• 제목/요약/키워드: Refrigeration Effect

검색결과 849건 처리시간 0.021초

에탄올을 첨가한 TMA 포접화합물의 냉각특성에 대한 연구 (The Study on Cooling Characterics of TMA Clathrate with Ethanol)

  • 김창오;김진흥;정낙규;김석현
    • 설비공학논문집
    • /
    • 제14권8호
    • /
    • pp.634-640
    • /
    • 2002
  • The purpose of this study is to investigate the propriety of TMA clathrate as a cold storage medium. Particularly, this is to examine the extent of subcooling improvement when the additives is added to the TMA clathrate, because water used for cold storage ma terial has low phase change temperature and subcooling. This study has been analyzed and compared pure water with TMA 30 wt% clathrate how phase change temperature, subcooling and specific heat in the various concentrations are changed. This results prove low phase change temperature and subcooling control effect when the ethanol is added to the TMA 30 wt% clathrate than the TMA 30 wt% clathrate. In addition, it results low specific heat when there is added to the TMA 30 wt% clathrate over 0.5 wt% ethanol in the cold heat source temperature under $-7^{\circ}C$. The other side, it results high specific heat when the ethanol is added in it at the cold heat source temperature under $-5^{\circ}C$. Therefore, it is found that the additive must be controlled by available solution limit and study for new additive must be lasted to know its effect.

저온축열용 포접화합물에 냉각특성에 관한 실험적 연구 (A study on cooling characteristics of clathrate compound for cold storage applications)

  • 한영옥;김진흥
    • 설비공학논문집
    • /
    • 제11권2호
    • /
    • pp.205-214
    • /
    • 1999
  • The objective of this paper is to investigate the thermal properties of TMA clathrate compound applicable to cold storage system for building air-conditioning. Especially, the test tube experiments are performed by comparing and analyzing the temperature of phase change, specific heat and subcooling characteristic according to the variation of density, temperature of heat source and charging quantity in TMA clathrate compound. The results are summarized as follows:1) $-15^{\circ}C$ is not proper as the temperature of heat source because the temperature of subcooling is above $8.3^{\circ}C$ 2) temperature of phase change is dropped as the temperature of heat source is lower, 3) the effect of subcooling suppression with about 8$^{\circ}C$ is confirmed when the temperature of heat source is $-10^{\circ}C$ in case of 26, 27, and 30wt%, while the temperature of subcooling is about $0^{\circ}C$ when the temperature of heat source is $-15^{\circ}C$ in case of 25, 26 and 30wt%. Thus, the effect of subcooling suppression is greater as the temperature of heat source is lower. Additionally, the concentrative study is needed on mass concentration causing the phase change without subcooling phenomenon when the temperature of heat source is $-15^{\circ}C$. Thus, it is concluded that TMA clathrate compound has enough thermal properties as the cold storage medium for building air-conditioning.

  • PDF

저온축열용 포접화합물의 열물성에 관한 실험적 연구 (An Experimental Study on Thermal Properties of Clathrate for Cold Storage Applications)

  • 한영옥;정낙규;김진흥
    • 설비공학논문집
    • /
    • 제12권8호
    • /
    • pp.725-734
    • /
    • 2000
  • The objective of this paper is to investigate the thermal properties of TMA clathrate applicable to cold storage system for building air-conditioning. Especially, the test tube experiments are peformed by comparing and analyzing the temperature of phase change, specific heat and subcooling characteristic according to the variation of concentrations and temperature of heat source in TMA clathrate. The results are summarized as follows; 1) temperature of phase change is dropped as the temperature of heat source is lower, 2) the effect of subcooling suppression with about $9.3^{\circ}C$ is confirmed when the temperature of heat source is $-10^{\circ}C$ in case of 30wt%, while the temperature of subcooling is about $0^{\circ}C$ when the temperature of heat source is $-15^{\circ}C$ in case of 25, 29wt% and 30wt% . Thus, the effect of subcooling suppression is greater as the temperature of heat source is lower. Additionally, the concentrative study is needed on mass concentration causing the phase change without subcooling phenomenon when the temperature of heat source is $-15^{\circ}C$ Thus, it is concluded that TMA clathrate has proper properties as the cold storage medium for building air-conditioning.

