• 제목/요약/키워드: R-22, Small diameter

검색결과 47건 처리시간 0.024초

세관내 HCFC계 대체냉매의 압력강하에 관한 연구 (The Pressure Drop Characteristics in Small Diameter Tubes Using HCFC Alternative Refrigerants)

  • 손창효;이호림;정진호;최영석;오후규
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2000년도 춘계학술대회논문집B
    • /
    • pp.347-352
    • /
    • 2000
  • The pressure drop characteristics of R-22 and R-410A(a mixture of 50wt% R-32 and 50wt% R-125) flowing in a small diameter tube with 1.77[mm] inner diameter and 3.14[mm] outer diameter was investigated experimentally. the mass fluxes of refrigerants are ranged from 450 to $1050[kg/(m^2{\cdot}s)]$ and the qualites are varied from 0.05 to 0.95. The main experimental results were summarized as follows; The single-phase liquid friction factors for small diameter tubes are higher than those predicted by the Blasius equation. In case of two-phase flow, the pressure gradient of the small diameter tube increases with increasing mass velocity and vapor quality. The experimental data are not well correlated by predictions which were proposed for the large diameter tube.

  • PDF

소구경 원관내의 R-22 응축열전달에 대한 실험 (Experiments on R-22 condensation heat transfer in small diameter tubes)

  • 김내현;조진표;김정오;김만회;윤재호
    • 설비공학논문집
    • /
    • 제10권3호
    • /
    • pp.271-281
    • /
    • 1998
  • In this study, condensation heat transfer experiments were conducted with two small diameter(ø7.5, ø4.0) tubes. Comparison with existing in-tube condensation heat transfer correlations indicated that the correlations overpredict the present data. For example, Akers correlation overpredicts the data upto 104%. The condensation heat transfer coefficient of the ø4.0 I.D. tube was smaller than that of the ø7.5 I.D tube; at the mass velocity of 300kg/$m^2$s, the difference was 12%. The pressure drop data of the small diameter tubes ware highly(two to six times) overpredicted by the Lockhart-Martinelli correlation. Subcooled forced convection heat transfer test confirmed that Gnielinski's single phase heat transfer correlation predicted the data reasonably well.

  • PDF

내경 1.77 mm관내 R-22와 R-410A의 응축열전달 (The Condensation Heat Transfer of R-22 and R-410A in an Inner Diameter Tube of 1.77 mm)

  • 손창효;노건상
    • 한국가스학회지
    • /
    • 제12권1호
    • /
    • pp.48-53
    • /
    • 2008
  • 본 연구는 세관내 R-22와 R-410A의 응축 열전달 계수를 실험적으로 조사하였다. 냉매 순환루프의 주요 구성품은 수액기, 변속 액펌프, 질량유량계, 증발기(예열기), 응축기(시험부)로 구성된다. 시험부는 평활, 수평 동관으로 내관의 내경과 외경이 각각 1.77 mm와 3.38 mm이다. 냉매 질량유속은 $450{\sim}1050\;kg/(m^2s)$이고, 입출구 평균건도는 $0.05{\sim}0.095$이다. 주요 실험결과를 요약하면, 응축 열전달 계수는 질량유속과 건도이 증가할수록 증가하였고, R-410A의 응축 열전달 계수가 R-22에 비해 약간 높았다. 종래의 상관식과 비교한 결과, 저건도와 저질량유속을 제외하고는 실험값과 종래의 상관식으로 예측한 값의 차이가 큰 것으로 나타났다.

  • PDF

Experimental Investigation of R-22 Condensation in Tubes with Small Inner Diameter

  • Kim, Nae-Hyun;Cho, Jin-Pyo
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제7권
    • /
    • pp.45-54
    • /
    • 1999
  • In this study, condensation heat transfer experiments were conducted in two small diameter (ø17.5, ø4.0) tubes. Comparison with the existing in-tube condensation heat transfer correlations indicated that these correlations over predict the present data. For example, Akers correlation over predicted the data up to 104 %. The condensation heat transfer coefficient of the ø4.0 I.D. tube was smaller than that of the ø7.5 I.D tube; at the mass velocity of 300 kg/$m^2$s, the difference was 12 %. The pressure drop data of the small diameter tubes were highly (two to six times) over predicted by the Lockhart-Martinelli correlation. Sub-cooled forced convection heat transfer test confirmed that Gnielinski's single phase heat transfer correlation predicted the data reasonably well.

  • PDF

세관을 이용한 Tube-in-Tube 열교환기내 R-22, R-407C 및 R-410A 응축열전달 특성 (Condensation Heat Transfer Characteristics of Tube-in-Tube Heat Exchanger using Small Diameter Tubes with R-22, R-407C and R-410A)

  • 박우종;최광일;박기원;오종택
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.657-662
    • /
    • 2006
  • The present paper dealt with an experimental study of condensation heat transfer coefficients with refrigerant R-22, R-407C and R-410A, and was focused on pressure gradient and heat transfer coefficient in horizontal tube-in-tube heat exchangers using inner diameter of 4 mm, 3 mm and 2 mm in a 16.91 mm tube and length of 3,000 mm. Experiments were performed at inlet saturation temperature of 35 to $45^{\circ}C$ and mass flux ranges from 200 to $600 kg/m^2s$. The pressure gradient with inner tube diameter of 4.0 mm is higher 2.5 times than that of 8.0 mm. In tube-in-tube HEX, the pressure gradient of R-410A were lower than those of R-22 and R-407C. The condensation heat transfer coefficients increased with mass flux increase, but they decreased with saturation temperature increased. Condensation heat transfer coefficients of R-410A were a little higher than those of R-22 and R-407C. The condensation heat transfer coefficients of tube-in-tube HEX were about 40% higher than those of double tube HEX.

