• Title/Summary/Keyword: Smoke Ventilation System

Search Result 107, Processing Time 0.033 seconds

Effect of Positive Pressure Ventilator Tilting Angle on the Flame Suppression and Smoke Density (Positive Pressure Ventilator 경사각 변화에 의한 화염억제 효율과 연기농도 변화)

  • Kim, Sung-Won;Lee, Kyoung-Duck;Shin, Chang-Sub
    • Fire Science and Engineering
    • /
    • v.20 no.4 s.64
    • /
    • pp.135-142
    • /
    • 2006
  • The experiment applied Positive Pressure Ventilation to rapidly exhaust heat and smoke inside the construction in the fire was done. Changes of heat discharge and smoke density were measured, with the various blowing condition like a fan tilting angle to find the effect of the parameter. Experimental apparatus were with PPV and water mist system for better efficiency, and investigate the effect of heat discharge and smoke removal. In the experiment, flame temperature has decreased when PPV was applied. Smoke density, generated from fire also decreased dramatically and the efficiency showed the highest rate at $0^{\circ}$ tilting angle. In addition, combination of PPV and water mist system highly improved the efficiency of evacuation on heat and smoke density, clearly was influenced by the tilting angle.

A Fire Simulation of Light Railway Transit (경량전철시스템의 화재 시뮬레이션)

  • Won Chan-Shik;Lee Ki-Choon;Hur Nahmkeon;Mok Jae-Kyun
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2001.05a
    • /
    • pp.170-175
    • /
    • 2001
  • Fire inside light railway transit(LRT) was simulated for various fire scenarios using CFD analysis in order to assess the safety of passengers. Considered in the present paper are the effects of locations of fire, a fire size, an operation of ventilation system and an opening time of door on evolution of temperature and smoke concentration inside the LRT. For fire simulation, fire cells releasing heat and smoke corresponding to fire size were positioned at the location of fire. From the results, it is seen that the ventilation system and the opening time of door were the most important factors on temperature and smoke concentration inside the LRT

  • PDF

Numerical Study on the characteristics of fire driven flow for smoke ventilation system operating in the deeply underground subway station (대심도 지하역사에서의 화재시 급 배기 동작유무에 따른 열 연기 거동 분석)

  • Jang, Yong-Jun;Kim, Hag-Beom;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.66-72
    • /
    • 2008
  • In this study, transient 3D numerical simulations were performed to analyze the characteristics of fire driven flow for smoke ventilation system operating conditions in the deeply underground subway station. The smoke flow patterns were compared and discussed under smoke fan operating mode and off mode in the platform. Soongsil Univ. station(line number 7)was chosen for simulation which was the one of the deepest underground subway stations in the each lines of Seoul. The geometry for model is 365m in length include railway, 23.5m for width, 47m for depth. Therefore 10,000,000 structured grids were used for fire simulation. The parallel computational method for fast calculation was employed to compute the heat and mass transfer eqn's with 6 CPUs(Intel 3.0GHz Dual CPU, 12Cores) of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source.

  • PDF

Effect of the HVAC Conditions on the Smoke Ventilation Performance and Habitability for a Main Control Room Fire in Nuclear Power Plant (원자력발전소 주제어실 화재 시 공조모드가 배연성능 및 거주성에 미치는 영향 분석)

