• Title/Summary/Keyword: Rolling Blackout

Search Result 4, Processing Time 0.016 seconds

Spectral Analysis of LFO Using Synchrophasor in KEPCO Systems (Synchrophasor를 이용한 한전계통의 저주파 진동 스펙트럴 해석)

  • Shim, Kwan-Shik;Choi, Jun-Ho;Kim, Sang-Tae
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.12
    • /
    • pp.63-73
    • /
    • 2013
  • The parameters of electromechanical modes offer considerable insight into the dynamic stability properties of a power system. This paper presents a results of a LFO(low-frequency oscillation) based on the time-synchronized signals measured by synchrophasor in the rolling blackout. Spectral analysis was performed, and critical parameters were estimated using the data acquired from synchrophasors installed in the KEPCO system. As significant modes, a 0.68 Hz oscillation mode that occurred prior to the forced load shedding in the rolling blackout was estimated. Such an oscillation mode can cause an uncontrollable blackout. Therefore, the system should be operated so that significant oscillation modes are not activated. This results can serve as a reference in the future for reliable system operation in the event of a similar blackout.

Electricity Pricing Policy Alternatives to Control Rapid Electrification in Korea

  • Kim, Changseob;Shin, Jungwoo
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.2
    • /
    • pp.285-299
    • /
    • 2016
  • Although South Korea experienced a rolling blackout in 2011, the possibility of a blackout in South Korea continues to increase due to rapid electrification. This study examines the problems of energy taxation and price distortions as possible reasons for the rapid electrification in South Korea, which is occurring at a faster rate than in Japan, Europe, and other developed countries. Further, we suggest new energy taxation and price systems designed to normalize electricity prices. In order to do so, we consider two possible scenarios: the first imposes a tax on bituminous coal for electricity generation and the second levies a tax to provide compensation for the potential damages from a nuclear accident. Based on these scenarios, we analyze the effects of a new energy system on electricity price and demand. The results show that a new energy system could guarantee the power generation costs and balance the relative prices between energy sources, and could also help prevent rapid electrification. Therefore, the suggested new energy system is expected to be utilized as a basis for energy policy to decrease the speed of electrification, thus preventing a blackout, and to induce the rational consumption of energy in South Korea.

Auxiliary Power Unit Control Algorithm for Input Voltage Disturbance Suppression (입력 급변 대응을 위한 철도 차량용 보조전원장치 외란 억제 알고리즘 구현)

  • Kim, Ji-Chan;Baek, Seoung-Gil;Cha, Hanju
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.12
    • /
    • pp.1810-1817
    • /
    • 2015
  • The railway vehicle has an auxiliary power unit for supplying power to the associated electronic control devices and passenger service unit. Typically, input voltage from the catenary for rolling stock is highly fluctuating according to the substation capacity, vehicle propulsion and regeneration. Especially, the frost and freezing on contact wire in winter can cause a blackout inside vehicle, and also brings about electronic components damaging and the system down. To prevent this problem, a large filter and capacitor is used. But this is not a perfect solution, because it is increasing weight of the unit. In this paper, a new algorithm is proposed to suppress the disturbance without adding devices. Simulation and experimental results show that the proposed algorithm has performance to suppress the disturbance at the sudden input voltage variations.

Real-time Optimal Operation Planning of Isolated Microgrid Considering SOC balance of ESS

  • Lee, Yoon Cheol;Shim, Ji Yeon;Kim, Jeongmin;Ryu, Kwang Ryel
    • Journal of the Korea Society of Computer and Information
    • /
    • v.23 no.10
    • /
    • pp.57-63
    • /
    • 2018
  • The operating system for an isolated microgrid, which is completely disconnected from the central power system, aims at preventing blackouts and minimizing power generation costs of diesel generators through efficient operation of the energy storage system (ESS) that stores energy produced by renewable energy generators and diesel generators. In this paper, we predict the amount of renewable energy generation using the weather forecast and build an optimal diesel power generation plan using a genetic algorithm. In order to avoid inefficiency due to inaccurate prediction of renewable energy generation, our search algorithm imposes penalty on candidate diesel power generation plans that fail to maintain the SOC (state of charge) of ESS at an appropriate level. Simulation experiments show that our optimization method for maintaining an appropriate SOC balance can prevent the blackout better when compared with the previous method.