시스 순환전류 저감장치의 과도특성 및 보호방식에 관한 연구 (A Study on the Transient Characteristic and Protection Schemes of Sheath Circulating Current Reduction Equipment)

  • 강지원;한용희;정채균;이종범
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권7호
    • /
    • pp.421-428
    • /
    • 2003
  • After the cable is installed, many geometric factors, such as bowing types of the cable and the length difference of the cable between each minor section will cause the impedance unbalance between cables. The impedance unbalance will increase or decrease the sheath circulating currents, which are critical to human safety and sustaining the capabilities of electric power. Accordingly, in this paper, a new method is also proposed to reduce the sheath circulating currents and an reduction equipment according to the theory of the new method is developed. The reduction equipment is tested when the cable is on service. The test results show that it can reduce the sheath circulating currents by up to 97.8[%]. This confirms the validation of the new method and the reduction equipment, and assures the safe operation of the transmission cables. In order to illustrate the safe operation of the cable with new current reduction equipment at transient state due to lightning and single line-to-ground fault, extensive simulations have been made. Then the protection scheme of sheath circulating currents reduction equipment is proposed by adopting the new device of RDP(Reduction Device Protector).