  • Kim, Beom-Gyu;Lim, Heok-Soon;Lee, Young-Seung;Kim, Myung-Su
    • Fire Science and Engineering
    • /
    • v.30 no.5
    • /
    • pp.74-81
    • /
    • 2016
  • This study evaluated the habitability of operators for main control room fires in nuclear power plants. Fire modeling (FDS v.6.0) was utilized for a fire safety assessment so that it could determine the performance of the smoke ventilation and operator habitability with the main control room. For this study, it categorized fire scenarios into three cases depending on the conditions in the HVAC system. As a result of fire modelling, it showed that Case 1 (with HVAC) would give rise to the worst situation associated with the absolute temperature, radiative heat flux, optical density, and smoke layer height as deliberating the habitability and smoke ventilation. On the other hand, it showed that Cases 2 (w/o HVAC) and 3 can maintain much safer situations than Case 1. In the case of temperature at 820 s, Cases 2 and 3 were up to approximately 63% greater than Case 1 in the wake of ignition. In addition, the influence of radiative heat flux of Case 1 was even larger than Cases 2 and 3. That is, the radiative heat fluxes of Cases 2 and 3 were approximately 68% higher than Case 1. Furthermore, when it comes to considering the optical density, Case 1 was approximately 93% greater than Cases 2 and 3. Accordingly, it expected that the HVAC system can influence a the performance on the smoke ventilation that can be sustainable for operator habitability. On the other hand, it revealed an inconsecutive pattern for the smoke layer height of Cases 2 and 3 because supply vents and exhaust vents were installed within the same surface.

Study on Heat and Smoke Exhaust Characteristics for Different Operating Modes of Platform and Tunnel Fans during a Passenger Train Fire (전동차 화재시 승강장 및 터널 환기실의 팬 작동에 따른 열 및 연기 배출 특성 연구)

  • Chang, Hee-Chul;Kim, Tae-Kuk;Son, Bong-Sei;Park, Won-Hee
    • Fire Science and Engineering
    • /
    • v.22 no.1
    • /
    • pp.61-67
    • /
    • 2008
  • This study is focused on the numerical predictions of heat and smoke exhaust characteristics in an underground subway station stopping a fire train. Various ventilation operating modes with the fan equipped the platform and tunnels are considered. Distributions of temperature, carbon monoxide and visibility at a height of 1.7 m(breath height) above the platform are analysed for different ventilation fan operation mode. The numerical results show that smoke and heat is rapidly removed through tunnel by operating the tunnels fans. We suggested that during evacuation of passengers is not completed, the ventilation system in the platform is activated. After completion of passenger evacuation tunnel fans are activated but the fans in the platform are stopped.

The 1D-3D Simulation for Smoke Ventilation in a Rescue Station of a Railroad Tunnel under the Fire (장대 터널 내 구난역의 열차 화재 시 제연을 위한 1D-3D 연계 해석)

  • Jung, Jae-Hyuk;Hur, Nahm-Keon;Lee, Jung-Pyo;Kim, Jin-Kon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.10
    • /
    • pp.665-671
    • /
    • 2010
  • In the present study a 1D-3D numerical simulation was performed to analyze the fire safety in a rescue station of a long railroad tunnel equipped with a mechanical ventilation. The behavior of hot air was studied for the emergency operation mode of ventilation system in case of fire in the rescue station. The 1D simulation was carried out for entire tunnel region. Detailed 3D CFD simulation was performed for the rescue station area in the central region of the tunnel by using the result of the 1D simulation as the boundary condition of the 3D simulation. Various type of cross passage installation were evaluated for the prevention of smoke diffusion to suggest the optimized interval of the cross passages in the rescue tunnel.

Numerical Simulation on Smoke Movement in Multi-Compartment Enclosure Fires under Pressurized Air Supply Conditions (급기가압 조건에서 복합 구획 공간 화재의 연기 거동에 대한 수치해석 연구)

  • Ko, Gwon Hyun
    • Fire Science and Engineering
    • /
    • v.32 no.6
    • /
    • pp.15-21
    • /
    • 2018
  • This study examined the flow characteristics of fire smoke under pressurized air ventilation conditions by carrying out fire simulations on multi-compartment enclosure, including room, ancillary room and stair case. Fire simulations were conducted for the air-leakage test facility, which was constructed to measure the effective leakage area and aimed to improve the understandings of fire and smoke movement by analyzing the overall behaviors of fire smoke flow and pressure distributions of each compartment. The simulation results showed that the heat release rate of the fires was controlled sensitively by the amount of air supplied by the ventilation system. An analysis of the velocity distributions between the room and ancillary room showed that fire smoke could be leaked to the ancillary room through the upper layer of the door, even under pressurized air supply conditions. From these results, it was confirmed that the fire size and spatial characteristics should be considered for the design and application of a smoke control system by a pressurized air supply.

