Cool-down test of cryogenic cooling system for superconducting fault current limiter

  • Hong, Yong-Ju;In, Sehwan;Yeom, Han-Kil;Kim, Heesun;Kim, Hye-Rim
    • Progress in Superconductivity and Cryogenics
    • /
    • v.17 no.3
    • /
    • pp.57-61
    • /
    • 2015
  • A Superconducting Fault Current Limiter is an electric power device which limits the fault current immediately in a power grid. The SFCL must be cooled to below the critical temperature of high temperature superconductor modules. In general, they are submerged in sub-cooled liquid nitrogen for their stable thermal characteristics. To cool and maintain the target temperature and pressure of the sub-cooled liquid nitrogen, the cryogenic cooling system should be designed well with a cryocooler and coolant circulation devices. The pressure of the cryostat for the SFCL should be pressurized to suppress the generation of nitrogen bubbles in quench mode of the SFCL. In this study, we tested the performance of the cooling system for the prototype 154 kV SFCL, which consist of a Stirling cryocooler, a subcooling cryostat, a pressure builder and a main cryostat for the SFCL module, to verify the design of the cooling system and the electric performance of the SFCL. The normal operation condition of the main cryostat is 71 K and 500 kPa. This paper presents tests results of the overall cooling system.

Operational characteristics analysis of protective relay for utility application of HTS power cable (초전도 전력케이블의 계통 적용을 위한 보호계전기의 동작특성 분석)

  • Kim, Jae-Ho;Kim, Jin-Geun;Sim, Ki-Deok;Cho, Jeon-Wook;Yoon, Jae-Young;Lee, Seung-Ryul;Park, Min-Won;Yu, In-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.57-58
    • /
    • 2008
  • Recently, several kinds of superconductivity applications are implemented and evaluated in the utility power networks. The protection system for HTS(High Temperature Superconducting) power devices safe operation has not been established yet. For the protection of the HTS apparatus, a better understanding of the quench properties against fault current and appropriate protection devices are required. In this study, an algorithm of protection system is developed with respect to HTS power cable. The protection system of HTS power cable was analyzed in the simulated power system. Results obtained from simulation will provide much more decisive data in order to design a certain superconducting power device, and can give a good information for the installation in power system.

  • PDF

Component Modeling of Micro SMES Based Design of Stabilizer Simulation for Power Supply using PSCAD/EMTDC (Micro SMES를 이용한 전원공급 안정화장치 시뮬레이션을 위한 PSCAD/EMTDC 컴포넌트 모델링)

  • Kim, Bong-Tae;Park, Min-Won;Seong, Ki-Chul;Yu, In-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2002.04a
    • /
    • pp.228-230
    • /
    • 2002
  • Recently, electric power reliability of our country has been improved. However, there are still remaining problems which are short-duration variations like instantaneous and momentary interruption and voltage sag by nature calamity ; typhoon, lightning, snow, etc. Besides, power quality ; harmonics, caused by using power electronics equipments, become a hot issue Malfunction of controller and stop machinery, and losing the important data are caused by poor power quality at a couple of second. Due to those, UPS, which is made up battery, has being used, but there are several disadvantages ; long charge and discharge time, environmental problem by acid and heavy metal, and short life time. As generally know, micro-SMES is a method to settle those mentioned. However, there need huge system apparatuses in order to verify the effect of system efficiency and stability considering the size of micro-SMES, the sort of converter type, and various conditions ; inner temperature, magnetic field, quench characteristic of micro-SMES, and etc. In this paper, in order to bring the mentioned above to a settlement, a micro-SMES is modeled with characteristics of micro-SMES is interfaced to EMTOC program using Fortran program interface method. We obtained hopeful answers and made the simulation model of micro SMES.

