• Title/Summary/Keyword: Simplified synthetic testing facility

Search Result 5, Processing Time 0.026 seconds

A Study on A Gas Circuit Breaker Development Using Simplified Synthetic Testing Facility (간이합성시험설비를 이용한 가스차단기 개발에 관한 연구)

  • Chong, Jin-Kyo;Kim, Gyu-Tak
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.902-904
    • /
    • 2007
  • A $SF_6$ gas circuit breakers are widely used for short circuit current interruption in EHV or UHV power system. During a $SF_6$ gas circuit breaker development, Simplified synthetic testing facility is used. This paper shows how simplified synthetic testing facility is used for a SF6 gas circuit breaker development.

  • PDF

Simplified Synthetic Testing Facility with Modified TRV Circuit

  • Chong, Jin-Kyo;Lee, Kyung Seob;Lee, Chang-Hoon;Kim, Gyu-Tak
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.2
    • /
    • pp.881-885
    • /
    • 2018
  • In order to develop a gas circuit breaker (GCB), the breaking performance of the short line fault (SLF) should be prioritized over that of the breaker terminal fault (BTF). In brief, it is necessary to evaluate the thermal characteristics of the insulating gas that is filled in a GCB. In the process of developing a GCB, many companies use the simplified synthetic testing facility (SSTF).In order to evaluate the SLF breaking performance of a GCB with a long minimum arcing time, a modifications to the conventional SSTF was proposed. In this study, we developed the SSTF with a modified transient recovery voltage circuit. The performance of the newly developed SSTF was verified by an $L_{90}$ breaking performance test on a rating combination of 170 kV, 50 kA, and 60 Hz.

HY Simplified Synthetic Test Facility (한양대학교 간이차단 합성시험설비구축)

  • Chang, Yong-Moo;Hwang, Ryul;Kim, Cheol-Ho;Lee, Bang-Wook;Koo, Ja-Yoon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.220-220
    • /
    • 2009
  • We are developing of the evaluation technique and system for testing the performance of circuit breaker using Simplified Synthetic circuit. This facility specification is up to 90[kApeak] and up to 300[kVpeak]. It is possible to verify the interrupting capability by using low-energy and reduce the development period and the cost.

  • PDF

A Study On The Arc Resistance of $SF_6$ Gas Circuit Breaker ($SF_6$ 가스차단기의 아크저항에 관한 연구)

  • Chong, Jin-Kyo;Lee, Woo-Young;Kim, Gyu-Tak
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.9
    • /
    • pp.1566-1570
    • /
    • 2007
  • [ $SF_6$ ] gas circuit breakers are widely used for short circuit current interruption in EHV(Extra High Voltage) or UHV(Ultra High Voltage) power systems. To develop $SF_6$ gas circuit breakers, the arc resistance value is necessary to compare experimental results to numerical ones. The arc resistance value can be obtained from a breaking test with a $SF_6$ gas circuit breaker. The direct testing or synthetic testing facility is widely used to verify the breaking ability for $SF_6$ gas circuit breakers. We employed the simplified synthetic testing facility to test a $SF_6$ gas circuit breaker prototype. The arc resistance characteristic was measured and calculated under the various experimental conditions. This arc resistance value can be used for verifying the numerical results from arc simulation in a circuit breakers.

Interrupting Performance of 7.2kV $SF_6$ Gas Electromagnetic Contactor Using Rotary Arc Principle (7.2kV급 로타리아크 소호방식을 이용한 $SF_6$가스 전자접촉기의 차단특성)

  • Chang, K.C.;Chong, J.K.;Shin, Y.J.;Kim, J.K.;Kim, G.S.
    • Proceedings of the KIEE Conference
    • /
    • 1996.07a
    • /
    • pp.77-79
    • /
    • 1996
  • The model interrupters of $SF_6$ gas electromagnetic contactor whose ratings are 7.2kV, 4.0kA have been designed and manufactured on the basis of theoretical and computational analysis for its development. The eddy current analysis, the magnetic field analysis and the calculation of the rotational force on arcs have been conducted using FLUX2D package. The short circuit current interrupting tests have been conducted for the model interrupters using the simplified synthetic testing facility in KERI. The results show that the model interrupters have sufficient interrupting capability and the new design concept is prefer for good interrupting performance.

  • PDF