나선형 핀튜브 열교환기의 열전달 특성에 관한 실험적 연구 (Experimental Study on the Heat Transfer Characteristics of Spiral Fin-Tube Heat Exchangers)

  • 윤린;김용찬;김슬우;최종민
    • 설비공학논문집
    • /
    • 제17권6호
    • /
    • pp.529-535
    • /
    • 2005
  • This study experimentally examines the air-side performance of spiral finned tube heat exchangers. The effects of fin spacing, fin height, and tube alignment were investigated. Reduction of fin spacing decreased the Colburn j factor. However, the effect of fin height on the Colburn j factor was negligible. An increase of tube row decreased the Nusselt number for both staggered and in-line tube alignments. However, the decrease of the Nusselt number for the in-line tube alignment was much more significant than that of the staggered tube alignment. The average Nusselt number of the staggered tube alignment was larger than that of the in-line tube alignment by $10\%$ when the Reynolds number ranged from 300 to 1700. An empirical correlation of the Nusselt number was developed by using geometric parameters of heat exchanger and correction factors. The correction factor considered the effects of tube alignment and number of tube rows on the heat transfer. The proposed correlation yielded a mean deviation of $4\%$ from the present data.

독립 핀-튜브 열교환기의 열전달 성능특성에 관한 연구 (Study on Heat Transfer Characteristics of Discrete Fin-and-tube Heat Exchangers)

  • 이호성;김용한;최종민;김용찬
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.274-280
    • /
    • 2005
  • The objective of this study Is to investigate the heat transfer performance of plate discrete fin-and-tube heat exchangers with large fin pitch. In this study, twenty-two heat exchangers were tested with a variation of fin pitch, number of tube row, longitudinal tube pitch and fin alignment. Discrete fin type exchangers improved heat transfer performance more than 10% compared to tile continuous fin type heat exchangers. The air-side heat transfer coefficient decreased with a reduction of the fin pitch and an increase of the number of tube row, The staggered fin alignment improved heat transfer performance more than 6% compared to the inline fin alignment. The effect of longitudinal tube pitch was insignificant on the j-factor and experiments found opposite effects on the j-factor with respect to fin alignment. Heat transfer correlations were developed from the measured data for flat plate discrete fin-and-tube heat exchangers with large fin pitch. The correlations yielded good predictions of the measured data with mean deviations of 1,4% and 0.3% for tire inline and staggered tube alignment, respectively.

  • PDF

핀-튜브 열교환기의 핀피치 및 열수 변화에 따른 열전달 성능특성에 관한 연구 (Heat Transfer Characteristics of Flat Plate Finned-Tube Heat Exchangers with a Variation of Fin Pitch and Number of Tube Row)

  • 김용한;이호성;김용찬
    • 설비공학논문집
    • /
    • 제17권10호
    • /
    • pp.930-937
    • /
    • 2005
  • The objective of this study is to investigate the heat transfer performance of flat plate finned-tube heat exchangers with large fin pitch. In this study, twenty-two heat exchangers were tested with a variation of fin pitch, number of tube row, and tube alignment. The heat transfer coefficient decreased with a reduction of the fin pitch and an increase of the number of tube row. The staggered tube alignment improved heat transfer performance more than $10\%$ compared to the inline tube alignment. A heat transfer correlation was developed from the measured data for flat plate finned-tubes with large fin pitch. The correlation yielded good predictions of the measured data with mean deviations of $3.6\%\;and\;6.4\%$ for the inline and staggered tube alignment, respectively.