• 제목/요약/키워드: Sensible and latent energy recovery system

검색결과 10건 처리시간 0.027초

향온시설물에 대한 현열 및 잠열 에너지 회수시스템의 성능해석 (Performance Analysis of Sensible and Latent Energy Recovery System for Thermally Controlled Facilities)

  • 박병규;김무근;김근오
    • 설비공학논문집
    • /
    • 제12권12호
    • /
    • pp.1057-1065
    • /
    • 2000
  • A sizing of sensible and latent energy recovery system with condensing heat exchanger is important to the design of a thermally controlled facilities. The transient system simulation program TRNSYS 14.2/IISiBat has been used to evaluate the energy consumptions of a thermally controlled facilities which consist of boiler, chiller and condensing heat exchanger, The boiler and chiller are selected based on the annual peak loads and controlled to maintain the setting temperature of $14~17^{\circ}C$. Simulation shows that the amount of sensible and latent energy recovered by heat exchanger is almost 20% of total heating load.

  • PDF

Performance Analysis of Sensible and Latent Energy Recovery System for Thermally Controlled Facility

  • Park, Byung-Kyu;Kim, Moo-Geun;Kim, Geun-Oh
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제9권4호
    • /
    • pp.17-26
    • /
    • 2001
  • Simulation was conducted using TRNSYS to evaluate the thermal performance of a facility. This facility has a condensing-type heat exchanger which is able to recover the latent energy for the purpose of reducing the heating energy in winter. The boiler and chiller are selected based on the annual peak loads and controlled to maintain the facility at the set temperature of 14~$17^\circ{C}$. Supplied energy by the boiler and recovered energy by the heat exchanger were calculated as a function of number of pass through heat exchanger, kind of fuel and hot water velocity. Simulation results show that about 20% of the total heating load can be recovered by the heat exchanger and the amount of latent heat is increasing with the number of pass. This means that the efficiency of the waste energy recovery system can be increased by using a condensing-type heat exchanger rather than a traditional sensible heat exchanger.

  • PDF

실험을 통한 공동주택 환기시스템의 실제 운전 시 전열교환성능 검토 (An Evaluation on Energy Recovery Performance of the Ventilation System in Multi-Residential Building by Field Measurement)

  • 최연희;송두삼
    • 설비공학논문집
    • /
    • 제29권2호
    • /
    • pp.68-73
    • /
    • 2017
  • Recently, energy recovery ventilators (ERVs) have been installed for energy saving in many multi-residential buildings in Korea. The performance of the heat exchanger of an ERV is analyzed in this study under specific indoor and outdoor conditions in a test-cell measurement. However, the performance of the heat exchanger varies according to the indoor and outdoor condition. In this study, the performance of energy recovery of the ventilation system was therefore analyzed in actual weather conditions using field measurement. Experiments were conducted under winter conditions in a multi-residential building for 20 days. Based on the measurement results, the characteristics of sensible heat and latent heat exchange rates were analyzed.

배기열 회수용 종이 열교환기의 성능에 관한 연구 (A Study on the Performance of Paper Heat Exchanger for Exhaust Heat Recovery)

  • 유성연;정민호;최재호;권화길;이춘우;이기성
    • 유체기계공업학회:학술대회논문집
    • /
    • 유체기계공업학회 2003년도 유체기계 연구개발 발표회 논문집
    • /
    • pp.245-250
    • /
    • 2003
  • In order to control indoor air quality and save energy, it is needed to install a suitable ventilation system equipped with heat exchanger for heat recovery. The purpose of this research is to find the performance of paper heat exchanger for exhaust heat recovery, which exchanges latent heat as well as sensible heat. Experimental apparatus comprises heat exchanger model, constant temperature and humidity chamber, fan and measurement systems for temperature, pressure and flow rate. Thermal performance and pressure loss of the paper heat exchanger are measured and compared at various air velocities and outdoor conditions. Experimental results show that paper heat exchanger can recover $50{\sim}70%$ of the enthalpy difference between supply and exhaust air.

  • PDF

배기열 회수용 종이 열교환기의 성능에 영향을 미치는 인자에 관한 연구 (A Study on the Factors Affecting the Performance of Paper Heat Exchanger for Exhaust Heat Recovery)

  • 정민호;유성연
    • 설비공학논문집
    • /
    • 제17권10호
    • /
    • pp.956-964
    • /
    • 2005
  • In order to control indoor air quality and save energy, it is needed to install a suitable ventilation system equipped with heat exchanger for heat recovery The purpose of this research is to find the factors affecting the performance of paper heat exchanger for exhaust heat recovery, which can be applied directly to the conventional ventilation unit, air-purifier, and air-conditioning system. In this study, thermal performance and pressure loss of the paper heat exchanger are measured and compared at various operating conditions. The effectiveness of sensible, latent and total heat at the face velocity of 0.75 m/s are $77\%,\;47\%\;and\;57\%$ in the cooling condition and $77\%,\;59\%,\;and\;\%$ in the heating condition, respectively. The effectiveness for sensible heat is only affected by velocity. On the other hand, the effectiveness for latent heat is affected. by temperature and relative humidity.

