• Title/Summary/Keyword: R410A

Search Result 305, Processing Time 0.026 seconds

Condensation heat transfer of R407C and R410A in a horizontal smooth tube (R407C 및 R410A의 수평원관내 응축열전달)

  • 서정현;김민수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.5
    • /
    • pp.633-641
    • /
    • 1999
  • Experiments were carried out to investigate the condensation heat transfer characteristics for R22 and its alternatives, R407C (R32/125/134a, 23/25/52wt%) and R410A (R32/125, 50/50wt%). A concentric tube heat exchanger was made to conduct condensation heat transfer tests. Mass flux and saturation temperature of refrigerants at the test section inlet were varied to get the corresponding heat transfer coefficients. Serial and parallel input of secondary fluid (water) were applied to the test subsections. Compared with existing correlations of condensation heat transfer, experimental heat transfer coefficients obtained in this study were generally higher than the predicted values, and mean absolute deviations from several correlations were shown. Wall subcooling was introduced to get a new correlation for condensation heat transfer coefficients by modifying Shah's equation. The RMS deviation of the measured heat transfer coefficients from the new correlation in this study for R22 is 9.9% and that for R407C and R410A are 10.2% and 14.6%, respectively.

  • PDF

An Experimental Study on Convective Boiling of R-22 and R-410A in Horizontal Smooth and Micro-fin Tubes

  • Kim, Yongchan;Seo, Kook-Jeong;Lee, Kyu-Jung;Park, Youn cheol
    • Journal of Mechanical Science and Technology
    • /
    • v.15 no.8
    • /
    • pp.1156-1164
    • /
    • 2001
  • Evaporation heat transfer coefficients and pressure drops were measured for smooth and micro-fin tubes with R-22 and R-410A. Heat transfer measurements were performed for 3.0m long horizontal tubes with nominal outside diameters of 9.52 and 7.0mm over an evaporating temperature range of -15 to 5$\^{C}$, a mass flux range of 68 to 211kg/㎡s, and a heat flux range of 5 to 15kW/㎡. It was observed that the heat transfer coefficient increased with mass flux. Evaporation heat transfer coefficients of R-22 and R-410A increased as the evaporating temperature dropped at a lower heat flux. Generally, R-420A showed the higher heat transfer coefficients than R-22 in the range of low mass flux, high heat flux and high evaporating temperature. Pressure drop increased with a decrease of evaporating temperature and a rise of mass flux. Pressure drop of R-22 was higher than that of R-410A at the same mass flux.

  • PDF

An experimental study on the performance of a window system air-conditioner using R407C and R410B (R407C 및 R410B 적용 창문형 에어컨의 성능에 관한 실험적 연구)

  • Kim, M.H.;Shin, J.S.;Kim, K.J.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.9 no.4
    • /
    • pp.536-544
    • /
    • 1997
  • This study presents test results of a residential window system air-conditioner using R22 and two potential alternative refrigerants, R407C and R410B. A series of performance tests was performed for the basic and liquid-suction heat exchange cycle in a psychrometric calorimeter test facility. For R407C, the same rotary compressor was used as in the R22 system. However, compressor for the R410B system was modified to provide the similar cooling capacity. The evaporator circuit was changed to get a counter-cross flow heat exchanger to take advantage of zeotropic mixture's temperature glide, and liquid-line suction-line heat exchange cycle was also considered to improve the performance of the system. Test results were compared to those for the basic R22 system.

  • PDF

R-22 and R-410A Condensation in Flat Aluminum Multi-Channel Tubes

  • Kim, Nae-Hyun;Min, Chang-Keun;Jung, Ho-Jong
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.11 no.3
    • /
    • pp.114-124
    • /
    • 2003
  • In this study, condensation heat transfer tests were conducted in flat aluminum multi-channel tubes using R-410A, and the results are compared with those of R-22. The flat tubes have two internal geometries; one with smooth inner surface and the other with micro-fins. Data are presented for the following range of variables; vapor Quality (0.1∼0.9), mass flux (200∼600 kg/$m^2$s) and heat flux (5∼15 kW/$m^2$). Results show that the effect of surface tension drainage on the fin surface is more pronounced for R-22 than R-410A. The smaller Weber number of R-22 may be responsible. For the smooth tube, the heat transfer coefficient of R-410A is slightly larger than that of R-22. For the micro-fin tube, however, the trend is reversed. Possible reason is provided considering physical properties of the refrigerants. For the smooth tube, Webb's correlation predicts the data reasonably well. For the micro-fin tube, the Yang and Webb model was modified to correlate the present data. The modified model adequately predicts the data.

Variations in the Thermal Performance of R22 and R410A Refrigeration Systems Depending on Operation Conditions

  • Jeong, Ji-Hwan;Kweon, Young-Chel;Chang, Keun-Sun
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.12 no.1
    • /
    • pp.10-20
    • /
    • 2004
  • Experiments have been conducted in order to make comparisons of characteristics of a R410a cycle with a R22 cycle in terms of cooling capacity and coefficient of performance (COP). The parameters examined in the present work include air flow rate, indoor and outdoor air temperatures, and indoor relative humidity. These two refrigeration cycles constructed for this study share all components except compressor, accumulator, oil separator, and piping. The measurements were made using a psychrometric calorimeter. The experimental results show that the R410A cycle has several advantages for indoor units while the R22 cycle yields better performance for outdoor units.

