• Title/Summary/Keyword: Shorted turn

Search Result 38, Processing Time 0.025 seconds

A Study of Shorted-Turn Detection in the Cylindrical Synchronous Generator Rotor Windings via Discrete Wavelet Transform (이산 웨이브렛 변환을 이용한 동기발전기 회전자 층간단락 진단에 관한 연구)

  • Kim, Y.J.;Kim, J.M.
    • Proceedings of the KIPE Conference
    • /
    • 2005.07a
    • /
    • pp.476-478
    • /
    • 2005
  • This paper describes a method for the detection of shorted-turn in the cylindrical synchronous generator rotor windings based on the discrete wavelet transform. Multi-resolution analysis(MRA) based on discrete wavelet transform provides a set of decomposed signals in independent frequency bands. In the proposed method, shorted-turn detection in rotor windings is based on the decomposition of the rotor currents, where wavelet coefficients of these signals have been extracted. Comparing these extracted coefficients is used for diagnosing the healthy machine from faulty machine. Experimental results show the effectiveness of the proposed method for shorted-turn detection in the cylindrical synchronous generator rotor windings.

  • PDF

Study of Shorted-turn for Cylindrical Synchronous Generator Rotor (원통형 동기발전기 회전자의 층간단락에 관한 연구)

  • Kim, Young-Jun;Kim, Jang-Mok;Lee, Sang-Hyuk;Ahn, Jin-Woo
    • Journal of the Korean Society of Safety
    • /
    • v.21 no.2 s.74
    • /
    • pp.52-56
    • /
    • 2006
  • This paper describes the methods for the detection of shorted-turn in the rotor of a cylindrical synchronous generator. A search coil is installed in the air-gap to detect the shorted-turn. The occurrence of a fault in the rotor winding results in a decrease of the induced voltages in the stator. And the magnitude of the rotor flux can be estimated by using the search coil and the estimated stator voltages respectively. And the magnitude of the estimated rotor flux is used for discriminating the rotor windings short or not by detecting the magnitude of the rotor flux. The method using a search coil located in the air-gap can detect not only the occurrence of a turn fault but also its position in the rotor winding. But the method using the estimated stator voltages gives the magnitude of the rotor flux, and only the number of a short-turn.

A Study of Shorted-Turn Detection in the Cylindrical Synchronous Generator Rotor Windings via Discrete Wavelet Transform (이산 웨이브렛 변환을 이용한 동기발전기 회전자 층간단락 진단에 관한 연구)

  • Kim, Jang-Mok;Kim, Young-Jun;Ahan, Jin-Woo;Kim, Heung-Geun;Jung, Tae-Uk
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.11 no.6
    • /
    • pp.570-576
    • /
    • 2006
  • This paper describes a method for the detection of shorted-turn in the cylindrical synchronous generator rotor windings based on the discrete wavelet transform. Multi-resolution analysis(MRA) based on discrete wavelet transform provides a set of decomposed signals in independent frequency bands, which contain independent dynamic information due to the orthogonality of wavelet function. In the proposed method, shorted-turn detection in rotor windings is based on the decomposition of the rotor currents, where wavelet coefficients of these signals have been extracted. Comparing these extracted coefficients is used for diagnosing the healthy machine from faulty machine. Experimental results are presented for healthy, and machines with 25%, 42%, 67%, 83%, 99% inter-turn short circuits in a rotor slot. Deviation of wavelet coefficients in healthy mode from faulty modes depicts the inverse proportion of shorted-turns. Experimental results show the effectiveness of the proposed method for shorted-turn detection in the cylindrical synchronous generator rotor windings.

Development of Shorted-Tun Diagnosis System for Generator Rotor (발전기 회전자 층간단락 진단시스템 국산화 개발)

  • Lee, Young-Jun;Ju, Young-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1942-1944
    • /
    • 2000
  • On-line diagnosis system has been developed and is now applied the detection of shorted-turn in the field winding of large generator. This system consists of data aquisition system and display PC. The data aquisition system detects voltage waveform from flux probe sensor installed in the stator slot. The display PC shows the shorted-turn situation of generator rotor winding.

  • PDF

On-Line Detection of Shorted Turn in Generator Rotor Windings (발전기 회전자 권선의 운전중 층간단락 탐지)

  • Kim, Hui-Dong;Lee, Yeong-Jun;Park, Jong-Jeong;Ju, Yeong-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.3
    • /
    • pp.192-199
    • /
    • 1999
  • During start up and shut down, the generator is rotating at a low speed and copper dusts cause arcing between the turns in the slot. Shorted turns occurred primarily by the movement of these copper dusts between individual windings in the generator rotor. Detection of shorted turns was performed in five gas turbine generators in two combined cycle power plants. Two types of permanent and temporary flux probes were used in this paper. These flux probes have been used to develop a methodology for detecting shorted turns in an operating generator's rotor. The flux probes sense the rotor winding slot leakage flux and produce a voltage proportional to the rate of change of the flux. This pattern of flux variation is the signature unique to each rotor winding. An appropriate waveform analysis technique canidentify the pole location, the slot number, and the number of shorted turns within each slot. Shorted turns in field winding of gas turbine generator(125.7 MVA) were detected to twelve turns on al total 190 turns.

