The Design of the DC traction Protection system and Device for the test line of Light Rail Transit (경전철 시험선로의 직류 보호시스템 및 보호계전기 설계)

  • Jeon, Y.J.;Kim, J.H.;Baek, B.S.;Kim, N.H.;Lee, B.S.;Ahn, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07b
    • /
    • pp.1229-1231
    • /
    • 2002
  • This paper presents the design of DC protection system of Light Rail Transit system. Especially, the composition and interface for DC Switchgear. Digital protection unit and sort of protection algorithm are focused. DC Switchgear (DCSWGR) for LRT testline consist of 5 different panels with peculiar characteristics are examined. Also Basic actuation principle for DC fault select relay (50F), Line Test Device (LTD), DC Overcurrent(OCR) relay are introduced.

  • PDF

Improved distance relay suitable for intertie protection of a wind farm considering Fault Ride-Through requirement (풍력단지의 Fault Ride-Through 기능을 위한 연계선 보호용 거리계전기의 성능향상 기법)

  • Kang, Yong-Cheol;Kang, Hae-Gweon;Zheng, Tai-Ying;Lee, Byung-Eun;Jang, Sung-Il;Kim, Yong-Gyun
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.442_443
    • /
    • 2009
  • A large wind farm should satisfy the requirements for a grid and accomplish the optimization of the wind farm system. In that point of view, the wind farm intertie protection system, which must consider the Fault Ride-Through (FRT) requirement for more reliable protection, should be improved. This paper proposes a modified distance relay suitable for protection of a wind farm intertie considering a FRT requirement. The frequency change is used to discriminate the intertie fault from a outside zone fault. The performance of the proposed algorithm is verified using a PSCAD/EMTDC simulator.

  • PDF

Development of Transmission Line Protection Relay Models for PSS/E (PSS/E용 송전선로 보호 계전기 모델 개발)

  • Kim, Jong-Wook;Kang, Sang-Hee;Lee, Dong-Gyu;Lee, Seong-Jin;Kwon, Seok-Kee
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.423-425
    • /
    • 2005
  • Te digital simulation of electric power system is a very important tool that can decide a proper protection systems from the design of the systems. Protection systems base on the wrong simulation results can cause a serious danger in the stability of the power system. So, the power system makes for simulation and the actual power system must be maximumly homologized. In this paper, protection relay models used in actual systems were developed in the PSS/E.

  • PDF

A Study on the Harmonics Effect of Disc-Type Over Current Ground Relay for Emergency Generator Protection (비상발전기 보호용 원판형 지락과전류계전기의 고조파영향에 관한 연구)

  • Kim, Kyung-Chul;Kho, Hun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.6
    • /
    • pp.58-62
    • /
    • 2015
  • When an emergency generator is running, it supplies the power for critical loads. Generator protection requires the consideration of many abnormal conditions that may occur with generators include overvoltages and ground faults. Modern day power systems create harmonics within the electrical network that can have an impact upon the associated protective system. This paper focuses on the analysing of the cause and development of a solution for the malfunction of induction disc type overcurrent ground relay by generation of harmonics during emergency generator operation.

Development of Current-based Compact Digital Protective Relay for Induction Motor Protection (중용량 전동기보호를 위한 전류형 디지털 보호계전기 개발)

  • Jung, Jong-Jin;Kim, Joong-Pyo;Shin, Jong-Han;Park, Jang-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.140-142
    • /
    • 2005
  • This paper describes the current- based compact digital motor protective relay for low and high voltage induction motors, which are widely used in industrial and commercial power systems. The existing protective relays for motor protection had only overload, short circuit, reverse phase, open circuit and grounding protective elements, and measurement, start/stop control function. But in present day, for automation system, various functions are required, especially motor management and sequence control function and more. To meet these requirements, we developed an economic current-based compact digital motor protective relay which had various function to control, manage and monitor the induction motor.