A Study on Ventilation Effects on Smoke Behavior in Rescue Station for Tunnel Fires (철도터널 화재시 구난역 내의 연기거동에 미치는 배연효과에 관한 연구)

  • Jang, Won-Cheol;Kim, Dong-Woon;Lee, Seong-Hyuk;Ryou, Hong-Sun
    • Journal of the Korean Society for Railway
    • /
    • v.11 no.3
    • /
    • pp.294-299
    • /
    • 2008
  • The present study investigates the ventilation effects on smoke spreading with the rescue stations. Experiments for tunnel fires were carried out for n-heptane pool em at different fire locations, and the heat release rates (HRR) were obtained by addition, using the commercial code (FLUENT), the present article presents numerical results for smoke behavior in railway tunnels with rescue station, and it uses the MVHS (Modified Volumetric Heat Source) model for estimation of combustion products resulting from the fire source determined from the HRR measurement. As a result, it is found that smoke propagation is prevented successfully by the fire doors located inside the cross-passages and especially, the smoke behavior in the accident tunnel can be controlled through the ventilation system because of substantial change in smoke flow direction in the cross-passages.

Evaluation of Smoke Control Performance of Ventilation System Using by Hot Smoke Test (Hot Smoke Test를 이용한 주차장 환기설비의 제연 성능평가)

  • Joung, Suckhwan
    • Journal of Korean Society of Disaster and Security
    • /
    • v.12 no.2
    • /
    • pp.47-56
    • /
    • 2019
  • Recently, in order to overcome the difficulty of entering a fire source due to the occurrence of a large amount of smoke in the event of a fire in a parking lot, it has used that a method of discharge smoke using air supply, exhaust fans and jet fans installed for ventilation of parking lots. In this study, the variation of flow in the smoke layer was observed using CCTV under two conditions, in which only the air supply fan operates and the manned fan operates together, and the temperature around the plume was compared to Albert eq. to assess its suitability as a parking lot ventilation performance evaluation method. As a result, it was found that the smoke layer could be disturbed if the Jet Fan was operated at the same time, which could lead to the possibility of an initial evacuation disturbance. However, the additional operation of the Jet Fan has been confirmed by the observation CCTV that the emission performance is improved, which is believed to help conduct the suppression operation. The temperature around the plume was measured and compared to Alpert eq, and was analyzed to be about $2^{\circ}C$ lower at the center axis of the plume and $9.0^{\circ}C$ higher at 8 m in the direction of the discharge of smoke. The results of temperature measurements around the plume were lower than the maximum temperature expected in AS 4391 and did not exceed the expected temperature risk caused by the experiment. As with these results, the temperature risk from the progression of hot smoke tests is foreseeable, so it will be available as one of the general evaluation methods for assessing smoke control performance in a parking lot without relevant criteria.

Comparison of Two Different Smoke Extraction Schemes of Transversely Ventilated Tunnel Fire

  • Rie, Dong-Ho;Kim, Hyung-Taek;Yoo, Ji-Oh;Shin, Hyun-Jun;Yoon, Sung-Wook
    • International Journal of Safety
    • /
    • v.4 no.2
    • /
    • pp.30-35
    • /
    • 2005
  • In case of tunnel fire, one of the most effective facilities to save lives is the smoke control system. In this study, two different smoke extraction schemes of transversely ventilated tunnel were compared. One is the smoke extraction using the fixed exhaust ports on the false ceiling to achieve the uniform and distributed smoke extraction (uniform exhaust). The other is that using the remote controlled smoke extraction where only vents close to the fire is opened whereas the others are closed to enhance the limitation of the smoke spread (localized exhaust). A number of numerical simulations were performed to find out the optimal smoke extraction rate at each smoke extraction scheme to allow the tunnel users to escape to the safe area without endangering their lives by smoke.