The Condensation Pressure Drop of R-22 and R-410A in Small Diameter Tube (세관내 R-22와 R-410A의 응축 압력강하)

  • Son, Chang-Hyo
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.19 no.2
    • /
    • pp.156-162
    • /
    • 2008
  • The condensation pressure drop for R-22 and R-410A flowing in a small diameter tube was investigated. The test section is a counterflow heat exchanger with refrigerant flowing in the inner tube and coolant flowing in the annulus. The test section consists of 1220 mm length with horizontal copper tube of 3.38 mm outer diameter and 1.77 mm inner diameter. The refrigerant mass fluxes ranged from 450 to $1050\;kg/m^2{\cdot}s$ and the average inlet and outlet qualities were 0.05 and 0.95, respectively. The main experimental results were summarized as follows : In the case of two-phase flow, the pressure drop increases with increasing mass flux and decreasing quality. The pressure drop of R-22 is slightly higher than that of R-410A for the same mass flux. Most of correlations proposed in the large diameter tube showed enormous deviations with experimental data.

Comparison of Performance Variation between R-22 and R-410A Refrigeration Systems (운전조건 변화에 따른 R-22 냉동사이클과 R-410A 냉동사이클의 성능변화 비교)

  • 박태준;이민규;정지환;장근선
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.3
    • /
    • pp.166-176
    • /
    • 2003
  • Experiments have been conducted in order to make comparisons of a alternative refrigerant (R-410A) cycle characteristic with an existing refrigerant (R-22) cycle characteristic in terms of cooling capacity and coefficient of performance (COP). The parameters examined in the present work include air flow rate, indoor/outdoor air temperatures, and indoor relative humidity. These two refrigeration cycles share all components except compressor, accumulator, oil separator, and piping connecting them. The measurements were made using an air-enthalpy calorimeter. The experimental results show that the R-410A cycle has many advantages over indoor conditions while the R-22 cycle has better performance over outdoor conditions.

Study on Evaporation Pressure Drop of R- l34a, R-407C, and R-410A in the Oblong Shell and Plate Heat Exchanger (오블롱 셀 플레이트 열교환기에서의 R-l34a, R-407C, R-410A의 증발 압력강하에 관한 실험적 연구)

  • 박재홍;김영수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.9
    • /
    • pp.855-862
    • /
    • 2004
  • This study reports pressure drops during evaporation for R-l34a, R-407C (a mixture of 23 wt% R-32, 25 wt% R-125, and 52 wt% R-l34A) and R-410A (a mixture of 50 wt% R-32 and 50 wt% R-125) in the oblong shell and Plate heat exchanger. The effects of the mass fluxes, heat fluxes, refrigerant saturation temperatures and vapor quality of refrigerants on the measured data were explored in detail. The present data showed that pressure drops of all refrigerants increase with the vapor quality. At a higher mass flux, pressure drops are higher for the entire range of the vapor quality A rise in the heat flux doesn't show significant effects on the pressure drops. Finally, at a higher saturation temperature the pressure drops are found to be lower. The pressure drops for R-407C were approximately 20% lower than those of R-l34a. R-410A had 33% lower pressure drops than R-l34a. Correlation is also provided for the measured pressure drops in terms of the friction factor.

The Condensation Heat Transfer of R-22 and R-410A in an Inner Diameter Tube of 1.77 mm (내경 1.77 mm관내 R-22와 R-410A의 응축열전달)

  • Son, Chang-Hyo;Roh, Geon-Sang
    • Journal of the Korean Institute of Gas
    • /
    • v.12 no.1
    • /
    • pp.48-53
    • /
    • 2008
  • The condensation heat transfer coefficients of R-22 and R-410A in a small diameter tube were investigated. The main components of the refrigerant loop consist of a receiver, a variable-speed pump, a mass flowmeter, an evaporator (preheater), and a condenser (test section). The test section consists of smooth, horizontal copper tube of 3.38 mm outer diameter and 1.77 mm inner diameter. The refrigerant mass fluxes varied from 450 to $1050\;kg/(m^2s)$ and the average inlet and outlet qualities were 0.05 and 0.95. The main results were summarized as follows : the condensation heat transfer coefficient also increases with increasing mass flux and quality. The condensation heat transfer coefficient of R-410A was slightly higher than that of R-22. Most of correlations proposed in the large diameter tube showed significant deviations with experimental data except for the ranges of low quality and low mass flux.

  • PDF

An experimental investigation of thermodynamic performance of R-22 alternative blends (R-22 대체용 혼합냉매의 열역학적 성능에 대한 실험연구)

  • Hwang, E.P.;Kim, C.N.;Park, Y.M.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.9 no.1
    • /
    • pp.82-91
    • /
    • 1997
  • R-410a and R-407c witch have the best potential among the substances being considered as R-22 alternatives were tested as "drop in" refrigerants against a set R-22 baseline tests for comparison. The performance evaluations were carried out in a psychrometric calorimeter test facility using the residential split-type air conditioner under the ARI rating conditions. Other than the use of different lubricant and a hand-operated expansion valve, one of the commercial systems was selected for the experiment. Performance characteristics were measured; compressor power, capacity, VCR, mass flow rate and COP. The tests showed that R-407c can be directly applied to the existing refrigeration system because of its similar vapor pressure and other thermopysical properties with those of R-22. However, it required change to the volume flow rate of compressor in order to achieve the similar performance with R-22 because of its relatively small VCR and capacity. Meanwhile, R-410a has too high a vapor pressure to be applied to the existing system and this feature results in relatively low COP of the system compared to that of R-22. But this could be improved by changing compressor design considering R-410a's relatively high VCR and capacity compared to those of R-22.

  • PDF