• 제목/요약/키워드: Slit fin-tube heat exchanger

검색결과 35건 처리시간 0.025초

휜-관 열교환기에 있어서 각종 휜 형상의 성능 특성에 관한 실험적 연구 (Experimental study of performance characteristics of various fin types for fin-tube heat exchanger)

  • 윤백;김영생;박환영;박현연
    • 설비공학논문집
    • /
    • 제11권4호
    • /
    • pp.484-491
    • /
    • 1999
  • Air side heat transfer and pressure drop for ø9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power.

  • PDF

Experimental Study of Performance Characteristics of Various Fin Types for Fin-Tube Heat Exchanger

  • Youn, Baek;Kim, Young-Saeng;Park, Hwan-Young;Park, Hyun-Yeon
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제8권2호
    • /
    • pp.29-38
    • /
    • 2000
  • Air side heat transfer and pressure drop for f 9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65 mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7 mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power

  • PDF

웨이브 및 웨이브-슬릿 열전달촉진 휜-관 열교환기의 공기측 압력강하 및 열전달 특성에 관한 실험 (Experimental study of air side pressure drop and heat transfer characteristics of wave and wave-slit fin-tube heat exchangers)

  • 윤백;길용현;박현연;유국철;김영생
    • 설비공학논문집
    • /
    • 제10권5호
    • /
    • pp.589-599
    • /
    • 1998
  • Air side heat transfer and pressure drop for fin-tube heat exchanger with wave and wave-slit fins were measured for various fin spacings and number of tube rows. Outer diameter of the tube including fin collar is 10.07mm, and experiments were done with dry surface condition. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively, and wave depth of the wave fin is 2mm. Experiments were conducted for 1, 2 and 3 rows and 3 different fin spacings, 1.3, 1.5 and 1.7mm. An attempt was made to demonstrate advantage of the enhanced fins over the plane fin by introducing the concept of fan power, Effect of the number of tube rows on heat transfer was discussed in connection with general mechanisms of heat transfer enhancement for fin-tube heat exchanger. Also the effect of hydrophilic coating was investigated. Lastly, correlations for Colburn j-factor and friction factor were developed.

  • PDF

다양한 형상의 판형 휜을 장착한 원통다관형 열교환기의 열성능 해석 (Thermal Performance Analysis of a Shell-and-Tube Heat Exchanger with Plate Fins of Various Shape)

  • 신지영;손영석
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제28권4호
    • /
    • pp.648-656
    • /
    • 2004
  • In this study, a highly efficient shell-and-tube heat exchanger with plate fins is considered to improve thermal performance of the conventional shell-and-tube heat exchanger. This type of shell-and-tube heat exchanger with plate fins of various shape is simulated three-dimensionally using a commercial thermal-fluid analysis code. CFX4.4. The effect of the shape of the plate fin on heat transfer characteristics is also investigated by the simulation. Plate fins of four different shapes. plane, plane-slit. wave. and wave-slit fins, are considered. The flow fields, pressure drop and heat transfer characteristics in the heat exchanger are calculated. It is proved that the shell-and-tube heat exchanger with plate fins is superior to the conventional shell-and-tube heat exchanger without plate fins in terms of heat transfer. The shape of the plate fin is important in the performance of a heat exchanger such as heat transfer and pressure drop.

확대모델을 이용한 특성화된 핀형상의 열전달평가 (An Evaluation of Heat Transfer Characteristics of Individualized Fin Type Using Large Scale Model)

  • 윤점열;강희찬;이관수;김무환
    • 설비공학논문집
    • /
    • 제8권1호
    • /
    • pp.166-175
    • /
    • 1996
  • In recent years, air-conditioning units designed with higher efficiency and more compactness are required due to emphasis on energy efficiency in home electrical appliances. This trend in the air-conditioning industries has accelerated the development of improved heat exchanger with a better performance in heat transfer aspects. In this study, experiments were performed to investigate the shape and configuration of fins affecting on the performance of the conventional fin-and-tube type heat exchanger equipped in a commercial air conditioners. The geometry similtude method was employed to measure the heat transfer coefficient and pressure drop. Experimental results show that this method is very useful to analyze the heat transfer characteristics of the fin-and-tube type heat exchanger. It is also found that the slit fin has better performance than the conventional fin type in the air conditioners. The present results indicate that heat transfer from the fin si influenced by the parameters such as the forming area of the slit fin, the type of interrupted surfaces like a louver or slit, slit patterns and slit raised direction, and it also affects the overall heat exchanger performance.