  • PDF

충돌분류계(衝突噴流系)에서 난류촉진체(亂流促進體)에 의한 방열효과(放熱效果)에 관(關)한 연구(硏究) (An Experimental Study on the Cooling Effect by a Turbulence Promoter in Impinging Air Jet System)

  • 이용화;서정윤
    • 설비공학논문집
    • /
    • 제4권1호
    • /
    • pp.48-56
    • /
    • 1992
  • The purpose of this study was to investigate the enhancement of heat transfer without additional external power in the case of rectangular air jet impinging vertically on the flat heating surface. In an attempt to enhance the heat transfer rate in two-dimensional impinging jet, the technique used in the present study was placement of square rod bundles as a turbluence promoter in front of the heat transfer surface. The effects of the clearance between the flat plate and square rod, and the nozzle exit velocity on the heat transfer characteristics have been investigated experimentally. The results obtained through this study were summerized as follows. High heat transfer enhancement was achived by means of flow acceleration and thinning of boundary layer by inserting rods in front of the heating flat plate. The smaller the clearance between rod and heating plate was, the larger heat transfer effect became. Average Nusselt number reached maximum at $Re=5.76{\times}10^4$ and C=1㎜ and the enhancement rate of heat transfer became maxium at this condition with the enhancement ratio as high as about 1.427 when normalized by the flat plate value. The correlating equation of average Nusselt number and Reynolds number was obtained, which is $\bar{N}uo=1.324{\cdot}Re^{0.459}{\cdot}(C/A)^{-0.034}$.

  • PDF

공동주택 지하주차장의 자연환기성능 향상방안에 관한 연구 (A Strategies to Improve the Natural Ventilation Performance at Underground Parking Lot in Multi-Residential Buildings)

  • 서정민;이중훈;송종의;정정화;송두삼
    • 설비공학논문집
    • /
    • 제23권2호
    • /
    • pp.153-163
    • /
    • 2011
  • Energy efficiency and indoor air quality have become main issue to develop healthy and sustainable building in these days. As an effort to reduce the energy consumption in multi-residential building, many attempts as like passive design strategies and renewable energy as well as active control method are tried. However, underground parking lot in multi-residential building seldom adopt the sustainable strategies and only mechanical system is installed as usual. Moreover, the mechanical system installed in underground parking lot is rarely operated due to the electric demand for operation after completion. In this study, as an energy efficient measure, natural ventilation system using stack effect as a driving force for underground parking lot will be proposed and the performance of the suggested system will be analyzed by simulation method.

순간냉각식 정수기 냉수조의 설계변수에 따른 성능 특성에 관한 해석적 연구 (Analytical Study on the Performance Characteristics of an Instant Cooling Type Water Purifier with the Design Parameters of the Cooling Tank)

  • 전용석;박홍희;이주성;김용찬
    • 설비공학논문집
    • /
    • 제24권7호
    • /
    • pp.545-552
    • /
    • 2012
  • The objective of this study is to analyze the effect on the energy consumption of an instant cooling type water purifier by the design parameters of the cooling tank. Initially, the simulation program was developed and verified. The simulation results showed that the energy consumption was reduced by replacing the shape of the cooling tank from a rectangular to a cube, increasing the evaporator length, decreasing the volume of the cooling tank, and increasing the performance of the insulator. The order of the effect magnitude on the energy consumption was as follows; volume of the cooling tank, conductivity and thickness of the insulator, shape of the cooling tank, length of the evaporator, and length of the water tube.

바닥공조시스템에서 복사온도가 열적 쾌적성에 미치는 영향 (Effect of Radiative Mean Temperature on Thermal Comfort of Underfloor Air Distribution System)

  • 정재동;홍희기;유호선
    • 설비공학논문집
    • /
    • 제20권11호
    • /
    • pp.711-717
    • /
    • 2008
  • Despite the fact that UFAD(Under Floor Air Distribution) systems have many benefits and are being applied in the field in increasing numbers, there is a strong need for an improved fundamental understanding of several key performance features of these systems. This study numerically investigates the effect of supplied air temperature and supplied flow rate on the performance of UFAD, especially focused on thermal comfort. Also this study has compared UFAD with conventional overhead air distribution system. In contrast to the well-mixed room air conditions of the conventional overheat system, UFAD system produces an overall floor-to-ceiling airflow pattern that takes advantage of the natural buoyancy produced by heat sources in the occupied zone and more efficiently removes heat loads and contaminants from the space. Thermal comfort parameters were evaluated by CFD approach and then PMV was computed to detect the occupants' thermal sensation. Results show that radiative mean temperature plays crucial role on the evaluating PMV. Until now, the radiative temperature has been the missing link between CFD and thermal comfort, but the present study paves the way for overcoming this weakness.

