Verification Strategy of IEC 61850 Communication Reliability for Constructing the Substation Automation System (변전자동화시스템 구축을 위한 IEC 61850 통신신뢰성 검증 방안)

  • Lee, N.H.;Jang, B.T.;An, Y.H.;Kim, B.H.;Shin, E.B.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.10a
    • /
    • pp.231-234
    • /
    • 2009
  • IEC 61850 based substation automation system is operating under digital network with a number of IEDs and a HMI as relation of server and client. In case of IEDs, before implementing the system, all of the system integrators require IEC 61850 certificate from individual IED manufacture. Otherwise, there is nothing to verify IED for constructing substation automation system at the real substation. This paper shows verification strategy of IEC 61850 communication reliability such as association /release, report, dataset and four type control function.

  • PDF

A Study on Reliability Analysis of Substation Automation System (변전소 자동화 시스템의 신뢰도 해석에 관한 연구)

  • Park, Chul-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.64 no.4
    • /
    • pp.281-285
    • /
    • 2015
  • Electrical energy supply interruption degrades reliability of power supply as well as social costs and economic loss. It is important to assess the reliability of the power system. Nowadays IEC61850 based substation automation system(SAS) has been developed for an updating of automation and interoperability. In this study, three kinds of reliability block diagram(RBD) were proposed to examine of network availability of the three types SAS. And reliability and unreliability of the SAS was formulated using the RBD. Finally, while varying the value of reliability and unreliability, the reliability and the unreliability of the overall system were evaluated.

A Study on the Model of A Electric Railway Substation Automation Based on IEC 61850 and IEC 61970 (IEC 61850과 IEC 61970을 표준으로 하는 전철변전소 종합자동화 모델에 관한 연구)

  • Ko, Chung-Ku;Jang, Woo-Jin;Choi, Kyu-Hyoung
    • Proceedings of the KSR Conference
    • /
    • 2011.10a
    • /
    • pp.1014-1019
    • /
    • 2011
  • The substation automation is a system to remote-monitor and control electric power flow. And in line with electrification of railway, an interest in electric railway substation automation is increasing. IEC standardized IEC 61850, IEC 61968 and IEC 61970 communication protocol for the telecommunication standardization of the electric power automation industry. The recent SCADA systems in managed electric railway substations are have the problem about the compatibility with the products which fit to the international standard specification afterward. In this paper, the model of electric railway substation automation based on IEC 61850 and IEC 61970 is presented. And the method supporting the compatibility between the equipment is proposed.

  • PDF

Study on IEC 61850 Performance Testing Procedures of BF Protection IED (차단키 실패 보호 IED의 IEC 61850 시스템 성능 시험 절차서에 관한 연구)

  • Lee, Nam-Ho;Jang, Byung-Tae
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.8
    • /
    • pp.59-66
    • /
    • 2008
  • Korea Electric Power Research Institute in charge of the power IT project "Development of Prototype for Advanced Substation Automation System based on the Digital Control Technology" is performing system verification. Breaker Failure protection IED can operate protection activity by communicating with other IEDs such as T/L IED, owing to IEC 61850 international standard and digital substation automation system. Accordingly, IED testing process should be changed from the conventional way by electrical contact test on individual IED to system based testing method by network communication. This paper describes how to test BF IED based on substation automation system and testing procedures using UML, which is used to implement S/W design.

IEC 61850 Application in Distribution Automation System (배전자동화 시스템에 IEC 61850 적용 방안)

  • Kim, Taw-Wan;Lim, Il-Hyung;Choi, Myeon-Song;Lee, Seung-Jae;Kwon, Sung-Chul
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.4
    • /
    • pp.687-693
    • /
    • 2011
  • In this paper, problems and solutions are proposed for applying IEC 61850 to Distribution Automation System(DAS). Communication protocol integration in power automation system have issued by IEC standards, IEC 61850 of them has researched for applying IEC 61850 to many areas of power system in spite of that it was made for substation automation system. Especially, DAS is just about to apply IEC 61850 by communication network change from serial to ethernet although DNP 3.0 is used. But it's impossible to apply directly IEC 61850 to DAS by difference of environment which unfixed wide area and separated nodes in power distribution system unlike concept of IEC 61850 is made by Substation Automation System(SAS) environment of limited space. Thus, this paper proposed applications of three types which conceptual, practical, and future to consider problems and solutions when apply IEC 61850 to Ethernet based DAS.

