• 제목/요약/키워드: Rated interrupting current

검색결과 3건 처리시간 0.017초

유효성분 동작형 누전차단기(Igc Free ELB)의 원리 및 동작 특성 해석 (Analysis of the Principle and Operation Characteristics of an (Igc-Free ELB) Operated by an Active Component)

  • 최충석
    • 전기학회논문지P
    • /
    • 제59권4호
    • /
    • pp.456-461
    • /
    • 2010
  • This study compares the criteria of earth leakage breakers (ELB) and analyzes the characteristics of an Igc-free ELB operated by an active component which is not misoperated by capacitive current. Even for the same ELB, the earth leakage current flowing through the human body is estimated to be differ greatly depending on the power source, voltage, location and status of contact, contact time duration, etc. Earth leakage breakers are classified based on the rated voltage, rated sensing current, rated operating time etc. Mounting and demounting of the existing equipment can be performed easily since an $I_{gc}$-free ELB is manufactured with the same structure as a conventional ELB. The rated operating current of a conventional and an $I_{gc}$-free ELB is 30mA, the sensing current is 25mA and the rated non-operating current is 15mA. In the analysis of non-operating current characteristics, the rated non-operating current of 15mA was satisfied up to a 20mA charging current in the conventional ELB, but does not satisfy the rated non-operating current as it operates when the resistive leakage current is lower than 15mA for a charging current exceeding 20mA. Also, the ELB is misoperated without a resistive leakage current when the charging current exceeded 25mA. However, the newly developed $I_{gc}$-free ELB satisfied the rated non-operating current even when the charging current was 60mA. Also, in comparison to the interrupting characteristics, it was confirmed that the charging current satisfying the rated non-operating current of the $I_{gc}$-free ELB was three times higher than that of the conventional ELB.

열팽창분사원리를 이용한 25,8kV급 가스차단기의 차단특성 (Interrupting Characteristics of 25.8kV Gas Circuit Breaker Using Thermal-Expansion Principle)

  • 장기찬;신영준;박경엽;정진교;김진기;김귀식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1994년도 하계학술대회 논문집 C
    • /
    • pp.1603-1605
    • /
    • 1994
  • Recently, Gas Circuit Breakers are rapidly replacing Vacuum Circuit Breakers in the medium voltage switchgear. This is due to the improved performance of - GCB in interrupting capability, price, weight, size etc., while the countermeasure to suppress the switching surges of VCB has not been satisfactory. Intensive research works on the GCB have been conducted in the world widely since 1980. Nowadays it is well known that the thermal expansion type GCB can provide- better performance than puffer type in the distribution power system. KERI has conducted researches in the GCB rated at 25.8kV 25kA with Jinkwang Co. using the thermal expantion principle since 1993. In this paper, the calculated results of electric and magnetic fields for the model GCB are presented and analyzed. The effect of permanent magnet used to improve the interruption capabilty at the low current level is also investigated. The design parameters for the interrupter inspected through the short-circuit tests conducted at high power laboratory of KERI.

  • PDF

모의송전계통에 차단기의 전류비율을 고려한 초전도 한류기 설치위치 분석 (Analysis on Installation Location of SFCL considering Current Rate of Circuit Breaker in a Power Transmission System)

  • 박한민;김진석;임성훈;김재철
    • 전기학회논문지
    • /
    • 제64권3호
    • /
    • pp.357-364
    • /
    • 2015
  • The power system configuration is changed to solve increasing power demand. This changes in power system configuration with mesh-, network grid generate the problem of fault current increase. Superconducting fault current limiter (SFCL) has been expected the one of the solutions to solve this problem. And there has already been reported much to the application and research of SFCL in the power distribution system. However, the application and research of SFCL are insufficient in a transmission power system. Also, the fault current limiting effect by the SFCL varies with installation location of SFCL. Therefore, this paper constructed the power transmission system through experiment and analyzed installation location method of SFCL using the current rate of each circuit breaker (CB) according to fault location.