헤더-채널 분기관에서의 헤더 입구 형상이 2상 유동 분배에 미치는 영향에 대한 실험적 연구 (Effect of Inlet Geometries on the Two-Phase Flow Distribution at Header-Channel Junction)

  • 이준경
    • 설비공학논문집
    • /
    • 제25권6호
    • /
    • pp.324-330
    • /
    • 2013
  • The main objective of this work is to experimentally investigate the effect of inlet geometries on the distribution of two-phase annular flow at header-channel junctions simulating the corresponding parts of compact heat exchangers. The cross-section of the header and the channels were fixed to $16mm{\times}16mm$ and $12mm{\times}1.8mm$, respectively. Experiments were performed for the mass flux and the mass quality ranges of $30{\sim}140kg/m^2s$ and 0.3~0.7, respectively. Air and water were used as the test fluids. Three different inlet geometries of the header were tested:no restriction (case A), a single 8 mm hole at the center (case B), and nine 2 mm holes around the center (case C) at the inlet, respectively. The tendencies of the two-phase flow distribution were different, in each case. For cases B and C (flow resistance exists), more uniform flow distribution results were seen, compared with case A(no flow resistance), due to the flow pattern change to mist flow from annular flow at the inlet, and the flow recirculation near the end plate of the header.

피치각과 날개 길이에 따른 축류팬의 성능 (Effect of Pitch Angle and Blade Length on an Axial Flow Fan Performance)

  • 전성택;조진표
    • 설비공학논문집
    • /
    • 제25권1호
    • /
    • pp.43-48
    • /
    • 2013
  • In this study, the performance of an impeller according to blade length and pitch angle was studied experimentally by building a variable pitch impeller while changing blade length to review the effect of blade length and pitch angle on a fan's performance. The pitch angle was changed in six steps from $20^{\circ}{\sim}45^{\circ}$ at intervals of $5^{\circ}$ while the blade lengths were changed to 90 mm, 100 mm, 110 mm and 120 mm with an identical airfoil shape while carrying out the experiment. The results are summarized as follows: The air flow per static pressure of axial fans increased linearly with increase of pitch angle, but the high static pressure showed a decrease at a pitch angle of $35^{\circ}$. The shaft power increased proportionally to the pitch angle at all blade lengths; the larger the pitch angle, the larger the measured increase of shaft power. This is because the drag at the fan's front increases with the pitch angle. In the axial fans considered in this research, the flow and increase of static pressure amount increased up to a pitch angle of $30^{\circ}$ but decreased rapidly above $35^{\circ}$.

외기 온도 변화가 핀-관 열교환기의 공기측 열전달계수와 마찰계수에 미치는 영향에 관한 실험적 연구 (An Experimental Study on the Effect of the Air Temperature on the Air-Side Heat-Transfer Coefficient and the Friction Factor of a Fin-and-Tube Heat Exchanger)

  • 김내현;조홍기
    • 설비공학논문집
    • /
    • 제29권4호
    • /
    • pp.149-158
    • /
    • 2017
  • In general, the air-side j and f factors of evaporators or condensers are obtained through single-design tests performed under air-dry and wet-bulb temperatures. Considering that the indoor or outdoor air temperatures vary significantly during the operation of an air conditioner, it is necessary to confirm that the experimentally-obtained j and f factors are widely applicable under variable air conditions. In this study, a series of tests were conducted on a two-row slit-finned heat exchanger to confirm the applicability. The results showed that, for the dry-surface condition, the changes of the tube-side water temperature, water-flow rate, and air temperature had virtually no effect on the air-side j and f factors. For the wet condition, however, the f factor was significantly affected by these changes; contrarily, the j factor is relatively independent regarding this change. The formulation of the possible reasoning is in consideration of the condensation behavior underneath the tube. The wet-surface j and f factors are larger than those of the dry surface, with a larger amount for the f factor.