• 제목/요약/키워드: Pumping station

검색결과 133건 처리시간 0.136초

도시 소유역 배수펌프장 운영개선 방안 연구 (2) - 침수범람모의에 의한 침수방지 방안 비교 연구 (Operational Improvement of Small Urban Storm Water Pumping Station (2) - Comparative Study to Reduce the Flooding Problems using Flood Simulation Model)

  • 길경익;한종옥;김구현
    • 한국물환경학회지
    • /
    • 제22권1호
    • /
    • pp.110-115
    • /
    • 2006
  • Flooding situation of Sutak basin was simulated and simulation seemed to be consistent with the real flooding situation in terms of high water levels and timings of flooding. The flood simulation model was used to evaluate alternatives to mitigate flooding problems in Sutak basin. From the evaluation of flood mitigation plans, it was found that combined operation of Sutak and Inchang pumping stations through partial diversion of inflow of Sutak pumping station to Inchang pumping station was the most effective one among the suggested mitigation plans. About 500 meter diversion channel will be needed to send 30% of Sutak pumping station inflow to Inchang pumping station. This will reduce overload of Sutak pumping station and the storage capacity of Inchang pumping station will be more efficiently utilized.

펌프제어밸브를 사용한 취수펌프장에서의 수격현상 (Waterhammer for the Intake Pumping Station with the Pump Control Valve)

  • 김경엽;오상현
    • 한국유체기계학회 논문집
    • /
    • 제4권4호
    • /
    • pp.16-21
    • /
    • 2001
  • The field tests on the waterhammer were carried out for PalDang intake pumping station of the metropolitan water supply 5th stage project. The pumping station was equipped with the pump control valve as the main surge suppression device and the surge relief valve as auxiliary. However, the pump control valve had not been early controlled in the planned closing mode, and the slamming occurred to the valve which abruptly closed during the large reverse flow. Because the pressure wave caused by the pump failure was superposed on the slam surge, the upsurge increased so extremely that the shaft of the valve was damaged. It was desirable that the surge relief valve was installed in the pumping station or near the pump exit for the delay of response. After reforming the oil dashpot of the pump control valve, the sliming disappeared and the measured pressure was in fairly good agreement with the results of simulation. In case of three pumps for ${\phi}2,600$ pipeline being simultaneously tripped, the pressure head in the pumping station increased to 95.6 m, and the upsurge caused by the emergency stop of four pumps for ${\phi}2,800$ pipeline was 89.6m. We concluded that the pumping station acquired the safety and reliability for the pressure surge.

  • PDF

과도수리현상 해석과 실증을 통한 펌프장 안정성 확보방안 (A Safety Plan for the Pumping Station by Hydraulic Transient Analysis and Demonstration)

  • 라병필;김진만;이동근;박종호;김경엽
    • 한국유체기계학회 논문집
    • /
    • 제8권5호
    • /
    • pp.22-28
    • /
    • 2005
  • As the water supply facilities are recently getting larger, the domestic waterworks become multi-regional water supply system. Large water supply facilities generally consist of the intake pumping station, water treatment plant and water supply/distribution facilities. Although the pumping stations and the pipeline systems are used to pump up water, it often happens pipeline damage and flooding accident by the water hammer. In this paper, the intake pumping station is guaranteed by both the computer simulation and the field test analysis. This study is contributed to the safe operation program for the pumping station in which results of the adjustment on the safety plan of the pumping station, the air valve and the valve closing time.

갈신양수장 관개지구의 관개효율과 관개패턴분석 (Analysis of Irrigation Efficiency and Pattern in Galshin Pumping District)

  • 류범희;박승기
    • 농촌계획
    • /
    • 제26권3호
    • /
    • pp.91-102
    • /
    • 2020
  • The purpose of study was analyze the pumping characteristics, Irrigation Efficiency(IE), and irrigation pattern by period of rice growing stage with based on the performance of design irrigation water requirement and operational Galshin Pumping(GP) station in GP irrigation district constructed under rural water development project master plan. GP station was located in Yedang reservoir, Yesan-gun, Chungcheongnam-do and has been supplying irrigation water since 2006. The research data are the Irrigation Water Requirement(IWR) and the Pumping Water Amount(PWA) from 2006 to 2015 at the GP station, which is the supplied amount. The IWR were calculated using the Blaney-Criddle formula of the HOMWRS program, Hydrological Operation Model for Water Resource System, developed by Korea Rural Community Corporation. The Blaney-Criddle formula was used to calculate design irrigation water requirement of Galshin rural water development project master plan. During 2006-2015, the study period, the annual average IWR is 763.2(±149.1)mm, the annual PWA of the GP station is 397.4mm to 1,056.9mm, and those average annual PWA is 643.4(±208.4)mm. The annual IE of GP station 96.5% to 169.0%, and the average annual IE is 124.3%, which is higher than the research results conducted in other pumping stations. Analyzing the irrigation patterns of the GP irrigation district, the IWR Ratio per 10days(IWRR) and the PWA Ratio per 10days(PWAR) of the G P station were obtained. The IWRR is the percentage of IWR for each 10 days of a month to total IWR per year, and the PWAR is the percentage of PWA for each 10 days of a month to total PWA per year. The Kolmogorov- Smirnov(K-S) test results of IWRR and PWAR showed the characteristics classification by rice growing stage and stable normal distribution characteristics. Average IWRR(AIWRR) and Average PWAR(APWAR) are presented as irrigation patterns. Irrigation pattern analysis will be able to standardize comparison, analysis and probability calculation of the pumping station characteristics of different pumping stations and apply to objective evaluation of the pumping station district.