  • PDF

Development of Shorted-Turn Sensor for Generator Rotor Windings (발전기 회전자 턴단락 센서 국산화 개발에 관한 연구)

  • Lee, Young-Jun
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.2050-2051
    • /
    • 2007
  • As a fundamental investigation to develop a sensor which is able to detect shorted turn phenomenon of generator rotor, we have experimented with self-made sensor using flux generator and high-resolution oscilloscope. We have recorded sensor-induced voltage according to the different condition, such as variations of turn, diameter and length of sensor. Based on the acquired data, we analyzed and simulated under similar circumstances of actual spot to maximize reliability. We have a plan to invest more resources to supply power plants with the developed sensor for ourselves.

  • PDF

Diagnosis Method and Characteristic Analysis of Shorted Turns on Generator Rotor using Flux Sensorless (자속센서리스 회전자 층간단락 진단기법 및 특성해석)

  • Kim Sun-Ja;Jeon Ywun-Seok;Lee Seung-Hak;Jeong Byung-Hwan;Lee Myung-Un;Choe Gyu-Ha
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.10 no.3
    • /
    • pp.257-263
    • /
    • 2005
  • Short-circuit rotor windings on a generator causes unstable oscillation of unbalance of flux, asymmetrical heat. In order to prevent serious accidents of short-circuit rotor windings, it is important to study the shorted-turn diagnosis method for rotor windings of the generator. To improve the defects of the diagnosis with sensors, the new sensorless method for rotor shorted-turn diagnosis is proposed, which is to measure the electrical values of the voltage and current at the generator and then to detect if the shorted-turned phenomena would occurred. For the feasibility of the suggested method the theoretical results are shown in the aspects of the air-gap flux density, the flux leakage, the generated output voltage and the shorted field current through the digital simulation. Also the possibility of decision for the suggested sensorless method could be shown in this paper.

Single-axis Flat Electro-Magnetic Actuator using Shorted Turn for Fast Initial Response (평판형 전자기 엑츄에이터의 초기응답속도 향상을 위한 쇼티트 턴에 관한 연구)

  • Hwang, Ki-Il;Kim, Jin-Ho
    • Journal of the Korean Magnetics Society
    • /
    • v.19 no.6
    • /
    • pp.222-226
    • /
    • 2009
  • This paper presents the new design of flat electromagnetic actuator. Novel shorted turn and copper center pole are placed into existent design in order to reduce the inductance of coil and accelerate the initial response. Finite element analysis using commercial electromagnetic solver “MAXWELL” is performed to simulate the improvement of dynamic characteristics such as fast initial response and so on.

Assessment of Insulation Condition in Operating Large Turbine Generator (운전중인 대형 터빈발전기에서 절연상태 평가)

  • 김희동
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.6
    • /
    • pp.324-329
    • /
    • 2004
  • Six stator slot couplers(SSC) and a flux probe sensor installed on the stator winding slots of large turbine generator. Assessment of insulation condition has been based upon the measurements of partial discharge(PD) of stator windings and shorted-turn of rotor windings in operating large turbine generator. The maximum PD magnitude(Qm), normalized quantify number(NQN), PD pattern and shorted-turn were measured using on-line insulation condition monitoring system. The NQN and Qm of slot PD side in the phase A are indicated the highest value in six SSC sensors. Monitoring system results showed that discharge at conductor surface and internal discharge were detected at the surface of stator winding and in voids of the groundwall insulation. Insulation of stator and rotor windings in large turbine generator was judged to be in good condition.

Assessment of Insulation Condition for Generator Rotor Windings (발전기 회전자 권선의 건전성 평가)

  • Lee, Young-Jun;Ju, Young-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2006.07e
    • /
    • pp.59-60
    • /
    • 2006
  • A shorted-turn test was performed at the Pyungtaek combined cycle power plant on gas turbine generators. The test was conducted using a permanent flux probe and on-line shorted-turn diagnosis system. The permanent flux probe installed in the generator air gap senses the field winding slot leakage flux and produces a voltage proportional to the rate of change signature unique to each field winding. We have also applied a voltage waveform analysis technique that can identify the pole location, slot number and number of shorted-turn with each slot.

  • PDF