• Title/Summary/Keyword: Protective Relay Resetting Area

Search Result 3, Processing Time 0.027 seconds

Development of An Expert System to Decide the Resetting Area of Protective Distance Relay in Power Transmission Systems (송전계통 보호 거리계전기 재정정 영역 판정 전문가시스템 개발)

  • 최면송;민병운;김기화;현승호;이승재
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.8
    • /
    • pp.437-443
    • /
    • 2003
  • In this paper an expert system is developed to decide the resetting area of protective devices in power transmission systems. A configuration change in power transmission networks from a substation extension such as new line or bus addition need resetting of protective devices around the point of configuration changes. To find the resetting area in complex power system is very difficult, especially when the distance protective relays are considered to be reset. The proposed expert system, in this paper to find the resetting area has many rules based on the changes of fault currents and apparent factors from the power system alteration. It solves the problem to find relay resetting area using the network information in the database and the rule-base. The case study shows a result of the problem to find relay resetting area in KEPCO system when there is any configuration change.

A Method of Preventing Blackout Caused by Relay (계전기 동작에 의한 광역정전 방지방안)

  • Jin, B.G.;Lee, S.J.;Kim, S.T.
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.7-8
    • /
    • 2007
  • This paper presents an vulnerability index for hidden failure of protective relays in transmission system. The bad influence can be quantized by an vulnerability index. When there is mis-operation, no-operation or mis-setting, power flow can be quantized by an index. According to the index, relays can be resetting. So the wide area blackout can be prevented.

  • PDF

Impact of hidden failure analysis of protective relay in transmission system (송전계통 보호계전기 취약도 평가)

  • Jin, Bo-Gun;Lee, Seung-Jae;Kim, S.-Tae;Lee, Dong-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2006.11a
    • /
    • pp.12-14
    • /
    • 2006
  • This paper presents an vulnerability index for hidden failure of protective relays in transmission system. The bad influence can be quantized by an vulnerability index. When there is mis-operation, no-operation or mis-setting, power flow can be quantized by an index. According to the index, relays can be resetting. So the wide area blackout can be prevented.

  • PDF