배기열 회수용 종이 열교환기의 성능예측에 관한 연구 (A Study on the Performance Prediction of Paper Heat Exchanger for Exhaust Heat Recovery)

  • 유성연;김진혁;정민호;지명석
    • 설비공학논문집
    • /
    • 제20권6호
    • /
    • pp.372-380
    • /
    • 2008
  • In order to control indoor air quality and save energy, it is needed to install a suitable ventilation system equipped with heat exchanger for heat recovery. Paper heat exchanger can recover $50{\sim}70%$ of the enthalpy difference between supply and exhaust air. The purpose of this research is to obtain the experimental correlations for the friction factor, heat transfer coefficient, mass transfer coefficient and permeance of paper heat exchanger, which can be used to predict the performance of the paper heat exchanger. Pressure drops at various velocities, and sensible and latent heat transfer rates at various dry-bulb temperatures, relative humidities and specific humidities are measured to derive experimental correlations. The results of prediction using correlations show fairly good agreement with the experimental data obtained in the actual operating conditions.

고온 축열 시스템의 개발에 관한 연구 (A System Development of Thermal Energy Storage at High Temperatures)

  • 홍성안;박원훈;최형준
    • 태양에너지
    • /
    • 제8권1호
    • /
    • pp.13-21
    • /
    • 1988
  • Heat transfer phenomena in a high-temperature heat storage unit were investigated using molten salts. Carbonate salt, an equimolar mixture of $Li_2CO_3$ and $K_2CO_3$, which melts at $505^{\circ}C$ with a latent heat of 82 cal/g, was selected as the most promising latent heat storage material based on its low cost and excellent thermophysical properties at moderately high temperatures. It was also found that nitrate salts were good candidates of sensible heat storage materials. For the carbonate salt to be utilized commercially, however, several means of enhancing thermal recovery must be explored by promoting heat conduction through the solid salt formed during the heat discharge period. These would be achieved by the additions of aluminum screens and wool, and stainless fins. Finally, experimental results of moving boundary of phase change were well compared with predictied values obtained from the approximate solution.

  • PDF

배기열 회수용 종이 열교환기의 성능예측에 관한 연구 (A Study on the Performance Prediction of Paper Heat Exchanger for Exhaust Heat Recovery)

  • 유성연;김진혁
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.294-299
    • /
    • 2005
  • In order to control indoor air quality and save energy. it is needed to install a suitable ventilation system equipped with heat exchanger for heat recovery. Paper heat exchanger can recover $50{\sim}70$ of the enthalpy difference between supply and exhaust air. The purpose of this research is to obtain the experimental correlations for the friction factor, heat transfer coefficient, mass transfer coefficient and permeance of paper heat exchanger, which can be used for the performance prediction of the paper heat exchanger. Pressure drop at various velocities and heat transfer rate at various dry-bulb temperatures, relative humidities, and specific humidities are measured to make experimental correlations. The results of prediction using correlations show fairly good agreement with experimental data.

  • PDF

다단 물유동층 열교환기에 의한 보일러 배가스의 폐열 회수 성능에 관한 연구 (A Study on the Heat Recovery from Boiler Exhaust Gas with Multi-stage Water-fluidized-bed Heat Exchanger)

  • 김대기;박상일;김한덕
    • 대한기계학회논문집B
    • /
    • 제25권12호
    • /
    • pp.1776-1783
    • /
    • 2001
  • Heat recovery from boiler exhaust gas with multi-stage water-fluidized-bed heat exchanger is analyzed in this study. The recovered energy here is not only sensible heat but also latent heat contained in the exhaust gas. In this system direct contact heat transfer occurs while exhaust gas passes through water bed and the thermal energy recovered this way is again delivered to the water circulating through heat exchanging pipes within the bed. Thus the thermal energy of exhaust gas can be recovered as a clean hot water. A computer program developed in this study can predict the heat transfer performance of the system. The results of experiments performed in this study agree well with the calculated ones. The heat and mass transfer coefficients can be fecund through these experiments. The performance increases as the number of stage increases. However at large number of stages the increasing rate becomes very low.

이중관 재질에 따른 이중관형 열회수 환기장치의 열회수 특성 연구 (A study on the heat recovery Characteristics of double tube type heat recovery ventilation system by double pipe material)

  • 김은영;조진표
    • 한국산학기술학회논문지
    • /
    • 제18권4호
    • /
    • pp.21-26
    • /
    • 2017
  • 본 연구에서는 이중관형 열회수 환기장치의 제품 적용 가능성을 검토하기 위해 성능 시험을 수행하였으며 이중관의 내측관의 재질에 변경에 따른 검토를 하기 위해 종이관, 알루미늄관, 폴리머관을 제작하여 동일한 급/배기 풍량을 인가하여 측정하였다. 온도 교환 효율은 모든 경우에서 알루미늄관의 경우가 가장 큰 값을 나타냈으며 종이관과 폴리머관은 비슷한 결과를 보였다. 이는 내측관으로 사용된 재료의 열전도율과 두께의 차이 때문인 것으로 판단된다. 습도 교환 효율은 모든 경우에서 종이관의 경우가 가장 큰 값을 나타냈으며 알루미늄관과 폴리머관은 비슷한 결과를 보였다. 이는 종이 재질은 습도 교환이 가능하지만 알루미늄과 폴리머재질은 습도 교환이 불가능하기 때문인 것으로 판단된다. 습도 교환과 온도 교환의 두 값을 포함하는 전열 교환 효율은 종이관의 경우가 가장 큰 값을 나타냈으며 알루미늄관과 폴리머관은 비슷한 결과를 보였다. 에너지계수(COE)는 현열과 잠열교환이 동시에 일어나는 종이관의 경우 전열에너지계수 값을 현열교환만 일어나는 알루미늄관과 폴리머관은 현열에너지계수를 비교해 보면 종이관의 에너지계수가 가장 큰 값을 나타냄을 알 수 있었다. 본 연구를 통하여 이중관형 열회수 환기장치의 내부관 재질에 따른 성능을 비교 분석 하였으며 환기장치로 적용이 가능한 것을 알 수 있었다.