  • PDF

증발기의 설계조건에서 공기측 열전달계수 및 압력강하 산출 (Evaluation of Air-side Heat Transfer and Friction Characteristics on Design Conditions of Evaporator)

  • 김창덕;이진호
    • 설비공학논문집
    • /
    • 제15권12호
    • /
    • pp.1007-1017
    • /
    • 2003
  • An experimental study on the air-side pressure drop and heat transfer coefficient of slit fin-tube heat exchanger has been carried out. The data reduction methodology for air-side heat transfer coefficients in the literature is not based on a consistent approach. This paper focuses on new method of data reduction to obtain the air-side performance of fin-tube heat exchanger using R22 and recommends standard procedures for dry and wet surface heat transfer estimation in fin-tube heat exchanger having refrigerant on the tube-side. Results are presented as plots of friction f-factor and Colburn j -factor against Reynolds number based on the fin collar outside diameter and compared with previous studies. The data covers a range of refrigerant mass fluxes of 150∼250 kg/$m^2$s with air flows at velocity ranges from 0.3 m/s to 0.8 m/s.

응축기의 설계조건에서 공기측 열전달계수 및 압력강하 산출 (Evaluation of Air-side Heat Transfer and Friction Characteristics on Design Conditions of Condenser)

  • 김창덕;전창덕;이진호
    • 설비공학논문집
    • /
    • 제15권3호
    • /
    • pp.220-229
    • /
    • 2003
  • An experimental study on the air-side pressure drop and heat transfer coefficient of slit fin-tube heat exchanger has been carried out. The data reduction methodology for air-side heat transfer coefficients in the literature is not based on a consistent approach. This paper focuses on new method of data reduction to obtain the air-side performance of fin-tube heat exchanger using R22 and recommends standard procedures for dry surface heat transfer estimation in fin-tube heat exchanger having refrigerant on the tube-side. Results are presented as plots of friction f-factor and Colburn j -factor against Reynolds number based on the fin collar outside diameter and compared with previous studies. The data covers a range of refrigerant mass fluxes of 150~250 kg/$m^2$s with air flows at velocity ranges from 0.6 m/s to 1.6 m/s.

습표면 조건에서 슬릿 핀-튜브 열교환기의 열전달 및 압력강하 특성 (Heat Transfer and Friction Characteristics of Slit Fin and Tube Heat Exchangers in Wet Conditions)

  • 장근선
    • 설비공학논문집
    • /
    • 제19권1호
    • /
    • pp.1-9
    • /
    • 2007
  • Water condensate accumulated on the surface of a fin-and-tube heat exchanger significantly affects its thermal and hydraulic performance. The purpose of this study is to investigate the effect of condensate retention on the air-side heat transfer performance and flow friction. Total 12 samples of slit and plate fin-and-tube heat exchangers with varying fin spacing and number of tube rows are tested under dry and wet conditions. The thermal fluid measurements are made using a psychometric calorimeter. Frontal air velocity varies in the range from 0.7 m/s to 1.5 m/s. Using the experimental data, presented are the heat transfer coefficients in terms of Colburn j-factor and friction factor.

2열 절개형 핀-관 열교환기의 공기측 유동 및 열전달 특성 (Air-side flow and heat transfer for a two-row lanced finned tube heat exchanger)

  • 배진효;이재헌
    • 대한기계학회논문집B
    • /
    • 제22권1호
    • /
    • pp.79-92
    • /
    • 1998
  • A numerical study has been performed to obtain the air-side flow and heat transfer characteristics for a two-row lanced finned tube heat exchanger with 7 mm tube outer diameter. The increases of dimensionless local heat flux at the leading edge of slit and bottom surface of the fin were noticed. The temperature of air at downstream of the 2nd row of the lanced fin becomes more uniform than that of the plain fin because the mixing of energy increases by the slit and the side-slit. As the inlet velocity increases, the contribution of the 1st row to heat transfer decreases and that of 2nd row increases.

An Experimental Study of the Airside Performance of Slit Fin-and-Tube Heat Exchangers under Dry and Wet Conditions

  • Chang, Keun-Sun;Long, Phan-Than
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제17권1호
    • /
    • pp.7-14
    • /
    • 2009
  • Water condensate accumulated on the surface of a fin-and-tube heat exchanger significantly affects its thermal and hydraulic performances. The purpose of this study is to investigate the effects of condensate retention on the air-side heat transfer performance and flow friction for various flow and geometric conditions. Total of twelve samples of slit and plate fin-and-tube heat exchangers are tested under dry and wet conditions. The thermal fluid measurements are made using a psychrometric calorimeter. Frontal air velocity varies in the range from 0.7 m/s to 1.5 m/s. Using the experimental data, presented are heat transfer coefficients in terms of Colburn j-factors and friction factors, and these data are compared with the existing correlations.