과도수리현상 해석과 실증을 통한 펌프장 안정성 확보방안 (The Plan of Safety for Pump Station through Hydraulic Transient Analysis & Demonstration)

  • 라병필;김진만;박종호;김경엽
    • 유체기계공업학회:학술대회논문집
    • /
    • 유체기계공업학회 2004년도 유체기계 연구개발 발표회 논문집
    • /
    • pp.199-207
    • /
    • 2004
  • Water supply facilities are recently getting larger according as domestic waterworks become multi regional water supply system. Large water supply facilities generally consist of the intake pumping station, water treatment station and water supply & distribution facilities. Although pumping stations and pipeline systems are used to pump up water, it often happens pipeline damage and flooding accident by the water hammer. As a result of this study, a pumping station is guaranteed by the computer simulation and field test analysis. Therefore these are contributed safety operation in pumping station through adjustment of the pumping station safety plan, air valve and valve closing time.

  • PDF

한전 배전선로 주변에 위치한 J가압장의 피뢰설비 구축방안 검토 (To examine the construction plan of the lightening rod equipment for the J-booster pumping station in and around KEPCO'a high voltage distribution power line)

  • 홍성택;이은춘;신강욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.293-295
    • /
    • 2003
  • KEPCO's high voltage distribution power line laid under the ground near to the J-booster pumping station that supply water for living. Lightening rod equipment does not installed at the J-booster pumping station because KEPCO's over head ground wire for protection functions as a lightening rod equipment. In this study, it is concerned whether KEPCO's over head ground wire for protect the distribution power line affect to the J-booster pumping station which is installed for reduce the damage from the direct and indirect lightening. If KEPCO's protection area does not affect to the J-pumping station, it is plan to examine the construction method of lightening rod protection angle and lightening rod equipment and to suggest the optimum protection plan using the surrounding structure based on the suitability of protection area.

  • PDF

팔당 취수펌프장의 수격현상에 관한 수치해석적 연구 (Numerical Study on the Waterhammer of PalDang Intake Pumping Station)

  • 김경엽;유택인
    • 한국유체기계학회 논문집
    • /
    • 제3권4호
    • /
    • pp.52-58
    • /
    • 2000
  • The numerical study on the waterhammer was carried out for the intake pumping station of the metropolitan water supply 6th stage project. Because the waterhammer problems as a result of the pump power failure were the most important, these situations were carefully investigated. The surge tank and the stand pipes effectively protected the tunnels md the downstream region of pipeline from the pressure surge. In case the moment of inertia of the pump and motor was above $5080\;kg{\cdot}m^2$, the column separation did not occur in the pipeline between the pumping station and the inlet of 1st tunnel. As the moment of inertia increased, the pressure surges decreased in the pipeline conveying raw water. The pump control valve was chosen as the main surge suppression device for the intake pumping station. After power failure, the valve disc should be rapidly closed in 2.5 seconds and controlled the final closure to 15 seconds by the oil dashpot. If the slamming happened to the pump control valve, there was some danger of this system damaging. As the reverse flow through the valve increased, the upsurge extremely increased.

  • PDF

소프트웨어 개발 방법론에 따른 양배수장 디지털 트윈 시스템 개발과정 고찰 (Exploration of Water Pumping Station Digital Twin System Development Process According to Software Development Methodologies)

  • 이병준;김난영;윤성수
    • 한국농공학회논문집
    • /
    • 제66권3호
    • /
    • pp.53-62
    • /
    • 2024
  • The purpose of this study is to examine the methodology for applying digital twin technology to pumping station, identify the factors to be determined at each stage, and present its applicability. When analyzing the requirements for developing a digital twin for pumping station, they were categorized into service requirements, IoT device requirements, and gateway requirements, with a total of 39 requirements established. In system design, it was structured according to the principles of modularity, abstraction, stepwise decomposition, and information hiding, allowing the implementation of planned items for diagnosis and operational management. There are difficulties in setting communication-related protocols and applying them in the field due to the complexity of overseeing the entire system with data. Therefore, it is necessary to clarify the purpose of the system, and there are challenges in identifying the characteristics of individual facilities, such as pumps in pumping station, and fully incorporating them into the system process. Thus, the framework of the initial design is crucial for implementing a digital twin.

양수장의 농업용수 공급량 및 수질 모니터링 (Monitoring of Irrigation Water Supply and Water Quality from a Pumping Station)

  • 최진규;손재권;구자웅;윤광식;김영주
    • 한국관개배수논문집
    • /
    • 제7권1호
    • /
    • pp.19-26
    • /
    • 2000
  • The irrigation water supply and water quality from a pumping station were surveyed. Guiseok pumping station was selected as a monitoring site. Water level in irrigation canal was monitored continuously and water samples were taken and analyzed, periodical

  • PDF

Flowra를 이용한 P신도시 지역난방 주 배관망 및 펌프장 예비 설계 및 경제성 검토 (PRELIMINARY DESIGN AND ECONOMICS CONSIDERATION OF P-NEW-CITY DISTRICT HEATING MAIN PIPES AND PUMPIG STATION)

  • 김진권
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2010년 춘계학술대회논문집
    • /
    • pp.127-128
    • /
    • 2010
  • As P-new-city is planned and constructed, district eating utilizing an existing near-by power plant's waste heat is considered as an economic and environment friendly way of providing heating to the new city. Many pipeline diameters and pumping station location and capacity were assumed, investigated and optimized, to satisfy the customers' heat demand considering common district heating pipe-network design and construction practice, and also and construction, pumping station land price and construction and the pumping energy cost during lifetime of DH systems.

  • PDF