• Title/Summary/Keyword: R-123

Search Result 677, Processing Time 0.033 seconds

External Condensation Heat Transfer Coefficients of R245fa on Low Fin and Turbo-C Tubes (낮은 핀관과 Turbo-C 촉진관에서 R245fa의 외부 응축 열전달계수)

  • Shim, Yun-Bo;Park, Ki-Jung;Jung, Dong-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.3
    • /
    • pp.167-175
    • /
    • 2009
  • In this study, condensation heat transfer coefficients(HTCs) of R22, R123, R134a and R245fa are measured on both 26fpi low fin and Turbo-C tubes. All data are taken at the vapor temperature of $39^{\circ}C$ with a wall subcooling of $3{\sim}8^{\circ}C$. Test results show that HTCs of the newly developed low vapor pressure alternative refrigerant, R245fa, are $7.8{\sim}9.2%$ and $10.3{\sim}18.6%$ higher than those of R123 for 26fpi low fin tube and Turbo-C tube respectively. For all refrigerants tested, HTCs of Turbo-C enhanced tube are higher than those of 26fpi low fin tube. For the low fin tube, Beatty and Katz's prediction equation yielded 20% deviation for all fluids. The heat transfer enhancement ratio of R245fa on the Turbo-C tube is $5.9{\sim}6.4$ while that of R123 is $5.7{\sim}5.9$. From the view point of environmental safety and condensation heat transfer, R245fa is a long term candidate to replace R123 currently used in centrifugal chillers.

Design of an evaporator heat exchanger for R123 and R134a refrigerants (Rl23, R134a냉매 특성에 따른 증발기 설계)

  • 김익생
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.28 no.5
    • /
    • pp.368-374
    • /
    • 1999
  • 최근 세계적으로 환경보호에 대한 관심이 고조됨에 따라 기술개발 방향이 환경을 고려한 규정 및 장치에 제한을 받고 있다. 따라서 냉동 공조 기기에 사용되는 기존의 CFC계열 냉매가 오존층 파괴의 주 원임이 판명됨에 따라 환경 문제가 없는 HCFC계열인 R123와 HFC R134a로의 대체가 불가피하게 되었다.

  • PDF

Nucleate Pool Boiling of a Structured Enhanced Tube Used in a Flooded Refrigerant Evaporator

  • Kim, Nae-Hyun;Cho, Jin-Pyo;Choi, Kuk-Kwang
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.8 no.2
    • /
    • pp.23-28
    • /
    • 2000
  • In this study, pool boiling performance of a structured enhanced tube for a flooded refrigerant evaporator was experimentally investigated. Tests were performed for three different refrigerants(R-11, R-123, R-l34a). Compared with the heat transfer coefficients of the smooth tube, the heat transfer coefficients of the enhanced tube were 6.6 times larger for R-11, 6.0 times larger for R-123 and 3.5 times larger for R-l34a, which are comparable with the performance of foreign products. The heat transfer coefficients of R-l34a was higher than those of R-11 or R-123, both for the enhanced tube and for the smooth tube. At 4.4$^\circ$C saturation temperature, however, the heat transfer coefficients of R-l34a was approximately the same as those of R-11. The effect of the saturation pressure on the boiling performance was similar to that of the smooth tube-the heat transfer coefficient increased as the saturation pressure increased.

  • PDF

Pool boiling performance of an enhanced tube used in flooded refrigerant evaporator for turbo-refrigerator (터보냉동기용 만액식 증발기에 사용되는 성형가공관의 풀비등 성능)

  • 김태형;김내현
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.6
    • /
    • pp.808-814
    • /
    • 1999
  • Pool boiling performance of a metal-formed enhanced tube for a flooded refrigerant evaporator was experimentally investigated. Tests were performed for three different refrigerants(R-11, R-123, R-l34a), at two different saturation temperatures $4.4^{\circ}C \;and \;26.7^{\circ}C$ .Heat flux was varied from 10㎾/$m^2\;to\ 50㎾/$m^2$. Compared with the heat transfer coefficients of the smooth tube, the heat transfer coefficients of the enhanced tube were 6.6 times higher for R-11, 6.0 tines higher for R-123 and 3.5 times higher for R-l34a. The enhancements are comparable with those of foreign products. The heat transfer coefficients of R-l34a were higher than those of R-11 and R-123, either for the enhanced tube or for the smooth tube. At $4.4^{\circ}Csaturation temperature, however, the heat transfer coefficients of R-l34a were approximately the same as those of R-11, The effect of the saturation pressure on the boiling performance was similar to that of the smooth tube - the heat transfer coefficient increases as the saturation pressure increases.

  • PDF

Isolation and Characteristics of Endolichenic Fungi Producing Antifungal Compound (항진균성 물질을 생산하는 지의류 내생 곰팡이의 선별 및 특성)

  • Hwang, Hyun-Gook;Kim, Yi-Na;Baik, Keun-Sik;Choi, Sang-Ki
    • Korean Journal of Microbiology
    • /
    • v.47 no.1
    • /
    • pp.97-101
    • /
    • 2011
  • To isolate a novel antifungal compound, we obtained 107 kinds of endolichenic fungi from Lichen Bioresources Center and examined their antifungal capability. Two fungi EL123 and EL156 showed high antifungal activity against Candida albicans in both MYA and EMM media. Nucleotide sequence analysis and NCBI Blast analysis in ITS region including 5.8S rRNA revealed that EL123 has 95% homology with Thielavia microspora and EL156, 99% with Cryptosporiopsis diversispora which belong to Ascomycetes. It observed that EL156 formed a branched mycelium whereas EL123 formed a straight one. EL156 also produced the antifungal substance faster than EL123 when they grew on MY liquid medium.