  • PDF

세관내 R-22 and R-134a의 증발 유동양식과 열전달 (The Evaporation Flow Patterns and Heat Transfers of R-22 and R-134a in Small Diameter Tubes)

  • 손창효
    • 한국수소및신에너지학회논문집
    • /
    • 제18권3호
    • /
    • pp.275-283
    • /
    • 2007
  • 본 논문은 세관(ID<7 mm) 내 R-22와 R-134a의 증발 열전달과 유동양식에 대한 실험적 연구이다. R-22와 R-134a의 유동양식을 관찰하기 위해 내경 2와 8 mm의 파이렉스 튜브를 사용하였고, 열전달 계수는 내경 1.77, 3.35, 5.35 mm의 수평 평활동관에 대해서 측정하였다. 증발 유동양식에서 내경 2 mm의 환상류 영역이 내경 8 mm에 비해 저건도 영역에서 발생하는 것을 확인할 수 있었고, 내경 2 mm의 유동양식은 Mandhane의 선도와 많은 오차를 보였다. 세관(ID<7 mm) 내 증발 열전달 계수는 종래의 대구경관(ID>7 mm)에 비해 관직경에 대한 영향이 많이 나타나는 것을 알 수 있었다. 내경 1.77 mm의 열전달 계수는 내경 3.36 mm와 5.35 mm에 비해서 20내지 30% 정도 높은 것을 나타났다. 또한 종래의 열전달 상관식(Shah's, Jung's, Kandlikar's and Oh-Katsuda's correlation)과 비교한 결과, 실험 데이터는 상관식과 많은 이탈 정도를 보였다. 따라서 실험데이타를 기초로 세관내 R-22와 R-134a에 적용할 수 있는 증발 열전달 상관식을 새로이 제안하였다.

극세관 헬리컬 코일 증발관내 R-22의 열전달 및 압력손실 특성 (Characteristics of Heat Transfer and Pressure Drop of R-22 Inside an Evaporating Tube with Small Diameter Helical Coil)

  • 김주원;김정훈;서석기;김정훈;김종수
    • 대한기계학회논문집B
    • /
    • 제24권5호
    • /
    • pp.699-708
    • /
    • 2000
  • To make compact evaporator, experiments that show characteristics of evaporating heat transfer and pressure drop in the helically coiled small diameter tube were taken in this research. The experiments were performed with HCFC-22 in the helically coiled small diameter tube; inner diameter=1.0(mm), tube length=2.0(m), and curvature diameter=31, 34, 46.2(mm). The experiments were also carried out with the following test conditions; saturation pressure=0.588(MPa), mass velocity=$150{\sim}500(kg/m^2s)$, and heat flux=$1{\sim}5(kW/m^2)$. The experiment results are that the empirical correlation to predict heat transfer coefficient for single phase flow in helically coiled small diameter tube was obtained. It was found that dry-out is occurred at low-quality region for evaporation heat transfer because of breaking of annular liquid film. The friction factor of single phase flow of helically coiled tube was agreed with Prandtl's correlation. Finally, It was proposed for correlation that can precisely predict the friction factor of two phase flow of helically coiled tube.

세관내 R-134a의 유동특성에 관한 실험적 연구 (An Experimental Study on Flow Characteristics of R134a in a Small Diameter Tube)

  • 손창효
    • 한국산학기술학회논문지
    • /
    • 제8권6호
    • /
    • pp.1307-1312
    • /
    • 2007
  • 본 논문은 세관내 R-134a의 유동특성을 실험적으로 조사한 것이다. 이에 대한 실험장치는 마그네틱 기어 펌프, 증발기, 수액기, 사이트 글라스, 응축기 계측기로 구성된다. 유동양식을 관찰하기 위한 사이트 글라스는 증발기 입출구에 설치하였다. 실험은 세관내 R-22와 R-134a의 유동특성을 살펴보기 위해서 수행되었다. 이에 대한 실험변수인 냉매질량 유속은 100에서 1000 $kg/m^2s$이고, 포화온도는 $30^{\circ}C$이다. 증발과정 중의 유동양식에서 2 mm의 세관내 환상유동은 8 mm관의 대구경관에 비해 저건도와 저질량유속에서 발생하였다. 본 실헐 결과와 종래의 유동양식 선도와 비교한 결과, 2 mm의 세관내 증발 유동양식은 Baker, Mandhane, Taitel-Dukler의 유동양식 선도와는 큰 차이를 보였지만, Dobson의 유동양식 선도와는 좋은 일치를 보였다.

  • PDF

세관 내 액단상 열전달 및 압력강하 특성에 관한 연구 (Study on the Single-Phase Heat Transfer and Pressure Drop Characteristics of R-718 in Small Diameter Tubes)

  • 홍진우;정재천;김종렬;노건상;구학근;오후규
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집D
    • /
    • pp.425-432
    • /
    • 2001
  • Single-phase heat transfer coefficients and pressure drops of R-22 were measured in smooth, horizontal copper tubes with inner diameters of 3.36 mm, 5.35 mm, 6.54 mm and 8.12 mm, respectively. The experiments were conducted in the closed loop, which was driven by a magnetic gear pump. Data are presented for the following range of variables: Reynolds from 1000 to 20000. Single-phase heat transfer coefficients increased by $10{\sim}30%$ as the inner diameter of tube was reduced and it was found that a well-known previous correlation, Gnielinski's correlation, was not suitable for the small diameter tubes. But the pressure drop in the small diameter tubes have been shown slightly deviations with Blauius' correlation. Based on an analogy between heat and mass transfer, the new heat transfer correlation is proposed to predict the experimental data successfully.

  • PDF