서지보호기의 상태 감시를 위한 MOV의 고장률 예측 (Failure Rate Estimation of MOV for Condition Monitoring of Surge Protective Devices)

  • 김동진;김영선;박재준;이기식
    • 전기학회논문지
    • /
    • 제62권9호
    • /
    • pp.1302-1307
    • /
    • 2013
  • MOV(Metal Oxide Varistor) is the most important part of SPD(Surge Protective Device) which can protect electric facilities from an impulse current such as a lightning. So far, the fault of MOVs have decided only by surge count without considering magnitude of surge current and an amount of input energy. This paper proposed the fault prediction algorithm for the MOV using look up table made by surge count and input current data which have non-linear characteristics for input current and are estimated by high voltage experimental results. Proposed algorithm was proved by experiment on verification at a high voltage laboratory.

전력계통에 초전도한류기 적용시 차단용량 확보를 위한 초전도한류기 적용방안 연구 (Analysis on the Application Capacity of the Superconducting Fault Current Limiter considering Reclosing and Fault Current)

  • 김진석;임성훈;김재철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.592-593
    • /
    • 2015
  • Recently, the fault current has increased to exceed the rated breaking capacity of protective device due to the growth of the power demand on the power system where is changed into the loop-, mesh-, network grid. To limit fault current, the superconducting fault current limiter (SFCL) is announced with various methods. In many researches, the current limiting effect with the SFCL has been analyzed considering the rated breaking capacity of the CB with one fault condition. However, the power system has various short circuit and operation conditions. In order to select the capacity of the SFCL with reclosing operation and burden of the fault current on the protective device, the characteristics of the power system were investigated. Through the analysis, the evaluation method of the current rate was improved.

  • PDF

전력계통에서의 과전류계전기 보호협조에 관한 연구 (A Study on the Overcurrent Relay Coordination in Power Systems)

  • 최홍규;김경철;오정석;김병철
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 학술대회 논문집
    • /
    • pp.351-358
    • /
    • 2004
  • When fault occur in power systems, the protective relay plays a roles of protecting power system according to its setting values. There, it is very important that the protective relay have high selectivity performance in power system by correct setting the relays. This paper analyzed protect device protect cooperation or Transient stability and apply to Overcurrent relay in the real power system operation environment by using EDSA Program.

  • PDF

채혈바늘에 의한 2차 감염 방지기능을 갖는 랜싯과 전동식 채혈기의 개발 (Development of the Electric Lancing Device and the Lancet to Prevent the Secondary Contamination by Needlestick Injury)

  • 홍성철;장석진;강신한
    • 한국산학기술학회논문지
    • /
    • 제12권12호
    • /
    • pp.5464-5468
    • /
    • 2011
  • 본 연구는 채혈바늘에 의해 발생하는 2차 감염을 방지하기 위한 안전 랜싯(Lancet)을 설계 개발하고, 연속하여 채혈하는 경우에 쉽게 그리고 편리하게 사용할 수 있도록 무선 전동방식 채혈기의 설계 제작을 목적으로 한다. 안전랜싯은 채혈침과 보호캡이 일체형으로 설계되어 채혈 순간을 제외하고는 채혈침이 항상 보호캡 속에 있도록 하여 채혈바늘에 의한 사고를 방지하도록 하였다. 전동 채혈기는 충전건전지를 전원으로 하고 솔레노이드의 작동으로 랜싯을 타격하여 채혈하도록 설계되었으며, 연발타격 또는 단발타격의 기능을 선택하도록 설계 제작되었다. 또한 타격봉에 의한 충격력과 사용된 배터리의 수명 등이 측정되었다. 이 채혈기는 한방병의원의 사혈기로도 사용되도록 제작되었다.