A Structural Approach and Deployment of a Substation Automation System (변전소 자동화 시스템의 구성 및 개발 사례)

  • You, Jeong-Sik;Lee, Kwon-Han;Choi, Dae-Hee;Choi, Yong-Bum;Lee, Hak-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.258-260
    • /
    • 2001
  • This paper describes the definition of a substation automation system and presents core components and its layered structure based on the modular approach. Also it introduces the implementation and deployment of our substation automation system which was adopted to the field recently.

  • PDF

Development of IEC 61850 Performance Testing Procedures of BUS Protection IED Using UML (UML을 이용한 모선보호 IED의 IEC 61850 성능시험 절차서 개발)

  • Lee, Nam-Ho;Jang, Byung-Tae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.5
    • /
    • pp.767-772
    • /
    • 2008
  • Korea Electric Power Research Institute in charge of the power IT project "Development of Prototype for Advanced Substation Automation System based on the Digital Control Technology", is performing the verification of performance of the substation automation system. In order to verify a system based BUS protection IED, the standardized document and procedures are required. But there is nothing to describe systematically how to verify IEC 61850 based IED in the system environment except an individual IED testing way and report. This paper presents the substation automation system based ways and procedures to verify the IED using UML(Unified Modelling Language).

A Study on the Field Test of IEC 61850 based Substation Automation System (IEC 61850 변전자동화시스템 실증시험에 관한 연구)

  • Lee, N.H.;Jang, B.T.;Kim, B.H.;Shim, E.B.
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.250_251
    • /
    • 2009
  • IEC 61850 based substation automation system mainly consists of human machine interface as a client and a various of IEDs as a server. Both of them should require the field testing for performance verification including IEC 61850 communication services. This means that the test can assure the interoperability of IEC 61850 based substation automation system consisted of multi vendor's products. This paper shows a research result on the field test of the IEC 61850 based HMI and IEDs. And it proposes some engineering solutions for the system implementation.

  • PDF

STUDY ABOUT THE SELECTION OF COMTROL AND INDICATION POINT FOR TOTAL AUTOMATION (전력설비종합자동화를 위한 감시제어포인트 선정에 관한 연구)

  • 이용해;남태현
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1989.10a
    • /
    • pp.562-566
    • /
    • 1989
  • The selection of control and indication joints effects the supervisory and control scope of SCADA system. This paper proposes the point selection for the no-man substation. The points of no-man s/s are 3-4times as many ad points of man-substation. And also the considering points are described to implement total automation.

  • PDF

Development of an Intelligent Station HMI in IEC 61850 Based Substation

  • Rim, Seong-Jeong;Zeng, Sheng-Wu;Lee, Seung-Jae
    • Journal of Electrical Engineering and Technology
    • /
    • v.4 no.1
    • /
    • pp.13-18
    • /
    • 2009
  • Because the existing Human-Machine Interface (HMI) for the conventional substation cannot dynamically indicate the configuration information of the Substation Automation System (SAS). In this paper, an intelligent station HMI is proposed for IEC 61850 based substation. The program of the proposed HMI not only can automatically generate the layout of single line diagram, but can also indicate the communication network and functions of IEDs by reading SCL files. It greatly helps monitor the operation status, communication network and each IED dynamically, such as failure detection in SAS. Furthermore, this paper presents the possibility of developing new software for SAS with the full use of IEC 61850-6. Once the software is complete, there is no need to change it when the substation is upgraded or when it is migrated to other IEC 61850 based substations, which is a cost-effective solution.