  • PDF

A Study on Distance Relay of Transmission with UPFC Using Artificial Neural Network (신경회로망을 이용한 UPFC가 연계된 송전선로의 거리계전기에 관한 연구)

  • Park, Jeong-Ho;Jung, Chang-Ho;Shin, Dong-Joon;Kim, Jin-O
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.196-198
    • /
    • 2002
  • This paper represents a new approach for the protective relay of power transmission lines using a Artificial Neural Network(ANN). A different fault on transmission lines need to be detected, classified and located accurately and cleared as fast as possible. However, The protection range of the distance relay is always designed on the basis of fixed settings, and unfortunately these approach do not have the ability to adapt dynamically to the system operating condition. ANN is suitable for the adaptive relaying and the detection of complex faults. The backpropagation algorithm based multi-layer perceptron is utilized for the learning process. It allows to make control to various protection functions. As expected, the simulation result demonstrate that this approach is useful and satisfactory.

  • PDF

A Percentage Current Differential Relay for Bus Protection Using a Compensation Algorithm Unaffected by a Remanent Flux (잔류자속에 무관한 보상 알고리즘을 적용한 모선보호용 전류차동 계전방식)

  • Kang, Yong-Cheol;Yun, Jae-Sung;Lim, Ui-Jai
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.308-310
    • /
    • 2003
  • This paper proposes a percentage current differential relaying algorithm for bus protection with a compensation algorithm of a CT. The compensating algorithm estimates the core flux at the start of the first saturation based on the value of the third-difference of the secondary current. It calculates the core flux and compensates distorted currents in accordance with the magnetization curve. The test results indicate that the algorithm can discriminate internal faults from external faults when the CT saturates. It can improve not only stability of the relay in the case of an external fault but sensitivity of the relay in the case of an internal fault.

  • PDF

Agent-Based Distance Relaying Algorithm for Phase-to-Ground Faults (에이전트 환경에서의 1선지락 거리계전 알고리즘)

  • Hyun, Seung-Ho;Jin, Bu-Gun;Lee, Seung-Jae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.11
    • /
    • pp.1885-1891
    • /
    • 2007
  • This paper presents a distance relaying algorithm for phase-to-ground faults in transmission lines under Multi-Agent protection environment. In normal condition, a distance relay agent stores the latest states, e.g., voltage of source side, voltage of the opposite side and the loading conditions, etc., through communication between the agents. Once a fault occurs, the relay calculates the fault location using the knowledge about the states just before the fault happens. This stand-alone operation is to improve reliability under the fault condition at which the accuracy or time required for communication may not be guaranteed. The mathematical expression of fault location is derived through loop analysis, before hand, in the manner that both fault current from the opposite end and fault resistance are included implicitly so that their effects are minimized. The suggested algorithm is applied to a typical transmission system with two power sources on both ends to show its effectiveness.

A Percentage Current Differential Relaying Algorithm for Bus Protection Using an Advanced Compensating Algorithm of the CTs (개선된 변류기 보상알고리즘을 적용한 모선보호용 비율전류차동 계전방식)

  • 강용철;윤재성;강상희
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.3
    • /
    • pp.158-164
    • /
    • 2003
  • This paper proposes a percentage current differential relaying algorithm for bus protection using an advanced compensating algorithm of the secondary current of current transformers (CTs). The compensating algorithm estimates the core flux at the start of the first saturation based on the value of the second-difference of the secondary current. Then, it calculates the core flux and compensates distorted currents using the magnetization curve. The algorithm Is unaffected by a remanent flux. The simulation results indicate that the proposed algorithm can discriminate internal faults from external faults when the CT saturates. This paper concludes by implementing the algorithm into a TMS320C6701 digital signal processor. The results of hardware implementation are also satisfactory. The proposed algorithm can improve not only stability of the relay in the case of an external fault but sensitivity of the relay in the case of an internal fault.

A Study on the Improvement of the Method for Implementing Protection Algorithm by using Component Object Model(COM) (컴포넌트 오브젝트 모델을 응용한 계전 알고리즘 구현방법의 개선에 관한 연구)

  • Park, In-Kwon;Yoon, Nam-Seon;An, Bok-Shin
    • Proceedings of the KIEE Conference
    • /
    • 1998.07c
    • /
    • pp.1210-1212
    • /
    • 1998
  • The complexity of newly developed protection algorithm and higher performance requested by the user makes the software embedded in the protective relay much harder to develop and maintain. The versatility of 32bit microprocessor and the availability of cheaper memory semiconductors introduced the fertile developing background for the protective relay developers. The use of component object model(COM) in the software developing process enables the developer to write much complex code in the easy and safe way and to maintain the code easily, too. And the aid of the COM library, the distributed computing environment will be expected to appear by the use of the COM programming model in the protective relay firmware program.