비접지 DC 급전계통에서 전류형 지락보호계전기의 사용 (New Ground Fault Protective Relay in DC Traction Power System)

  • 정상기;백남욱;김연수;이성혁;이한민
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2004년도 춘계학술대회 논문집
    • /
    • pp.1297-1302
    • /
    • 2004
  • In DC power distribution system for urban rail transits potential relay, 64P, is used to detect the ground faults. The problem with this 64P is that though it detects the ground fault it cannot identify the faulted region. Therefore the faulted region cannot be isolated properly. It could results in power loss of the trains on the healthy regions and the safety of the passengers in the trains could be affected adversely. A new ground fault protective relaying scheme that can identify the faulted region is presented in this paper. The new concept uses the current differential scheme and the permissive scheme to identify the faulted region correctly. A device with similar characteristic to the arrestor is adapted to use the current relay for the ground fault detection. The role of the device is to block the ground leakage current in normal operating condition and enable the ground fault current to flow in ground fault condition. The algorithm of the new relay and the effect of the newly adapted device in the new relaying scheme are discussed.

  • PDF

저압용 서지 보호 장치(SPD)의 보호 거리 해석 (Analysis of the Protective Distance of Low-Voltage Surge Protective Device(SPD) to Equipment)

  • 이정우;오용택
    • 조명전기설비학회논문지
    • /
    • 제26권4호
    • /
    • pp.28-34
    • /
    • 2012
  • Installing surge protection devices for a low-voltage system is important to ensure the survival of electric or electronic devices and systems. If surge protection devices (SPD) are installed without consideration of the concept of lightning protection zones, the equipment to be protected might be damaged despite the correct energy coordination of SPDs. This damage is induced by the reflection phenomena on the cable connecting an external SPD and the load protected. These reflection phenomena depend on the characteristics of the output of the external SPD, the input of the loads, and the cables between the load and the external SPD. Therefore, the SPD has an effective protection distance under the condition of the specific load and the specific voltage protection level of SPD. In this paper, PSCAD/EMTDC software is used to simulate the residual voltage characteristics of SPD Entering the low-voltage device. And by applying a certain voltage level, the effective protection distances of SPD were analyzed according to the each load and length of connecting cable, and the effectiveness of SPD were verified.

바리스터와 LC필터를 사용한 2단 서지보호장치 (Two-Stage Surge Protection Device with Varistor and LC Filter.)

  • 이복희;김지훈;이경옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 추계학술대회 논문집 학회본부
    • /
    • pp.279-281
    • /
    • 1996
  • This paper deals with the two stage surge protection device by using varistor and LC low pass filter. Recently varistor alone has been used with overvoltage protection devices for the AC power mains and has same problems associated with high remnant voltage and noise. In this work, in order to improve the cutoff performance of surge protection device, the lightning surge protection device having two stage hybrid circuit for an AC single phase mains was designed and fabricated. Operation characteristics and surge clamping performance of the surge protection device in an $8/20{\mu}s$ surge current are investigated. As a consequence, it is found that the proposed two stage surge protective device for AC power mains has a variety of advantages such as a smaller clamping voltage, high frequency noise reduction and large clamping capacity.

  • PDF

선화아연바리스터 기반의 1-포트 서지보호장치의 최적 설계 기법 (Optimal Design Method of 1-Port Surge Protective Device Based on Zinc Oxide Varistor)

