzed diffusion behaviors of smoke and heat exhaust in such states by performing 13 kinds of different ventilation scenarios by using a 3-D Fire Dynamic Simulation (FDS) simulation model to clarify the safety evaluation for the heat and smoke exhaust on subway fire events.

Experiments of Smoke Behavior in an Underground Subway Station (지하역사에서의 화재연기거동 실험)

  • Kim, Dong-Hyeon;Jang, Yong-Jun;Park, Won-Hee
    • Journal of the Korean Society for Railway
    • /
    • v.10 no.1 s.38
    • /
    • pp.67-73
    • /
    • 2007
  • Experiments were carried out to investigate smoke movement in platform of a subway station which currently is in service in Pusan, the second largest city in Korea. The recently constructed underground station of the "bank type" (two platforms on both sides of track) which is the popular layout of platforms in Korea, is chosen in Pusan. The smoke generator and heater are used for simulating the smoke movement at the fire break in the platform located in the 2nd basement of the station. Video recordings were used to monitor smoke lowering. In this study, the movements of smoke in the underground station are investigated under various smoke-control operating modes. Three tests wire conducted according to its operating mode of the ventilation systems in the platform: no operation of any ventilation systems, smoke extraction mode in occurrence of fire (presently running mode) and full capacity of smoke extraction where all vents are activated in the platform. The results can be used for comparing with the numerical prediction results of fire subway stations.

The Study on Fire Phenomena in The Deeply Underground Subway Station (대심도 지하역사에서의 화재현상 연구)

  • Jang, Yong-Jun;Kim, Hag-Beom;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2008.06a
    • /
    • pp.1773-1780
    • /
    • 2008
  • When the fire occur in the deeply underground subway station, the difficulties of passenger evacuation are expected because of many stairs to the exit. In this study, SOONGSIL-University station (7 line, 47m depth) is the one of the deepest subway stations of the each line in the Seoul metro. The numerical computational-simulation was performed for the fire driven flow in the subway station. Hot and smoke flow was analyzed from the simulation results. The proper plan of evacuation against fire was considered through the results. The fire driven flow was simulated using FDS code in which LES method was applied. The Heat Release Rate was 10MW and the ultrafast model was applied for the growing model of the fire source. The proper mesh size was determined from the characteristic length of fire size. The parallel computational method was employed to compute the flow and heat eqn's in the meshes, which are about 10,000,000, with 6cpu of the linux clustering machine.

  • PDF

SIMULATION STUDIES ON A REDUCED-SCALE SUBWAY COACH FIRE (지하철 축소모형 객차화재 수치해석적 연구)

  • Kim, K.W.;Park, W.H.;Kim, C.H.;Jung, W.S.;Lee, D.H.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2010.05a
    • /
    • pp.501-504
    • /
    • 2010
  • In this study, fire behavior for subway coach fire in the 1/10 reduced scale model is analyzed using numerical analysis method (FDS). The size of the reduced model coach is 1.9 m long, 0.290 m high and 0.235 m. The simulation is carried out only one-sided four doors of the coach are opened. A fire source is the n-heptane pool fire with a mean heat release rate 2.33 kW. Smoke temperature, heat release rate and mass loss rate for the model are calculated.

  • PDF