  • PDF

Electromagnetic characteristics of superconducting fault current limiters under the quenching (박막형 초전도 한류기의 퀜치상태의 전자기 특성)

  • Choi, H.S.;Chung, H.S.;Choi, C.J.;Lee, S.I.;Chung, S.B.;Oh, K.G.;Lim, S.H.;Han, B.S.;Chung, D.C.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.415-417
    • /
    • 2003
  • we analyzed the electromagnetic behavior of a superconducting fault current limiter (SFCL) under the quench state using FEM. The analysis model used in this work is 5.5 KVA meander-line type SFCLs. Meshes of 3,650 triangular elements were used in the analysis of this SFCL. Analysis results showed that the distribution of current density was concentrated to inner curved line in meander-line type-SFCL and the maximum current density was 14.61 $A/m^2$ and also the maximum Joule heat was 2,030 $W/m^2$ in this region. We think that the new and the modified structure must be considered for an uniform distribution of the electromagnetic field.

  • PDF

Hall voltage measurement with respect to internal layout of REBCO coated conductors in an external magnetic field

  • Kim, Young Gon;Baek, Geonwoo;Han, Seunghak;Choi, Yojong;Kim, Junseong;Jeon, Haeryong;Ko, Tae Kuk
    • Progress in Superconductivity and Cryogenics
    • /
    • v.21 no.4
    • /
    • pp.48-52
    • /
    • 2019
  • Recently, many studies have been reported on the magnetoresistance and Hall effect of REBCO thin films and bulk. The voltage interferes quench detection of high-temperature superconducting magnet and generates leakage current in no insulation high-temperature superconducting coil. Therefore, in this paper, experiments on magnetoresistance and Hall effect of commercial YBCO and GdBCO tapes have been carried out. As a result, anomalous voltages expected for the magnetoresistance and Hall effect of REBCO tapes were observed and analyzed. In addition, the voltage characteristics of REBCO have been identified, and the Hall coefficient are calculated for use in high magnetic field magnet applications.

Analysis on the Improvement of Power Capacity Increase in the Transformer-Type SFCL with Neutral Lines (중성선을 갖는 변압기형 초전도 한류기의 용량증대 개선 연구)

  • Cho, Yong-Sun;Choi, Hyo-Sang;Kim, Deog-Goo;Go, Sung-Pil
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.7
    • /
    • pp.1438-1443
    • /
    • 2011
  • The increase of power capacity in the superconducting fault current limiter (SFCL) is essential for application into the power grid. To achieve this, when superconducting units were connected in series and parallel, the unbalanced quenching characteristics between superconducting units generated by different critical current behavior should be improved. In the transformer-type SFCL, the superconducting units connected in series could be simultaneously quenched by the connection of neutral lines between secondary coils and superconducting units. From this the consumed power in superconducting units was equally distributed. In addition, the more the turn ratio of the transformer was reduced, the more consumed power in the superconducting units was reduced by the decrease of the induction voltage generated in the superconducting units. From those results, the transformer-type SFCL using neutral lines could increase the power capacity of the SFCL by the equal power division into the superconducting units.

A study on the SMES component modeling using PSCAD/EMTDC (PSCAD/EMTDC를 이용한 SMES Component modeling에 관한 연구)

  • Kim, Jin-Gun;Kim, Jae-Ho;Jung, Hee-Yeol;Park, Min-Won;Yu, In-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1998-1999
    • /
    • 2007
  • Before applying the HTS(High Temperature Superconductor) power devices to a real utility network, system analysis should be carried out by some simulation tools. PSCAD/EMTDC simulation tool is one of the most popularized useful analysis tools for electrical power system. Unfortunately the model component for HTS coil is not provided in PSCAD/EMTDC simulation tool. In this paper, EMTDC model component for HTS coil has been developed considering real characteristics of HTS coil like critical current, temperature and magnetic field. The developed model component of HTS coil could be used for power system application. Using the developed model component for HTS coil, we can easily do the simulation of HTS power devices application test in utility with the various inductance, quench current, inner magnetic field, and temperature values, for instances; SMES(Superconducting Magnetic Energy Storage) system, superconducting motor, transformer, and FCL(Fault Current Limiter)