  • 정태훈;김용성;박근보;이승일
    • 한국산학기술학회논문지
    • /
    • 제19권4호
    • /
    • pp.93-102
    • /
    • 2018
  • 본 논문은 뇌격전류에 따른 저압 배전계통의 전자식 전력량계 및 배전 패널의 통신설비와 전원장치를 보호할 목적으로 사용하는 서지보호장치(SPD)에 관한 것이다. 서지보호장치(SPD)는 접속방식에 따라 1-포트 서지보호장치(SPD)와 감결합 요소를 포함한 2-포트 서지보호장치(SPD)로 구분된다. 뇌격전류에 대한 내부 시스템의 보호는 협조된 서지 보호체계를 이루는 계통적인 접근이 필요하다. 이에 대응하기 위해 이론적인 검토를 통해 피뢰구역(LPZ) 정의에 대한 고찰 및 해석을 진행하였다. 뇌서지에 의한 뇌격전류는 상당히 크기 때문에 하나의 서지보호장치(SPD)로 방호하기에는 한계가 발생하며, 이를 해결하기 위해 다단의 종속적으로 서지보호장치(SPD)를 설치하게 된다. 본 논문에서는 전력계통에 있어 한전계통에 연계되는 Incoming side가 아닌 건물 내에 설치되는 분기형 배전패널 내부의 전자식 전력량계 및 각종 통신(제어)설비를 보호할 목적으로 한전계통이 연계되는 MOF 단에 설치되는 LPZ0에 해당하는 피뢰기(LA, SA)와 보호협조를 이루는 LPZ1과 LPZ2의 경계영역에 설치하는 저압 배전계통용 II등급 서지보호장치(SPD)에 대해 설계를 하였다. 또한 감결합 요소가 없고, 부하 전류를 흘릴 수 있는 직렬 접속 방식의 1-포트 서지보호장치(SPD)에 대한 최적의 설계 방안을 도출하고 실험을 통해 기존의 방식과 비교하여 성능 개선과 관련한 검증을 실시하였다.

리튬이온 배터리의 사용 특성 분석을 위한 무선 모니터링 시스템 설계 (Design of a Wireless Monitoring System for Analyzing the Usage Characteristics of Lithium-ion Batteries)

  • 박재용;정양희;강성준
    • 한국전자통신학회논문지
    • /
    • 제19권5호
    • /
    • pp.1067-1074
    • /
    • 2024
  • 여수산업단지 등과 같은 대규모 생산설비에서는 다양한 감시 장치들이 가동되고 있고 이들 장치의 운전을 위한 전원 설비로써 열악한 환경에 대응하기 위한 저전력 리튬이온 배터리를 내장한 방호장치를 사용하고 있다. 본 연구에서는 이들 리튬이온 배터리의 사용 특성 분석을 위한 무선 모니터링 시스템을 설계, 구현하고 이들 시스템을 이용하여 배터리를 포함하는 방호장치의 온도, 습도 및 방호장치 내의 배터리 충방전에 의한 가스 발생과 배터리의 특성 변화를 무선으로 상시 모니터링 할 수 있도록 하였다. 이들 시스템을 통하여, 산업단지 내의 감시장치 등에 필요한 배터리의 안정적인 관리와 전원을 공급함으로써 공장 생산설비의 효율적인 운영과 관리 체계를 수립하는데 기여하고자 한다.

코로나19 의심 또는 확진 환자가 병원 밖 심정지 발생 시 구조자의 개인 보호장비(PPE) 착용에 의한 가슴압박 효과 비교 : 무작위 교차 시뮬레이션 연구 (Effect of level D personal protective equipment on chest compression for pre-hospital arrest patients with suspected or confirmed COVID-19 : A randomized crossover simulation trial)

  • 홍석환;양연수;한상균
    • 한국응급구조학회지
    • /
    • 제25권1호
    • /
    • pp.23-36
    • /
    • 2021
  • Purpose: The purpose of this study was to determine how the use of level D personal protective equipment (PPE) and cardiopulmonary resuscitation (CPR) feedback equipment affects chest compression (CC). Furthermore, this study provides basic data for developing Korean CPR guidelines that can be applied to patients with suspected or confirmed COVID-19. Methods: This randomized, single-blinded, crossover simulation trial included 26 student paramedics who performed 2-minute chest compressions using three different methods: Method A involved performing traditional CC for two minutes without donning level D PPE, Method B involved performing CC while donning level D PPE, and Method C involved performing CC with a CPR feedback device while donning level D PPE. Results: The use of a CPR feedback device during the 2-minute CC increased the exercise intensity of the subjects, but donning level D PPE didn't affect the quality of CC and the exercise intensity. The results of methods A and B showed changes in the quality of compression 80 seconds after the start of CC. No significant changes occurred in 2-minute CC when using the CPR feedback device. Conclusion: Using a CPR feedback device could prevent deterioration in the quality of CC while donning level D PPE.