• 제목/요약/키워드: Sheath circulating current reduction equipment

검색결과 4건 처리시간 0.015초

지중송전계통에서 저감장치를 이용한 시스 순환전류 저감방안에 관한 연구 (A Study on the Reduction Methods of Sheath Circulating Current using the Reduction Equipment in Underground Transmission Systems)

  • 강지원;양해원
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권9호
    • /
    • pp.474-481
    • /
    • 2002
  • Sheath circulating current is increased in the change of sheath mutual impedance which is caused by unbalanced cable system, and different section length between joint boxes. If excessive current flows in sheath, sheath loss which is reduced the transmission capacity is produced. Recently, excessive sheath circulating current was partially measured in underground cable systems of KEPCO. Accordingly, actual schemes to reduce excessive sheath circulating current are urgently required for installed cable system as well as newly-installing cable systems. This paper describes the relation analysis of sheath circulating current and burying types. And also, various schemes to reduce excessive circulating current using EMTP/ATPDraw and applicable schemes are proposed through a detailed analysis regarding cable systems by considering various electrical and environmental factors. It is evaluated that the proposed reduction schemes can be effectively applied to reduce the excessive sheath circulating current with the minimized electrical problems. And reduction effect is Proved with sheath circulating current reduction equipment.

시스 순환전류 저감장치의 과도특성 및 보호방식에 관한 연구 (A Study on the Transient Characteristic and Protection Schemes of Sheath Circulating Current Reduction Equipment)

  • 강지원;한용희;정채균;이종범
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권7호
    • /
    • pp.421-428
    • /
    • 2003
  • After the cable is installed, many geometric factors, such as bowing types of the cable and the length difference of the cable between each minor section will cause the impedance unbalance between cables. The impedance unbalance will increase or decrease the sheath circulating currents, which are critical to human safety and sustaining the capabilities of electric power. Accordingly, in this paper, a new method is also proposed to reduce the sheath circulating currents and an reduction equipment according to the theory of the new method is developed. The reduction equipment is tested when the cable is on service. The test results show that it can reduce the sheath circulating currents by up to 97.8[%]. This confirms the validation of the new method and the reduction equipment, and assures the safe operation of the transmission cables. In order to illustrate the safe operation of the cable with new current reduction equipment at transient state due to lightning and single line-to-ground fault, extensive simulations have been made. Then the protection scheme of sheath circulating currents reduction equipment is proposed by adopting the new device of RDP(Reduction Device Protector).

시스순환전류 저감장치의 적정 설치위치 검토 (A Study on the Proper Installation Location of a Sheath Circulating Current Reduction Equipment)

  • 홍동석;장태인;강지원;이동일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.638-640
    • /
    • 2005
  • 본 논문에서는 지중 실계통에 저감장치의 설치 위치를 다양하게 변경시켰을 경우 시스 순환전류의 변화를 분석하였으며, 그 결과 보통접속함에 저감장치를 설치하였을 경우가 절연접속함에 설치했을 경우에 비해 적은 저감효과를 보임으로써 저감장치 적용지점 선정에 있어 보통접속함의 저감장치 취부를 가능한 자제할 것으로 권하고 있는 국내 기준(안)의 타당성을 확인하였다.

  • PDF

시스전류 저감장치 적용시 고장전류분류율 검토 및 대책 (A Study of Fault Current Distribution Ratio with a Reduction Equipment of Sheath Circulating Current)

  • 홍동석;장태인;강지원;김재승;윤형희;임헌의
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.503-505
    • /
    • 2003
  • 본 논문에서는 방전갭을 이용한 시스 순환 전류 저감장치 보호유닛을 제안하여 SVL형식의 저감장치 보호유닛과 뇌써지시 과도특성을 비교하였으며, 또한 시스 순환전류 저감장치 보호유닛 적용시의 고장전류분류율을 검토한 결과 모든 경우에 대하여 각 접지선의 고장전류분류율이 현행의 기준을 만족함으로써 시스 순환전류 저감장치 보호유닛을 적용한 저감장치의 현장적용 가능성을 제시하였다.

  • PDF