  • PDF

Electrical insulating design of 600kJ conduction cooled HTS SMES

  • Choi, Jae-Hyeong;Kwag, Dong-Soon;Cheon, Hyeon-Gweon;Min, Chi-Hyun;Kim, Hae-Jong;Seong, Ki-Chul;Kim, Sang-Hyun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.9 no.2
    • /
    • pp.27-30
    • /
    • 2007
  • The electrical insulation design and withstanding test of mini-model coils for 600 kJ class conduction cooled high temperature superconducting magnetic energy storage (HTS SMES) have been studied in this paper. The high voltage is generated to both ends of magnet of HTS SMES by quench or energy discharge. Therefore, the insulation design of the high voltage needs for commercialization, stability, reliability and so on. In this study, we analyzed the insulation composition of a HTS SMES, and investigated about the insulation characteristics of the materials such as Kapton, AIN and vacuum in cryogenic temperature. Base on these results, the insulation design for 600 kJ conduction cooled HTS SMES was performed. The mini-model was manufactured by the insulation design, and the insulation test was carried out using the mini-model.

Analysis on the dielectric characteristics of a composite insulation system composed of LN2 and GN2

  • Kim, Junil;Lee, Onyou;Mo, Young Kyu;Bang, Seungmin;Kang, Jong O;Lee, Hongseok;Nam, Seokho;Kang, Hyoungku
    • Progress in Superconductivity and Cryogenics
    • /
    • v.17 no.3
    • /
    • pp.33-36
    • /
    • 2015
  • A liquid nitrogen ($LN_2$) is usually used to be a coolant and insulant for a HTS coil system. HTS wires for a superconducting apparatus may be surrounded by gaseous nitrogen ($GN_2$) due to film boiling generated by a quench or voids occurred by electrical breakdown. The increased maximum electric field intensity at $GN_2$ may result in the degradation of dielectric strength of a HTS coil system. In this paper, a study on the dielectric characteristics of a composite insulation system composed of $LN_2$ and $GN_2$ is performed. A sphere-to-plane electrode system made with stainless steel is used to perform the experiments under AC and lightning impulse voltage condition. A sphere electrode is surrounded by $GN_2$ and a plane electrode is immersed into $LN_2$ to conduct dielectric experiments with a composite insulation system. The dielectric experiments are performed according to the level of $LN_2$ from the plane electrode to a sphere electrode. It is found that the dielectric characteristics of a composite insulation system are dependent on the level of $LN_2$ and the field utilization factor of an electrode system.

Current Limiting Characteristics due to Application Location of a Superconducting Fault Current Limiter in a Simulated Power Distribution System (모의배전계통에 초전도한류기의 도입위치에 따른 전류제한 특성)

  • You, Il-Kyoung;Kim, Jin-Seok;Kim, Myoung-Hoo;Kim, Jae-Chul;Lim, Sung-Hun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.12
    • /
    • pp.90-95
    • /
    • 2009
  • The application of a large power transformer into a power distribution system was inevitable due to the increase of power demand and distributed generation. However, the decrease of the power transformer‘s impedance causes the short-circuit current of the power distribution system to increase and thus, the higher short-circuit current exceeds the cut-off ratings of the protective devices such as a circuit breaker. To solve these problems, several countermeasures have been proposed to protect the power system effectively from the higher fault current and the superconducting fault current limiter (SFCL) has been expected to be the promising countermeasure. However, the current limiting effect of SFCL including its bus voltage drop compensation depends on SFCL's application location in a distributed power system. In this paper, the current limiting and the bus-voltage drop compensating characteristics of the SFCL applied into a power distribution system were studied. In addition, the quench and the recovery characteristics of the SFCLs in each location of the power distribution system were compared each other.